RDG204KN Room Thermostat RDG204KN
Siemens HVAC · Order number RDG204KN · Heating, Ventilation, Air Conditioning › Room Thermostats
Room Thermostat Controller
Download .knxprod RDG204KN 3.5 · 232 KB
Product
| Manufacturer | Siemens HVAC |
|---|---|
| Product name | RDG204KN Room Thermostat |
| Order number | RDG204KN |
| Hardware | HardwareEntry.0.1103 |
| Medium | Twisted Pair |
| Bus current (mA) | 5 |
| Rail mounted | Yes |
| Registration | Certified · 2022-05-02 |
| Languages | de-DE, en-US, fr-FR |
| Catalog entry | M-00FD_H-RDG204KN-1_HP-1103-35-306E_CI-RDG204KN-1 |
| Fingerprint | 306E |
| SHA-256 | cfa6ad551908a318ecbd4794152f38b3d74ca406bc5a95d53fc1562ccc06fc1b |
| First seen | 2026-11-25 |
| Markets | 66 markets |
Application program: RDG204KN 3.5
| Application number | $1103 |
|---|---|
| Version | 3.5 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 156 |
| Group objects | 118 |
Group objects (118)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | System time | Receive | 8 Bytes | 19.1 date time | CWU |
| 2 | Date | Receive | 3 Bytes | 11.1 date | CWU |
| 3 | Time of day | Receive | 3 Bytes | 10.1 time of day | CWU |
| 4 | Fault information | Send | 6 Bytes | 219.1 alarm info | CRT |
| 5 | Fault state (0=Normal/1=Fault) | Send | 1 Bit | 1.5 alarm | CRT |
| 6 | Fault transmission (0=Disable/1=Enable) | Receive | 1 Bit | 1.3 enable | CWU |
| 7 | Room operating mode: Preselection | Receive | 1 Byte | 20.102 HVAC mode | CWU |
| 8 | Room operating mode: Preselection | Send | 1 Byte | 20.102 HVAC mode | CRT |
| 9 | Room operating mode: Preselection Auto | Receive | 1 Bit | 1.17 trigger | CW |
| 10 | Room operating mode: Preselection Comfort | Receive | 1 Bit | 1.17 trigger | CW |
| 11 | Room operating mode: Preselection Economy | Receive | 1 Bit | 1.17 trigger | CW |
| 12 | Room operating mode: Preselection Protection | Receive | 1 Bit | 1.17 trigger | CW |
| 13 | Room operating mode: Scheduler | Receive | 1 Byte | 20.102 HVAC mode | CWU |
| 14 | Room operating mode: Scheduler Comfort | Receive | 1 Bit | 1.17 trigger | CW |
| 15 | Room operating mode: Scheduler Economy | Receive | 1 Bit | 1.17 trigger | CW |
| 16 | Room operating mode: Scheduler Protection | Receive | 1 Bit | 1.17 trigger | CW |
| 17 | Room operating mode state | Send | 1 Byte | 20.102 HVAC mode | CRT |
| 18 | Room operating mode state: Comfort | Send | 1 Bit | 1.11 state | CRT |
| 19 | Room operating mode state: Economy | Send | 1 Bit | 1.11 state | CRT |
| 20 | Room operating mode state: Protection | Send | 1 Bit | 1.11 state | CRT |
| 21 | Room temp: [P19] Heating setpoint Economy | Receive | 2 Bytes | 9.1 temperature (°C) | CW |
| 22 | Room temp: [P20] Cooling setpoint Economy | Receive | 2 Bytes | 9.1 temperature (°C) | CW |
| 23 | Room operating mode: Window contact (0=Close/1=Open) | Receive | 1 Bit | 1.19 window/door | CWU |
| 24 | Room operating mode: Presence detector (0=Unoccupied/1=Occupied) | Receive | 1 Bit | 1.18 occupancy | CWU |
| 25 | Room temp: Basic setpoint Comfort | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
| 26 | Room temp: Abs. setpoint Comfort | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
| 27 | Room temp: Abs. setpoint Comfort | Send | 2 Bytes | 9.1 temperature (°C) | CRT |
| 28 | Room temp: Current setpoint | Send | 2 Bytes | 9.1 temperature (°C) | CRT |
| 29 | Setpoint heating set | Receive | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CW |
