Siemens HVAC QMX6.P74 QMX6.P74 Room Unit

QMX6.P74 Room Unit QMX6.P74

Siemens HVAC · Order number QMX6.P74 · Heating, Ventilation, Air Conditioning › Room Operating Units & Display Units › QMX6 Room Units/Sensors

QMX6.P74 Room Unit

Download .knxprod QMX6.P74 1.1 · 962 KB

Product

ManufacturerSiemens HVAC
Product nameQMX6.P74 Room Unit
Order numberQMX6.P74
HardwareHardwareEntry.0.9204
MediumTwisted Pair
Bus current (mA)15
Rail mountedNo
RegistrationCertified · 2024-12-17
Languagesde-DE, en-US, fr-FR, sv-SE, es-ES, it-IT
Catalog entryM-00FD_H-QMX6.5FP74-1_HP-9204-11-D6F7_CI-QMX6.2EP74-1
FingerprintD6F7
SHA-2569458fc29b86087d74721aae0740589fdca7a7dcad60ee5b8788b6b65905e297a
First seen2026-11-25
Markets66 markets

Application program: QMX6.P74 1.1

Application number$9204
Version1.1
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters1130
Group objects349
Group objects (349)
NoNameFunctionSizeDPTFlags
1Status device functionOk/Defect1 Bit1.5 alarmCRT
2Send status valuesrequest1 Bit1.17 triggerCW
3Operation, locklocking1 Bit1.3 enableCW
13Temperature sensor, temperature value°C value2 Bytes9.1 temperature (°C)CRT
15Humidity sensor, relative humidity% r.h. value1 Byte5.4 percentage (0..255%)CRT
16Humidity sensor, relative humidity% r.h. value2 Bytes9.7 humidity (%)CRT
17Humidity sensor, fault1 = Failure1 Bit1.5 alarmCRT
19CO2 sensor, CO2 valueppm value2 Bytes7.1 pulsesCRT
20CO2 sensor, CO2 valueppm value2 Bytes9.8 parts/million (ppm)CRT
21CO2 sensor, failure1 = Failure1 Bit1.5 alarmCRT
22Temperature control, controllerOn/Off1 Bit1.1 switchCW
23Temperature control, controller statusOn/Off1 Bit1.11 stateCRT
24Temperature control, room mode (automatic operation)1 … 41 Byte20.102 HVAC modeCW
25Temperature control, room mode (manual operation)0 … 41 Byte20.102 HVAC modeCW
26Temperature control, room operating mode, automatic modeOn1 Bit1.1 switchCW
27Temperature control, room operating mode (manual operation), comfort modeOn1 Bit1.1 switchCW
28Temperature control, room operating mode (manual operation), standby modeOn1 Bit1.1 switchCW
29Temperature control, room operating mode (manual operation), economy modeOn1 Bit1.1 switchCW
30Temperature control, room operating mode (manual operation), protection modeOn1 Bit1.1 switchCW
31Temperature control, status of room mode (manual operation)0 … 41 Byte20.102 HVAC modeCRT
32Temperature control, status of room operating mode, automatic modeOn/Off1 Bit1.11 stateCRT
33Temperature control, status of room operating mode (manual operation), comfort modeOn/Off1 Bit1.11 stateCRT
34Temperature control, status of room operating mode (manual operation), standby modeOn/Off1 Bit1.11 stateCRT
35Temperature control, status of room operating mode (manual operation), economy modeOn/Off1 Bit1.11 stateCRT
36Temperature control, status of room operating mode (manual operation), protection modeOn/Off1 Bit1.11 stateCRT
37Temperature control, room mode status1 … 41 Byte20.102 HVAC modeCRT
38Temperature control, comfort extension0 = Stop/1 = Start1 Bit1.10 start/stopCW
39Temperature control, comfort extension statusOn/Off1 Bit1.11 stateCRT
40Temperature control, permanent protection modeOn/Off1 Bit1.1 switchCWTU
41Temperature control, actual temperature value°C value2 Bytes9.1 temperature (°C)CWTU
42Temperature control, heat alarm0 = No alarm/1 = Alarm1 Bit1.5 alarmCRT
43Temperature control, frost alarm0 = No alarm/1 = Alarm1 Bit1.5 alarmCRT
44Temperature control, status error actual temperature value1 = Failure1 Bit1.2 booleanCRT
45Temperature control, window contact status0 = closed/1 = open1 Bit1.19 window/doorCRT
46Temperature control, dew point alert0 = No alarm/1 = Alarm1 Bit1.5 alarmCWTU
47Temperature control, dew point alarm status0 = No alarm/1 = Alarm1 Bit1.5 alarmCRT
48Temperature control, presenceOn/Off1 Bit1.18 occupancyCWTU
49Temperature control, window 10 = closed/1 = open1 Bit1.19 window/doorCWTU
50Temperature control, window 20 = closed/1 = open1 Bit1.19 window/doorCWTU
51Temperature control, window 30 = closed/1 = open1 Bit1.19 window/doorCWTU
52Temperature control, window 40 = closed/1 = open1 Bit1.19 window/doorCWTU
53Temperature control, outside temperature°C value2 Bytes9.1 temperature (°C)CW
54Temperature control, status error ambient temperature1 = Failure1 Bit1.2 booleanCRT
55Temperature control, controller mode0 = cooling/1 = heating1 Bit1.100 cooling/heatingCWTU
56Temperature control, basic setpoint°C value2 Bytes9.1 temperature (°C)CW
57Temperature control, setpoint offsetK value2 Bytes9.2 temperature difference (K)CW
58Temperature control, setpoint, comfort mode°C value2 Bytes9.1 temperature (°C)CW
59Temperature control, heating setpoint, comfort mode°C value2 Bytes9.1 temperature (°C)CW
60Temperature control, heating setpoint, standby mode°C value2 Bytes9.1 temperature (°C)CW
61Temperature control, heating setpoint, economy mode°C value2 Bytes9.1 temperature (°C)CW
62Temperature control, heating setpoint, protection mode°C value2 Bytes9.1 temperature (°C)CW
63Temperature control, heating setpoints (°C)°C value8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCRW
64Temperature control, object heating setpoint shifts (K)°C value8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCW
65Temperature control, cooling setpoint, comfort mode°C value2 Bytes9.1 temperature (°C)CW
66Temperature control, cooling setpoint, standby mode°C value2 Bytes9.1 temperature (°C)CW
67Temperature control, cooling setpoint, economy mode°C value2 Bytes9.1 temperature (°C)CW
68Temperature control, cooling setpoint, protection mode°C value2 Bytes9.1 temperature (°C)CW
69Temperature control, cooling setpoint (°C)°C value8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCRW
70Temperature control, object cooling setpoint shifts (K)°C value8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCW
71Temperature control, status of current basic setpoint°C value2 Bytes9.1 temperature (°C)CRT
72Temperature control, setpoint offset statusK value2 Bytes9.2 temperature difference (K)CRT
73Temperature control, status of effective setpoint, comfort mode°C value2 Bytes9.1 temperature (°C)CRT
74Temperature control, status of current setpoint°C value2 Bytes9.1 temperature (°C)CRT
75Temperature control, status of effective cooling setpoint°C value2 Bytes9.1 temperature (°C)CRT
76Temperature control, status of effective cooling setpoint, comfort mode°C value2 Bytes9.1 temperature (°C)CRT
77Temperature control, status of effective cooling setpoint, pre-comfort mode°C value2 Bytes9.1 temperature (°C)CRT
78Temperature control, status of effective cooling setpoint, economy mode°C value2 Bytes9.1 temperature (°C)CRT
79Temperature control, status of effective cooling setpoint, protection mode°C value2 Bytes9.1 temperature (°C)CRT
80Temperature control, status of effective heating setpoint°C value2 Bytes9.1 temperature (°C)CRT
81Temperature control, status of effective heating setpoint, comfort mode°C value2 Bytes9.1 temperature (°C)CRT
82Temperature control, status of effective heating setpoint, pre-comfort mode°C value2 Bytes9.1 temperature (°C)CRT
83Temperature control, status of effective heating setpoint, economy mode°C value2 Bytes9.1 temperature (°C)CRT
84Temperature control, status of effective heating setpoint, protection mode°C value2 Bytes9.1 temperature (°C)CRT
85Temperature control, status of effective cooling setpoints°C value8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCRT
86Temperature control, status of effective heating setpoints°C value8 Bytes275.100 Temperature setpoint setting for 4 HVAC ModesCRT
87Temperature control, temperature limitation heating mode, actual temperature value°C value2 Bytes9.1 temperature (°C)CWTU
88Temperature control, temperature limitation heating mode, status error actual temperature value1 = Failure1 Bit1.2 booleanCRT
89Temperature control, temperature limitation in heating mode, statusOn/Off1 Bit1.11 stateCRT
90Temperature control, cooling, control value switchingOn/Off1 Bit1.1 switchCRT
91Temperature control, cooling, control value switching (sequence 2)On/Off1 Bit1.1 switchCRT
92Temperature control, heating, control value switchingOn/Off1 Bit1.1 switchCRT
92Temperature control, heating/cooling, control value switchingOn/Off1 Bit1.1 switchCRT
93Temperature control, heating/cooling, control value switching (sequence 2)On/Off1 Bit1.1 switchCRT
93Temperature control, heating, control value switching (sequence 2)On/Off1 Bit1.1 switchCRT
94Temperature control, cooling, control value steady0...100 %1 Byte5.1 percentage (0..100%)CRT
95Temperature control, cooling, control value steady (sequence 2)0...100 %1 Byte5.1 percentage (0..100%)CRT
96Temperature control, heating/cooling, control value steady0...100 %1 Byte5.1 percentage (0..100%)CRT
96Temperature control, heating, control value steady0...100 %1 Byte5.1 percentage (0..100%)CRT
97Temperature control, heating/cooling, control value steady (sequence 2)0...100 %1 Byte5.1 percentage (0..100%)CRT
97Temperature control, heating, control value steady (sequence 2)0...100 %1 Byte5.1 percentage (0..100%)CRT
98Temperature control, ventilator mode0 = automatic operation/1 = manual operation1 Bit1.3 enableCW
99Temperature control, ventilator speed (manual operation)0...100 %1 Byte5.1 percentage (0..100%)CW
100Temperature control, ventilator level (manual operation)0 … 31 Byte5.100 fan stage (0..255)CW
101Temperature control, ventilator mode status0 = automatic operation/1 = manual operation1 Bit1.3 enableCRT
102Temperature control, ventilation, control value for manual operation0...100 %1 Byte5.1 percentage (0..100%)CRT
103Temperature control, ventilation, current control value0...100 %1 Byte5.1 percentage (0..100%)CRT
104Temperature control, controller mode status0 = cooling/1 = heating1 Bit1.100 cooling/heatingCRT
105Temperature control, collective status (RTSM)8-bit status1 Byte21.107 combined status RTSMCRT
106Temperature control, collective status (RTC)16-bit status2 Bytes22.103 combined status RTCCRT
108Temperature control, controller status (RHCC)16-bit status2 Bytes22.101 RHCC statusCRT
109Temperature control, controller status (DPT_HVACContrMode)8-bit status1 Byte20.105 HVAC control modeCRT
110Temperature control, Status presenceOn/Off1 Bit1.18 occupancyCRT
111Humidity controller, controllerOn/Off1 Bit1.1 switchCRWT
112Humidity controller, actual humidity value% r.h. value2 Bytes9.7 humidity (%)CW