| 30 | Setpoint cooling set | Receive | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CW |
| 31 | Setpoint heating set | Send | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CRT |
| 32 | Setpoint cooling set | Send | 8 Bytes | 275.100 Temperature setpoint setting for 4 HVAC Modes | CRT |
| 33 | Room temperature: Rel. setpoint Comfort | Receive | 2 Bytes | 9.2 temperature difference (K) | CWU |
| 34 | Room temperature: Rel. setpoint Comfort | Send | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 35 | Extended comfort mode state | Send | 1 Bit | 1.11 state | CRT |
| 36 | External room temperature value | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
| 37 | Built-in room temperature value | Send | 2 Bytes | 9.1 temperature (°C) | CRT |
| 38 | Frost alarm (0=Normal/1=Alarm) | Send | 1 Bit | 1.5 alarm | CRT |
| 39 | Heat alarm (0=Normal/1=Alarm) | Send | 1 Bit | 1.5 alarm | CRT |
| 40 | X1: Temperature [°C] | Send | 2 Bytes | 9.1 temperature (°C) | CRT |
| 41 | X1: Digital [0/1] | Send | 1 Bit | 1.1 switch | CRT |
| 42 | X2: Temperature [°C] | Send | 2 Bytes | 9.1 temperature (°C) | CRT |
| 43 | X2: Digital [0/1] | Send | 1 Bit | 1.1 switch | CRT |
| 44 | U1: Temperature [°C] | Send | 2 Bytes | 9.1 temperature (°C) | CRT |
| 45 | U1: Digital [0/1] | Send | 1 Bit | 1.1 switch | CRT |
| 46 | Heating/Cooling changeover (1=Heating/0=Cooling) | Receive | 1 Bit | 1.100 cooling/heating | CWU |
| 47 | Heating/Cooling mode state (1=Heating/0=Cooling) | Send | 1 Bit | 1.100 cooling/heating | CRT |
| 48 | Application mode | Receive | 1 Byte | 20.105 HVAC control mode | CWU |
| 49 | Dew point alarm (0=Normal/1=Alarm) | Receive | 1 Bit | 1.5 alarm | CWU |
| 50 | Enable fan command (0=Disable-Auto/1=Enable-Manual) | Receive | 1 Bit | 1.3 enable | CWU |
| 50 | Enable fan command, inverted (0=Enable-Manual/1=Disable-Auto) | Receive | 1 Bit | 1.3 enable | CWU |
| 51 | Fan operation (0=Auto/1=Manual) | Send | 1 Bit | 1.1 switch | CRT |
| 51 | Fan operation, inverted (0=Manual/1=Auto) | Send | 1 Bit | 1.1 switch | CRT |
| 52 | Fan speed | Receive | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 53 | Fan output | Send | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 54 | Fan speed 1 (0=Off/1=On) | Receive | 1 Bit | 1.1 switch | CWU |
| 55 | Fan speed 2 (0=Off/1=On) | Receive | 1 Bit | 1.1 switch | CWU |
| 56 | Fan speed 3 (0=Off/1=On) | Receive | 1 Bit | 1.1 switch | CWU |
| 57 | Fan speed 1 (0=Off/1=On) | Send | 1 Bit | 1.1 switch | CRT |
| 58 | Fan speed 2 (0=Off/1=On) | Send | 1 Bit | 1.1 switch | CRT |
| 59 | Fan speed 3 (0=Off/1=On) | Send | 1 Bit | 1.1 switch | CRT |
| 60 | Outside temperature | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
| 61 | Heating, control value continuous | Send | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 62 | Heating, control value continuous, seq 2 | Send | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 63 | Cooling, control value continuous | Send | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 64 | Cooling, control value continuous, seq 2 | Send | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 65 | Heating, control value state (0=Off/1=On) | Send | 1 Bit | 1.11 state | CRT |
| 66 | Heating, control value state seq 2 (0=Off/1=On) | Send | 1 Bit | 1.11 state | CRT |
| 67 | Cooling, control value state (0=Off/1=On) | Send | 1 Bit | 1.11 state | CRT |
| 68 | Cooling, control value state seq 2 (0=Off/1=On) | Send | 1 Bit | 1.11 state | CRT |
| 69 | Heating and cooling, control value state (0=Off/1=On) | Send | 1 Bit | 1.11 state | CRT |
| 70 | Heating and cooling, control value state seq2 (0=Off/1=On) | Send | 1 Bit | 1.11 state | CRT |
| 71 | Heating and cooling, control value continuous | Send | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 72 | Heating and cooling, control value continuous seq 2 | Send | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 73 | Control dehumidification (1=On/0=Off) | Send | 1 Bit | 1.11 state | CRT |
| 74 | Control humidification (1=On/0=Off) | Send | 1 Bit | 1.11 state | CRT |
| 75 | Hum. Control mode (inactive/hum/dehum) | Send | 1 Byte | 20.115 hum dehum mode | CRT |
| 76 | Enable electric heater (0=Disable/1=Enable) | Receive | 1 Bit | 1.3 enable | CWU |
| 77 | Built-in room relative humidity value [%r.H.] | Send | 2 Bytes | 9.7 humidity (%) | CRT |
| 78 | External room relative humidity value [%r.H.] | Receive | 2 Bytes | 9.7 humidity (%) | CWU |
| 79 | Room rel. humidity: Setpoint high | Receive | 2 Bytes | 9.7 humidity (%) | CWU |
| 80 | Room rel. humidity: Setpoint low | Receive | 2 Bytes | 9.7 humidity (%) | CWU |
| 81 | Reset energy efficiency state (Green leaf) | Receive | 1 Bit | 1.17 trigger | CWU |
| 82 | Energy efficiency state / Green Leaf (0=Green/1=Red) | Send | 1 Bit | 1.6 binary value | CRT |
| 83 | Enable/disable Leaf indication (0=Disable/1=Enable) | Receive | 1 Bit | 1.3 enable | CWU |
| 84 | Keypad: Lock fan speed | Receive | 1 Bit | 1.2 boolean | CWU |
| 85 | Keypad: Lock fan speed in “auto” mode | Receive | 1 Bit | 1.2 boolean | CWU |
| 86 | Keypad: Lock the setpoint shift | Receive | 1 Bit | 1.2 boolean | CWU |
| 87 | Keypad: Lock the operating mode | Receive | 1 Bit | 1.2 boolean | CWU |
| 88 | Room operating mode: Presence detector (0=Unoccupied/1=Occupied) | Send | 1 Bit | 1.18 occupancy | CRT |
| 89 | Room operating mode: Window contact (0=Close/1=Open) | Send | 1 Bit | 1.19 window/door | CRT |
| 90 | Room temp: Current Cooling setpoint | Send | 2 Bytes | 9.1 temperature (°C) | CRT |
| 91 | Room temp: Current heating setpoint | Send | 2 Bytes | 9.1 temperature (°C) | CRT |
| 92 | Room temp: Current heating setpoint | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
| 93 | Room temp: Current Cooling setpoint | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
| 94 | Room operating mode: State | Receive | 1 Byte | 20.102 HVAC mode | CWU |
| 95 | Changeover water state (1=Heating/0=Cooling) | Send | 1 Bit | 1.100 cooling/heating | CRT |
| 96 | Changeover water state (1=Heating/0=Cooling) | Receive | 1 Bit | 1.100 cooling/heating | CWU |
| 97 | Manual fan command | Send | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 98 | DC Fan speed: [P359] Maximum speed heating | Receive | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 99 | DC Fan speed: [P360] Maximum speed cooling | Receive | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 100 | Built-in room air quality value | Send | 2 Bytes | 9.8 parts/million (ppm) | CRT |
| 101 | External room air quality value | Receive | 2 Bytes | 9.8 parts/million (ppm) | CWU |
| 102 | Damper demand [%] | Send | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 103 | Damper demand (0=Off/1=On) | Send | 1 Bit | 1.1 switch | CRT |