113Humidity controller, steady control signal – manual setpoint0...100 %1 Byte5.1 percentage (0..100%)CRWT
114Humidity controller, steady control signal – manual mode0 = auto/1 = manual1 Bit1.3 enableCRWT
114Humidity controller, steady control signal – manual mode1 = auto/0 = manual1 Bit1.3 enableCRWT
115Humidity controller, override0 = normal/1 = overridden1 Bit1.3 enableCRWT
116Humidity controller, switching point level 1% r.h. value2 Bytes9.7 humidity (%)CWT
116Humidity controller, setpoint% r.h. value2 Bytes9.7 humidity (%)CWT
117Humidity controller, switching point level 2% r.h. value2 Bytes9.7 humidity (%)CWT
118Humidity controller, switching point level 3% r.h. value2 Bytes9.7 humidity (%)CWT
119Humidity controller, switching point level 4% r.h. value2 Bytes9.7 humidity (%)CWT
120Humidity controller, switching point level 5% r.h. value2 Bytes9.7 humidity (%)CWT
121Humidity controller, status humidity setpoint% r.h. value2 Bytes9.7 humidity (%)CRT
121Humidity controller, status switching point level 1% r.h. value2 Bytes9.7 humidity (%)CRT
122Humidity controller, status switching point level 2% r.h. value2 Bytes9.7 humidity (%)CRT
123Humidity controller, status switching point level 3% r.h. value2 Bytes9.7 humidity (%)CRT
124Humidity controller, status switching point level 4% r.h. value2 Bytes9.7 humidity (%)CRT
125Humidity controller, status switching point level 5% r.h. value2 Bytes9.7 humidity (%)CRT
126Humidity controller, minimum control value0...100 %1 Byte5.1 percentage (0..100%)CRWT
127Humidity controller, maximum control value0...100 %1 Byte5.1 percentage (0..100%)CRWT
128Humidity controller, steady control signal% value1 Byte5.1 percentage (0..100%)CRT
129Humidity controller, control signal level 1On/Off1 Bit1.1 switchCRT
130Humidity controller, control signal level 2On/Off1 Bit1.1 switchCRT
131Humidity controller, control signal level 3On/Off1 Bit1.1 switchCRT
132Humidity controller, control signal level 4On/Off1 Bit1.1 switchCRT
133Humidity controller, control signal level 5On/Off1 Bit1.1 switchCRT
134Air quality controller, controllerOn/Off1 Bit1.1 switchCRWT
135Air quality controller, actual CO2 valueppm value2 Bytes9.8 parts/million (ppm)CW
136Air quality controller, steady control signal – manual setpoint0...100 %1 Byte5.1 percentage (0..100%)CRWT
137Air quality controller, steady control signal – manual mode0 = auto/1 = manual1 Bit1.3 enableCRWT
137Air quality controller, steady control signal – manual mode1 = auto/0 = manual1 Bit1.3 enableCRWT
138Air quality controller, override0 = normal/1 = overridden1 Bit1.3 enableCRWT
139Air quality controller, setpointppm value2 Bytes9.8 parts/million (ppm)CWT
139Air quality controller, switching point level 1ppm value2 Bytes9.8 parts/million (ppm)CWT
140Air quality controller, switching point level 2ppm value2 Bytes9.8 parts/million (ppm)CWT
141Air quality controller, switching point level 3ppm value2 Bytes9.8 parts/million (ppm)CWT
142Air quality controller, switching point level 4ppm value2 Bytes9.8 parts/million (ppm)CWT
143Air quality controller, switching point level 5ppm value2 Bytes9.8 parts/million (ppm)CWT
144Air quality controller, status switching point level 1ppm value2 Bytes9.8 parts/million (ppm)CRT
144Air quality controller, air quality status setpointppm value2 Bytes9.8 parts/million (ppm)CRT
145Air quality controller, status switching point level 2ppm value2 Bytes9.8 parts/million (ppm)CRT
146Air quality controller, status switching point level 3ppm value2 Bytes9.8 parts/million (ppm)CRT
147Air quality controller, status switching point level 4ppm value2 Bytes9.8 parts/million (ppm)CRT
148Air quality controller, status switching point level 5ppm value2 Bytes9.8 parts/million (ppm)CRT
149Air quality controller, minimum control value0...100 %1 Byte5.1 percentage (0..100%)CRWT
150Air quality controller, maximum control value0...100 %1 Byte5.1 percentage (0..100%)CRWT
151Air quality controller, steady control signal% value1 Byte5.1 percentage (0..100%)CRT
152Air quality controller, control signal level 1On/Off1 Bit1.1 switchCRT
153Air quality controller, control signal level 2On/Off1 Bit1.1 switchCRT
154Air quality controller, control signal level 3On/Off1 Bit1.1 switchCRT
155Air quality controller, control signal level 4On/Off1 Bit1.1 switchCRT
156Air quality controller, control signal level 5On/Off1 Bit1.1 switchCRT
157Calculator 1, temperature value 1°C value2 Bytes9.1 temperature (°C)CW
157Calculator 1, relative humidity 1% r.h. value2 Bytes9.7 humidity (%)CW
157Calculator 1, CO2 value 1ppm value2 Bytes9.8 parts/million (ppm)CW
157Calculator 1​, brightness value 1value in LUX2 Bytes9.4 lux (Lux)CW
157Calculator 1, % value 1% value1 Byte5.1 percentage (0..100%)CW
158Calculator 1, relative humidity 2% r.h. value2 Bytes9.7 humidity (%)CW
158Calculator 1, temperature value 2°C value2 Bytes9.1 temperature (°C)CW
158Calculator 1​, brightness value 2value in LUX2 Bytes9.4 lux (Lux)CW
158Calculator 1, % value 2% value1 Byte5.1 percentage (0..100%)CW
158Calculator 1, CO2 value 2ppm value2 Bytes9.8 parts/million (ppm)CW
159Calculator 1, % value 3% value1 Byte5.1 percentage (0..100%)CW
159Calculator 1, temperature value 3°C value2 Bytes9.1 temperature (°C)CW
159Calculator 1, relative humidity 3% r.h. value2 Bytes9.7 humidity (%)CW
159Calculator 1, CO2 value 3ppm value2 Bytes9.8 parts/million (ppm)CW
159Calculator 1​, brightness value 3value in LUX2 Bytes9.4 lux (Lux)CW
160Calculator 1, relative humidity 4% r.h. value2 Bytes9.7 humidity (%)CW
160Calculator 1, CO2 value 4ppm value2 Bytes9.8 parts/million (ppm)CW
160Calculator 1, % value 4% value1 Byte5.1 percentage (0..100%)CW
160Calculator 1​, brightness value 4value in LUX2 Bytes9.4 lux (Lux)CW
160Calculator 1, temperature value 4°C value2 Bytes9.1 temperature (°C)CW
161Calculator 1​, brightness value 5value in LUX2 Bytes9.4 lux (Lux)CW
161Calculator 1, temperature value 5°C value2 Bytes9.1 temperature (°C)CW
161Calculator 1, relative humidity 5% r.h. value2 Bytes9.7 humidity (%)CW
161Calculator 1, CO2 value 5ppm value2 Bytes9.8 parts/million (ppm)CW
161Calculator 1, % value 5% value1 Byte5.1 percentage (0..100%)CW
162Calculator 1, relative humidity 6% r.h. value2 Bytes9.7 humidity (%)CW
162Calculator 1, % value 6% value1 Byte5.1 percentage (0..100%)CW
162Calculator 1​, brightness value 6value in LUX2 Bytes9.4 lux (Lux)CW
162Calculator 1, temperature value 6°C value2 Bytes9.1 temperature (°C)CW
162Calculator 1, CO2 value 6ppm value2 Bytes9.8 parts/million (ppm)CW
163Calculator 1​, brightness, resultvalue in LUX2 Bytes9.4 lux (Lux)CRT
163Calculator 1​, humidity, result% r.h. value2 Bytes9.7 humidity (%)CRT
163Calculator 1​, CO2, resultppm value2 Bytes9.8 parts/million (ppm)CRT
163Calculator 1​, %, result% value1 Byte5.1 percentage (0..100%)CRT
163Calculator 1​, temperature, result°C value2 Bytes9.1 temperature (°C)CRT
164Calculator 2, CO2 value 1ppm value2 Bytes9.8 parts/million (ppm)CW
164Calculator 2​, brightness value 1value in LUX2 Bytes9.4 lux (Lux)CW
164Calculator 2, temperature value 1°C value2 Bytes9.1 temperature (°C)CW
164Calculator 2, relative humidity 1% r.h. value2 Bytes9.7 humidity (%)CW
164Calculator 2, % value 1% value1 Byte5.1 percentage (0..100%)CW
165Calculator 2, % value 2% value1 Byte5.1 percentage (0..100%)CW
165Calculator 2​, brightness value 2value in LUX2 Bytes9.4 lux (Lux)CW
165Calculator 2, temperature value 2°C value2 Bytes9.1 temperature (°C)CW
165Calculator 2, relative humidity 2% r.h. value2 Bytes9.7 humidity (%)CW
165Calculator 2, CO2 value 2ppm value2 Bytes9.8 parts/million (ppm)CW
166Calculator 2, relative humidity 3% r.h. value2 Bytes9.7 humidity (%)CW
166Calculator 2, CO2 value 3ppm value2 Bytes9.8 parts/million (ppm)CW
166Calculator 2, % value 3% value1 Byte5.1 percentage (0..100%)CW
166Calculator 2, temperature value 3°C value2 Bytes9.1 temperature (°C)CW
166Calculator 2​, brightness value 3value in LUX2 Bytes9.4 lux (Lux)CW
167Calculator 2, % value 4% value1 Byte5.1 percentage (0..100%)CW
167Calculator 2​, brightness value 4value in LUX2 Bytes9.4 lux (Lux)CW
167Calculator 2, temperature value 4°C value2 Bytes9.1 temperature (°C)CW
167Calculator 2, relative humidity 4% r.h. value2 Bytes9.7 humidity (%)CW
167Calculator 2, CO2 value 4ppm value2 Bytes9.8 parts/million (ppm)CW
168Calculator 2, % value 5% value1 Byte5.1 percentage (0..100%)CW
168Calculator 2, temperature value 5°C value2 Bytes9.1 temperature (°C)CW
168Calculator 2, relative humidity 5% r.h. value2 Bytes9.7 humidity (%)CW
168Calculator 2, CO2 value 5ppm value2 Bytes9.8 parts/million (ppm)CW
168Calculator 2​, brightness value 5value in LUX2 Bytes9.4 lux (Lux)CW
169Calculator 2, CO2 value 6ppm value2 Bytes9.8 parts/million (ppm)CW
169Calculator 2, relative humidity 6% r.h. value2 Bytes9.7 humidity (%)CW
169Calculator 2, temperature value 6°C value2 Bytes9.1 temperature (°C)CW
169Calculator 2​, brightness value 6value in LUX2 Bytes9.4 lux (Lux)CW
169Calculator 2, % value 6% value1 Byte5.1 percentage (0..100%)CW
170Calculator 2​, CO2, resultppm value2 Bytes9.8 parts/million (ppm)CRT
170Calculator 2​, humidity, result% r.h. value2 Bytes9.7 humidity (%)CRT
170Calculator 2​, brightness, resultvalue in LUX2 Bytes9.4 lux (Lux)CRT
170Calculator 2​, temperature, result°C value2 Bytes9.1 temperature (°C)CRT
170Calculator 2​, %, result% value1 Byte5.1 percentage (0..100%)CRT
171Calculator 3​, brightness value 1value in LUX2 Bytes9.4 lux (Lux)CW
171Calculator 3, temperature value 1°C value2 Bytes9.1 temperature (°C)CW
171Calculator 3, relative humidity 1% r.h. value2 Bytes9.7 humidity (%)CW
171Calculator 3, CO2 value 1ppm value2 Bytes9.8 parts/million (ppm)CW
171Calculator 3, % value 1% value1 Byte5.1 percentage (0..100%)CW
172Calculator 3, relative humidity 2% r.h. value2 Bytes9.7 humidity (%)CW
172Calculator 3, % value 2% value1 Byte5.1 percentage (0..100%)CW
172Calculator 3​, brightness value 2value in LUX2 Bytes9.4 lux (Lux)CW
172Calculator 3, temperature value 2°C value2 Bytes9.1 temperature (°C)CW
172Calculator 3, CO2 value 2ppm value2 Bytes9.8 parts/million (ppm)CW
173Calculator 3, % value 3% value1 Byte5.1 percentage (0..100%)CW
173Calculator 3​, brightness value 3value in LUX2 Bytes9.4 lux (Lux)CW
173Calculator 3, temperature value 3°C value2 Bytes9.1 temperature (°C)CW
173Calculator 3, relative humidity 3% r.h. value2 Bytes9.7 humidity (%)CW