| 104 | PICV:Heating maximal position | Receive | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 105 | PICV:Cooling maximal position | Receive | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 106 | Room rel. humidity: Setpoint high Eco | Receive | 2 Bytes | 9.7 humidity (%) | CWU |
| 107 | [P023] Room air quality: Setpoint [ppm] | Receive | 2 Bytes | 9.8 parts/million (ppm) | CWU |
| 108 | [P455] Minimum damper position [%] | Receive | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 109 | [P457] Maximum damper position [%] | Receive | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 110 | Heating/cooling state | Send | 1 Byte | 20.105 HVAC control mode | CRT |
| 111 | [P13] Comfort Setpoint minimum | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
| 112 | [P14] Comfort Setpoint maximum heating | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
| 113 | [P15] Comfort Setpoint minimum cooling | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
| 114 | [P16] Comfort Setpoint maximum | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
| 115 | Room temp: Heating setpoint Comfort | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
| 116 | Room temp: Cooling setpoint Comfort | Receive | 2 Bytes | 9.1 temperature (°C) | CWU |
Parameters (145)
| Parameter | Type | Default |
|---|---|---|
| [DIP] Plant type | list | --- |
| [P350] Fan control | list | Enabled |
| [P453] Air damper | list | DC 0...10 V (U1) |
| [P001] Control sequence | list | Cooling only |
| [P001] Control sequence | list | Heating and cooling |
| [P201] Output Y1 (and Y3 for 3-pos.) | list | On/off |
| [P203] Output Y2 (and Y4 for 3-pos.) | list | On/off |
| [P204] Output Y3 | list | On/off |
| [P205] Output Y4 | list | On/off |
| [P150] Input X1 | list | Room / Return temperature |
| [P153] Input X2 | list | --- |
| [P155] Input U1 | list | --- |
| [P450] Control strategy | list | Temperature (T) + Air quality (IAQ) |
| [P258] Manager / Subordinate | list | Manager |
| Preselection reception: Com. Obj | list | --- |
| Scheduler reception: Com. Obj | list | --- |
| State transmission: Com. Obj | list | --- |
| Room temperature: Economy Setpoint | list | As parameters only |
| Window state input | list | Local |
| Presence detector input | list | Local |
| Room temperature: Comfort Basic Setpoint | list | Disabled |
| Room temperature: Comfort Setpoint | list | Disabled |
| Room temperature: Current Setpoint | list | Disabled |
| Room temperature: Setpoint sets, receive | list | Disabled |
| Room temperature: Setpoint sets, send | list | Disabled |
| State Object for extended comfort mode | list | Yes |
| Frost Alarm | list | Disabled |
| Overheating alarm | list | Disabled |
| Application mode input | list | Disabled |
| Dewpoint alarm | list | Disabled |
| Humidity setpoints | list | As parameters only |
| [P259] Subordinate identification | list | 1 |
| [P450] Control strategy | list | Temp. (T) + Air quality (IAQ) |
| [P005] Scheduler | list | Disabled |
| [P002] Operation via room operating mode selector | list | Auto - Comfort - Protection |
| [P002] Operation via room operating mode selector | list | Auto - Protection |
| [P003] Operation via fan operating selector | list | Auto - Manual |
| [P003] Operation via fan operating selector | list | Forced ventilation |
| [P004] Unit | list | Degrees Celsius |
| [P008] Standard display | list | Room temperature |
| [P009] Additional display information | list | --- |
| [P017] Summer time | list | Europe |
| [P028] Keypad | list | Unlocked |