173Calculator 3, CO2 value 3ppm value2 Bytes9.8 parts/million (ppm)CW
174Calculator 3​, brightness value 4value in LUX2 Bytes9.4 lux (Lux)CW
174Calculator 3, temperature value 4°C value2 Bytes9.1 temperature (°C)CW
174Calculator 3, relative humidity 4% r.h. value2 Bytes9.7 humidity (%)CW
174Calculator 3, CO2 value 4ppm value2 Bytes9.8 parts/million (ppm)CW
174Calculator 3, % value 4% value1 Byte5.1 percentage (0..100%)CW
175Calculator 3, % value 5% value1 Byte5.1 percentage (0..100%)CW
175Calculator 3​, brightness value 5value in LUX2 Bytes9.4 lux (Lux)CW
175Calculator 3, temperature value 5°C value2 Bytes9.1 temperature (°C)CW
175Calculator 3, relative humidity 5% r.h. value2 Bytes9.7 humidity (%)CW
175Calculator 3, CO2 value 5ppm value2 Bytes9.8 parts/million (ppm)CW
176Calculator 3, temperature value 6°C value2 Bytes9.1 temperature (°C)CW
176Calculator 3, CO2 value 6ppm value2 Bytes9.8 parts/million (ppm)CW
176Calculator 3​, brightness value 6value in LUX2 Bytes9.4 lux (Lux)CW
176Calculator 3, relative humidity 6% r.h. value2 Bytes9.7 humidity (%)CW
176Calculator 3, % value 6% value1 Byte5.1 percentage (0..100%)CW
177Calculator 3​, temperature, result°C value2 Bytes9.1 temperature (°C)CRT
177Calculator 3​, brightness, resultvalue in LUX2 Bytes9.4 lux (Lux)CRT
177Calculator 3​, humidity, result% r.h. value2 Bytes9.7 humidity (%)CRT
177Calculator 3​, CO2, resultppm value2 Bytes9.8 parts/million (ppm)CRT
177Calculator 3​, %, result% value1 Byte5.1 percentage (0..100%)CRT
178Comparator 1, external value W1On/Off1 Bit1.1 switchCW
178Comparator 1, external value W1% value1 Byte5.1 percentage (0..100%)CW
178Comparator 1, external value W1°C value2 Bytes9.1 temperature (°C)CW
178Comparator 1, external value W1Value in LUX2 Bytes9.4 lux (Lux)CW
178Comparator 1, external value W1ppm value2 Bytes9.8 parts/million (ppm)CW
178Comparator 1, external value W18-bit value1 Byte5.10 counter pulses (0..255)CW
178Comparator 1, external value W132-bit value4 Bytes12.1 counter pulses (unsigned)CW
178Comparator 1, external value W116-bit value2 Bytes7.1 pulsesCW
179Comparator 1, external value W216-bit value2 Bytes7.1 pulsesCW
179Comparator 1, external value W2On/Off1 Bit1.1 switchCW
179Comparator 1, external value W2% value1 Byte5.1 percentage (0..100%)CW
179Comparator 1, external value W2ppm value2 Bytes9.8 parts/million (ppm)CW
179Comparator 1, external value W232-bit value4 Bytes12.1 counter pulses (unsigned)CW
179Comparator 1, external value W2Value in LUX2 Bytes9.4 lux (Lux)CW
179Comparator 1, external value W28-bit value1 Byte5.10 counter pulses (0..255)CW
179Comparator 1, external value W2°C value2 Bytes9.1 temperature (°C)CW
180Comparator 1, resultTrue/false1 Bit1.2 booleanCRT
181Comparator 2, external value W116-bit value2 Bytes7.1 pulsesCW
181Comparator 2, external value W132-bit value4 Bytes12.1 counter pulses (unsigned)CW
181Comparator 2, external value W1ppm value2 Bytes9.8 parts/million (ppm)CW
181Comparator 2, external value W1Value in LUX2 Bytes9.4 lux (Lux)CW
181Comparator 2, external value W1% value1 Byte5.1 percentage (0..100%)CW
181Comparator 2, external value W18-bit value1 Byte5.10 counter pulses (0..255)CW
181Comparator 2, external value W1On/Off1 Bit1.1 switchCW
181Comparator 2, external value W1°C value2 Bytes9.1 temperature (°C)CW
182Comparator 2, external value W2Value in LUX2 Bytes9.4 lux (Lux)CW
182Comparator 2, external value W2% value1 Byte5.1 percentage (0..100%)CW
182Comparator 2, external value W2ppm value2 Bytes9.8 parts/million (ppm)CW
182Comparator 2, external value W2On/Off1 Bit1.1 switchCW
182Comparator 2, external value W2°C value2 Bytes9.1 temperature (°C)CW
182Comparator 2, external value W28-bit value1 Byte5.10 counter pulses (0..255)CW
182Comparator 2, external value W216-bit value2 Bytes7.1 pulsesCW
182Comparator 2, external value W232-bit value4 Bytes12.1 counter pulses (unsigned)CW
183Comparator 2, resultTrue/false1 Bit1.2 booleanCRT
184Comparator 3, external value W116-bit value2 Bytes7.1 pulsesCW
184Comparator 3, external value W18-bit value1 Byte5.10 counter pulses (0..255)CW
184Comparator 3, external value W1ppm value2 Bytes9.8 parts/million (ppm)CW
184Comparator 3, external value W1°C value2 Bytes9.1 temperature (°C)CW
184Comparator 3, external value W1Value in LUX2 Bytes9.4 lux (Lux)CW
184Comparator 3, external value W1% value1 Byte5.1 percentage (0..100%)CW
184Comparator 3, external value W1On/Off1 Bit1.1 switchCW
184Comparator 3, external value W132-bit value4 Bytes12.1 counter pulses (unsigned)CW
185Comparator 3, external value W2°C value2 Bytes9.1 temperature (°C)CW
185Comparator 3, external value W232-bit value4 Bytes12.1 counter pulses (unsigned)CW
185Comparator 3, external value W2Value in LUX2 Bytes9.4 lux (Lux)CW
185Comparator 3, external value W2ppm value2 Bytes9.8 parts/million (ppm)CW
185Comparator 3, external value W2On/Off1 Bit1.1 switchCW
185Comparator 3, external value W28-bit value1 Byte5.10 counter pulses (0..255)CW
185Comparator 3, external value W216-bit value2 Bytes7.1 pulsesCW
185Comparator 3, external value W2% value1 Byte5.1 percentage (0..100%)CW
186Comparator 3, resultTrue/false1 Bit1.2 booleanCRT
189Green Leaf, temperature setpoint for display°C value2 Bytes9.1 temperature (°C)CW
190Green Leaf, activationtrigger1 Bit1.17 triggerCRT
191Green Leaf, temperature setpoint at activation°C value2 Bytes9.1 temperature (°C)CRT
202Display, temperature value (outside)°C value2 Bytes9.1 temperature (°C)CW
204Display, temperature value (room)°C value2 Bytes9.1 temperature (°C)CW
206Display, temperature setpoint value°C value2 Bytes9.1 temperature (°C)CW
208Display, relative humidity (room)% r.h. value2 Bytes9.7 humidity (%)CW
210Display, relative humidity (outside)% r.h. value2 Bytes9.7 humidity (%)CW
212Display, CO2 value (room)ppm value2 Bytes9.8 parts/million (ppm)CW
214Display, CO2 value (outside)ppm value2 Bytes9.8 parts/million (ppm)CW
215Air quality indicator, displayOn/Off1 Bit1.3 enableCW
217Air quality indicator, CO2 valueppm value2 Bytes9.8 parts/million (ppm)CW
218Display, window contact status0 = closed/1 = open1 Bit1.19 window/doorCW
220Display, room operating mode1 … 41 Byte20.102 HVAC modeCW
222Display, controller status (DPT_HVACContrMode)8-bit status1 Byte20.105 HVAC control modeCW
223Display, comfort extensionActive/inactive1 Bit1.11 stateCW
227Operation, temperature setpoint shiftK value2 Bytes9.2 temperature difference (K)CRT
230Operation, lock temperature setpointlocking1 Bit1.2 booleanCW
232Display, temperature setpoint shiftK value2 Bytes9.2 temperature difference (K)CW
233Operation, temperature setpoint°C value2 Bytes9.1 temperature (°C)CRT
234Operation, comfort extensionOn/Off1 Bit1.10 start/stopCRT
236Operation, lock comfort extensiondisable1 Bit1.2 booleanCW
238Operation, room operating mode (manual operation)0 … 41 Byte20.102 HVAC modeCRT
239Operation, lock room operating modelocking1 Bit1.2 booleanCW
241Display, room operating mode (manual operation)0 … 41 Byte20.102 HVAC modeCW
243Operation, fan speed0...100 %1 Byte5.1 percentage (0..100%)CRT
244Operation, lock fan speedlocking1 Bit1.2 booleanCW
246Display, fan speed0...100 %1 Byte5.1 percentage (0..100%)CW
249Operation, fan operating mode0 = automatic operation/1 = manual operation1 Bit1.3 enableCRT
250Display, fan operating mode0 = automatic operation/1 = manual operation1 Bit1.3 enableCW
252Operation, air quality setpointppm value2 Bytes9.8 parts/million (ppm)CRT
254Display, air quality setpointppm value2 Bytes9.8 parts/million (ppm)CW
255Operation, lock air quality setpointlocking1 Bit1.2 booleanCW
259Operation, humidity setpoint% r.h. value2 Bytes9.7 humidity (%)CRT
260Operation, lock humidity setpointlocking1 Bit1.2 booleanCW
262Display, humidity setpoint% r.h. value2 Bytes9.7 humidity (%)CW
265Operation, presenceOn/Off1 Bit1.18 occupancyCRT
266Operation, lock presencelocking1 Bit1.2 booleanCW
267Display, presenceOn/Off1 Bit1.18 occupancyCW
Parameters (415)
ParameterTypeDefault
Text_OfficialBuildNumber_1090unsignedInt 0…55
Text_Revision_1091unsignedInt 0…11
Cyclical transmission of device function (0 = in operation)listenable
Send status of device function inverted (1 = in operation)listNo
Cyclical transmission periodtime120
Specific transmission time for status objects after bus voltage recoverytime15
Transmission delay between status objectstime1
Behavior after downloadlistUse device parameter
Device operating modelistManager
Temperature sensorlistenable
Humidity sensorlistenable
CO2 sensorlistenable
Temperature controllistdisable
Humidity controllerlistdisable
Air quality controllerlistdisable
PL-Link timeouttime0
Lock operation via objectlistdisable
Button soundlistenable
Temperature unitlistCelsius (°C)
Display sensor and setpoint valuesliston top of each other
Display in idle statelistStandard page
Time until the idle state is activatedunsignedInt 0…25560
Time until the idle state is activatedtime60
Selection of valueslistTemperature
Display temperaturelistRoom temperature value
Temperature setpointlistdisable
Display relative humiditylistRoom humidity value
Humidity setpointlistdisable
Display CO2 valuelistRoom CO2 value
Air quality setpointlistdisable
Delay time until backlight deactivationtime15
Delay time until backlight deactivationunsignedInt 0…25515
Backlight brightness level (%)unsignedInt 0…10060
Show via LEDlistdisable
Minimum setpoint (°C)float -671088.6…670760.920
Maximum setpoint (°C)float -671088.6…670760.924
Activationlistdisable
Change temperature setpoint at activationlistenable
Temperature setpoint at activation (°C)float -671088.6…670760.922
Setpoint setting vialistBasic setpoint + setpoint shift
Controller modelistHeating and cooling
Selection of temperature setpointlistComfort mode: Heating/cooling setpoint
Selection of temperature setpointlistComfort mode: Heating setpoint
Selection of temperature setpointlistComfort mode: Cooling setpoint
Display/activation Green Leaflistdisable
Source of room temperature valuelistTemperature sensor
Select calculatorlistCalculator 1, result (°C)
Calculator 1listDeactivated
Calculator 2listDeactivated
Calculator 3listDeactivated
User interface resolutionlist0.5 °C
User interface resolutionlist0.5 °F
Temperature setpoint typelistAbsolute setpoints
Setpoint typelistAbsolute setpoint
Minimum comfort setpoint (°C)float -273…670433.318
Maximum comfort setpoint (°C)float -273…670433.324
Setting increment (°C)float 0.1…20.5