| [P030] Buzzer function | list | Enabled |
| [P031] Language | list | English |
| [P032] Room operating mode holidays | list | Economy |
| [P500] NFC | list | Enabled |
| [P502] Password | list | Disabled |
| [P503] Password | unsignedInt 0…999 | 0 |
| [P910] Transformation Precomfort | list | Economy |
| Presence detector function | list | Standard |
| [P102] Temporary Comfort mode [min] | list | ------ |
| [P010] Setpoint concept | list | Comfort concept |
| [P011] Comfort basic setpoint [°C] | list | 21.0°C |
| [P104] Setpoint display | list | Absolute setpoints |
| [P019] Economy heating setpoint [°C] | list | 15.0°C |
| [P020] Economy cooling setpoint [°C] | list | 30.0°C |
| [P100] Protection heating setpoint [°C] | list | 8.0°C |
| [P101] Protection cooling setpoint [°C] | list | ------- |
| [P013] Comfort setpoint minimum [°C] | list | 5.0°C |
| [P016] Comfort setpoint maximum [°C] | list | 35.0°C |
| [P014] Comfort setpoint maximum Heating [°C] | list | 21.0°C |
| [P015] Comfort setpoint minimum Cooling [°C] | list | 25.0°C |
| [P103] Temporary Comfort setpoint | list | Disabled |
| [P451] Humidity control strategy | list | With setpoint shift + external equipment (humid / dehum) |
| [P461] Temp setpoint shift (humidity) [K] | list | 3.0 K |
| [P024] Humidity setpoint high [%] | list | 50% |
| [P025] Humidity setpoint high Eco [%] | list | ------- |
| [P026] Humidity setpoint low [%] | list | ------- |
| [P023] Indoor air quality setpoint | list | 1000 ppm |
| [P454] Indoor air quality damper P-band Xp | list | 400 ppm |
| [P456] Indoor air quality fan P-band Xp | list | 400 ppm |
| [P109] Outside damper frost protection | list | ------- |
| [P351] Fan speeds | list | DC 0...10 V (DC fan) |
| [P455] Minimum damper position [%] | unsignedInt 0…100 | 0 |
| [P457] Maximum damper position [%] | unsignedInt 0…100 | 100 |
| [P458] Fan during damper control | list | Enabled |
| [P027] Electric heater when cooling | list | Enabled |
| [P200] Number of heating / cooling sequences | list | 2 sequence heating, 2 sequence cooling |
| [P050] Heating P-band Xp [K] | list | 2.0 K |
| [P057] Integral action time Tn heating [minutes] | unsignedInt 0…120 | 45 |
| [P052] Cooling P-band Xp [K] | list | 1.0 K |
| [P058] Integral action time Tn cooling [minutes] | unsignedInt 0…120 | 45 |
| [P051] Switching differential heating [K] | list | 1.0 K |
| [P053] Switching differential cooling [K] | list | 1.0 K |
| [P055] Dead zone Comfort mode [K] | list | 2.0 K |
| [P056] Setpoint differential [K] | list | 2.0 K |
| [P054] Radiator P-band Xp/switching differential [K] | list | 2.0 K |
| [P059] H/C changeover switching point cooling [°C] | list | 16.0°C |
| [P060] H/C changeover switching point heating [°C] | list | 28.0°C |
| [P061] Return temp limit delta cool | list | ------- |
| [P062] Return temp limit delta heat | list | ------- |
| [P063] Minimum supply air temperature [°C] | list | ------- |
| [P064] Maximum supply air temperature [°C] | list | ------- |
| [P110] Energy indicator | list | Green and Red dimmed out |
| [P111] Energy indicator range [K] | list | 2.0 K |
| [P250] Valve kick | list | Disabled |
| [P251] Purge time (every 2 hours) [minutes] | list | ------- |
| [P252] Flow temp limit floor heating [°C] | list | 28.0°C |
| [P254] Swap sequence H and C (2-pipe/2-stage) | list | Disabled |
| [P255] Track cooling setpoint on outside temperature | list | Disabled |