Setting incrementunsignedInt 1…205
Lock setpoint change over objectlistdisable
Min. relative setpoint (K)float -671088.6…670760.9-3
Min. relative setpoint (K)signedInt -32768…32767-150
Max. relative setpoint (K)float -671088.6…670760.93
Max. relative setpoint (K)signedInt -32768…32767150
Setting increment (K)float 0.1…20.5
Room operation modelistdisable
Preselection of room operating modeslistComfort/standby/economy/protection mode
Lock room operating mode via objectlistdisable
Activation of comfort modelistComfort extension
Comfort extensionlistdisable
Presence notificationlistdisable
Toggle comfort extensionlistenable
Display heating/coolinglistdisable
Display window contact statuslistdisable
Source of room humidity valuelistHumidity sensor
Select calculatorlistCalculator 1, result (% r.h.)
User interface resolutionlist1 % r.h.
Min. rel. humidity setpoint (% r.h.)unsignedInt 0…10010
Max. rel. humidity setpoint (% r.h.)unsignedInt 0…10095
Setting increment (% r.h.)unsignedInt 1…201
Source of room CO2 valuelistCO2 sensor
Select calculatorlistCalculator 1, result (ppm)
User interface resolutionlist50 ppm
Min. air quality setpoint (ppm)unsignedInt 0…2000400
Max. air quality setpoint (ppm)unsignedInt 0…20002000
Setting increment (ppm)unsignedInt 10…200100
Show air qualitylistenable
Source of CO2 valuelistCO2 sensor
Colour change green <-> orange [ppm]float 400…20001000
Colour change orange <-> red [ppm]float 400…20001400
Enable/disable air quality display via the buslistdisable
Fan controllistdisable
Fan typelist3-step
Number of fan speedsunsignedInt 0…2553
Minimum fan speed (%)unsignedInt 0…990
Maximum fan speed (%)unsignedInt 1…100100
Lock fan speed change via objectlistdisable
Offset (K)float -655…6550
Offset (K)signedInt -32768…327670
Object "Temperature value"listenable
Send temperature value on requestlistenable
Send temperature value on change of valuelistenable
Value change since last sent (K)float 0…6550.5
Value change since last sent (K)signedInt -32768…3276725
Block time for sending of temperature valuetime10
Send temperature value cyclicallytime900
Offset (% r.h.)signedInt -100…1000
Object "Relative humidity"listenable
Data typelistDPT 9.007 (KnxFloat)
Send relative humidity on requestlistenable
Send relative humidity on change of valuelistenable
Value change since last sent (% r.h.)unsignedInt 0…1001
Block time for sending of relative humiditytime10
Send status cyclicallytime900
Object "Failure"listdisable
Send status on requestlistdisable
Send status on change of statuslistenable
Send status cyclically (00:00:00 = no sending)time900
Offset (ppm)signedInt -32768…327670
Adjustment factor (x 0.01)signedInt 1…2000100
Installation altitude compensationlistdisable
Installation altitude (m)signedInt 0…30000
Object "CO2 value"listenable
Data typelistDPT 9.008 (KnxFloat)
Send CO2 value on requestlistenable
Send CO2 value on change of valuelistenable
Value change since last sent (ppm)unsignedInt 0…6553510
Block time for sending of CO2 valuetime10
Send CO2 value cyclicallytime900
System typelist2-pipe system
Switch heating/coolinglistAutomatically
Control value in emergency mode, cooling (%)unsignedInt 0…10030
Control value in emergency mode, cooling (%)unsignedInt 0…25577
Control value in emergency mode, heating (%)unsignedInt 0…10070
Control value in emergency mode, heating (%)unsignedInt 0…255179
Ventilation controllistdisable
Controller statuslistdisable
Send status on changelistenable
Send status cyclically (00:00:00 = no sending)time0
Controller status (DPT_HVACContrMode)listdisable
Status of current controller modelistdisable
Collective status (RTSM)listdisable
Collective status (RTC)listdisable
Controller status (RHCC)listdisable
Initial value after bus voltage recoverylistAs before bus voltage failure
Room operating mode (manual operation) switchover vialist8-bit object (DPT_HVACMode)
Object "Comfort extension"listdisable
Time period comfort extensiontime20
Status of comfort extensionlistdisable
Block time for sending of statustime0
Object "Permanent protection mode"listdisable
Object "Presence"listdisable
Object "Status presence"listdisable
Number of window contactsunsignedInt 0…40
Delay of reaction to open windowstime30
Invert window contactslistNo
Window contact statuslistdisable
Status of room mode (manual operation)listdisable
Message vialist8-bit object (DPT_HVACMode)
Status of current room modelistdisable
Source of actual temperature valuelistTemperature sensor
Offset (K)float -671088.6…670760.90
Monitoring actual temperature valuelistdisable
Monitoring timetime0
Actual temperature value error statuslistdisable
Block time for sending of statustime10
Limit (°C)float -273…67076040
Hysteresis (K)float 0…6707602
Object "Temperature control, heat alarm"listdisable
Send alarm on requestlistdisable
Send alarm on change of valuelistenable
Send alarm cyclicallytime0
Block time for sending the alarmtime10
Limit (°C)float -273…6707605
Object "Temperature control, frost alarm"listdisable
Comfort mode: Heating setpoint (°C)float -273…67076021
Protection mode: Heating setpoint (°C)float -273…6707607
Economy mode: Heating setpoint (°C)float -273…67076017
Standby mode: Heating setpoint (°C)float -273…67076019