| Threshold for frost alarm [°C] | list | 5.0°C |
| Threshold value overheating [°C] | list | 40.0°C |
| [P006] Measured value correction [K] | list | 0.0 K |
| [P007] Humidity value correction [%] | list | 0% |
| [P151] Sensor input X1 | list | NTC 3K |
| [P151] Normal position X1 | list | Open |
| [P151] Normal position or sensor input X1 | list | NTC 3K |
| [P154] Sensor input X2 | list | NTC 3K |
| [P154] Normal position X2 | list | Open |
| [P154] Normal position or sensor input X2 | list | Open |
| [P156] Sensor input U1 | list | NTC 3K |
| [P156] Normal position U1 | list | Open |
| [P156] Normal position or sensor input U1 | list | Open |
| [P206] PWM algorithm cycle Y1 [seconds] | unsignedInt 20…3600 | 1200 |
| [P207] PWM algorithm cycle Y2 [seconds] | unsignedInt 20…3600 | 1200 |
| [P208] PWM algorithm cycle Y3 [seconds] | unsignedInt 20…3600 | 1200 |
| [P209] PWM algorithm cycle Y4 [seconds] | unsignedInt 20…3600 | 1200 |
| [P210] On time minimum PWM output [%] | unsignedInt 1…20 | 5 |
| [P211] Off time minimum PWM output [%] | unsignedInt 1…20 | 5 |
| [P212] On time minimum 2-pos output [minutes] | unsignedInt 1…20 | 1 |
| [P213] Off time minimum 2-pos output [minutes] | unsignedInt 1…20 | 1 |
| [P214] Actuator run time Y1 and Y3 for 3-pos [seconds] | unsignedInt 20…300 | 150 |
| [P215] Actuator run time Y2 and Y4 for 3-pos [seconds] | unsignedInt 20…300 | 150 |
| [P400] Output Q1 function | list | --- |
| [P401] Output Q2 function | list | --- |
| [P402] Output Q3 function | list | --- |
| [P352] Fan overrun time [seconds] | unsignedInt 0…360 | 60 |
| [P029] Fan: Dead zone Comfort mode | list | Off |
| [P353] Fan speed switching point low (value in %) | unsignedInt 1…100 | 10 |
| [P361] Fan start kick | list | Enabled |
| [P354] Fan speed switching point med (value in %) | unsignedInt 1…100 | 65 |
| [P355] Fan speed switching point high (value in %) | unsignedInt 1…100 | 100 |
| [P356] DC fan switching point [%] | unsignedInt 1…100 | 10 |
| [P357] DC fan speed low min. output [%] | unsignedInt 1…100 | 30 |
| [P358] DC fan speed med. output [%] | unsignedInt 1…100 | 60 |
| [P359] DC fan speed high max. out. heat [%] | unsignedInt 1…100 | 80 |
| [P360] DC fan speed high max. out. cool [%] | unsignedInt 1…100 | 80 |
| [P362] On time minimum fan [minutes] | unsignedInt 1…6 | 2 |
| [P363] Periodic fan kick Comfort [minutes] | list | ------- |
| [P364] Periodic fan kick Economy [minutes] | list | ------- |
| [P365] Fan start delay [seconds] | unsignedInt 0…360 | 0 |
| [P366] Fan start, minimum hot water temperature [°C] | list | 30.0°C |
| [P501] Service filter [hour] | list | ------- |
| Fan operation | list | 0=Auto/1=Manual |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| RDG204KN 3.5 latest | $1103 | 306E | 2026-11-25 | 232 KB | Download |
About this file
This is the official ETS product database for the Siemens HVAC RDG204KN Room Thermostat (RDG204KN), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Siemens HVAC
- AQR2570N Flush Mount Sensor AQR2570N
- AQR2576N Flush Mount Sensor AQR2576N
- GDB111.1E/KN Damper actuator GDB111.1E/KN
- GDB111.9E/KN Rotary actuator GDB111.9E/KN
- GDB181.1E/KN VAV Compact Controller GDB181.1E/KN
- GLB111.1E/KN Damper actuator GLB111.1E/KN
- GLB111.9E/KN Rotary actuator GLB111.9E/KN
- GLB181.1E/KN VAV Compact Controller GLB181.1E/KN
- QAW740 Room Unit QAW740
- QMX3.P02 Room Unit QMX3.P02
- QMX3.P30 Room Unit QMX3.P30
- QMX3.P34 Room Unit QMX3.P34