Object "Heating setpoints"listdisable
Object "Heating setpoint shifts"listdisable
Comfort mode: Cooling setpoint (°C)float -273…67076022
Protection mode: Cooling setpoint (°C)float -273…67076035
Economy mode: Cooling setpoint (°C)float -273…67076026
Standby mode: Cooling setpoint (°C)float -273…67076024
Object "Cooling setpoints"listdisable
Object "Cooling setpoint shifts"listdisable
Basic setpoint (°C)float -273…67076022
Economy mode: Heating setpoint shift (K)float -670760…0-4
Standby mode: Heating setpoint shifts (K)float -670760…0-2
Economy mode: Cooling setpoint shift (K)float 0…6707604
Standby mode: Cooling setpoint shifts (K)float 0…6707602
Dead zone between heating and cooling (±K)float 0…6707600
Object "Basic setpoint"listdisable
Object "Setpoint, comfort mode"listdisable
Object "Setpoint offset"listdisable
Offset acts onlistComfort mode
Minimum possible setpoint (°C)float -273…6707605
Maximum possible setpoint (°C)float -273…67076040
Update cooling setpoint dependent on outside temperaturelistdisable
Ambient temperature offset (K)float -671088.6…670760.90
Ambient temperature monitoringlistdisable
Status of current basic setpointlistdisable
Send value on requestlistdisable
Send value on change of valuelistenable
Value change since last sent (K)float 0…6707600.2
Block time for sending of valuetime10
Send value cyclicallytime0
Status of current setpointlistdisable
Status of setpoint offsetlistdisable
Object "Status effective setpoint comfort mode"listdisable
Status of effective heating setpoint (DPT 9.001)listdisable
Additionally one object per room operating modelistdisable
Status of effective heating setpoints (DPT 275.100)listdisable
Send values on requestlistdisable
Send values on change of valuelistenable
Block time for sending of valuestime10
Send values cyclicallytime0
Status of effective cooling setpoint (DPT 9.001)listdisable
Status of effective cooling setpoints (DPT 275.100)listdisable
Control behaviorlistPI control
Hysteresis (K)float 0…6707600.2
Double hysteresis in economy/protection modelistdisable
Cycle timetime2
Invert control valuelistNo
Send control value on requestlistdisable
Send control value on changelistenable
Block time for sending of control valuetime10
Send control value cyclicallytime0
Heating system typelistUser defined
Proportional range (K)float 1…103
Reset timetime30
Sequence controllistdisable
Type of control value outputlistSteady (8-bit)
Scaling of control value (%)unsignedInt 1…100100
Scaling of control value (%)unsignedInt 0…255255
Maximum control value (%)unsignedInt 0…100100
Maximum control value (%)unsignedInt 0…255255
Minimum control value (%)unsignedInt 0…1000
Minimum control value (%)unsignedInt 0…2550
Change of control value since last sent (%)unsignedInt 0…1005
Change of control value since last sent (%)unsignedInt 0…25513
Valve always closed if control value lower than (%)unsignedInt 1…1001
Valve always closed if control value lower than (%)unsignedInt 3…2553
Valve always open if control value greater than (%)unsignedInt 0…9999
Valve always open if control value greater than (%)unsignedInt 0…252252
Period duration of pulse width modulationtime9
Value of control value at which sequence 2 starts (%)unsignedInt 0…10050
Value of control value at which sequence 2 starts (%)unsignedInt 0…255128
Temperature limitation in heating mode (System type: underfloor heating)listdisable
Limit (°C)float 20…7030
Hysteresis (K)float 1…101
Impact on sequenceunsignedInt 0…10
Current temperature monitoring floor temperaturelistdisable
Temperature limitation status in heating modelistdisable
Object "Dew point alert"listdisable
Dew point alarm statuslistdisable
Cooling system typelistUser defined
Ventilator modelistHeating
Number of speed levelsunsignedInt 1…33
Difference between temperature setpoint and actual value for level 1 (K)float 0…6707601
Difference between temperature setpoint and actual value for level 2 (K)float 0…6707602
Difference between temperature setpoint and actual value for level 3 (K)float 0…6707603
Fan speed at level 1 (%)unsignedInt 1…10025
Fan speed at level 1 (%)unsignedInt 0…25564
Fan speed at level 2 (%)unsignedInt 1…10050
Fan speed at level 2 (%)unsignedInt 0…255128
Fan speed at level 3 (%)unsignedInt 1…100100
Fan speed at level 3 (%)unsignedInt 0…255255
Ventilator modelistCooling
Ventilator modelistHeating and cooling
Status of ventilation mode (automatic/manual operation)listdisable
Control value for manual operationlistdisable
Value change since last sent (%)unsignedInt 0…1005
Value change since last sent (%)unsignedInt 0…25513
Current control valuelistdisable
Source of actual humidity valuelistHumidity sensor
Control behaviorlistStaged control
Number of levelsunsignedInt 1…53
Type of 1-bit controllistControl levels sequentially
Change switching points via objectlistdisable
Standard switching point level 1 (% r.h.)float 0…10040
Standard switching point level 2 (% r.h.)float 0…10070
Standard switching point level 3 (% r.h.)float 0…10090
Standard switching point level 4 (% r.h.)float 0…100100
Standard switching point level 5 (% r.h.)float 0…100100
Hysteresis (% r.h.)float 1…1005
Reset switching points at controller OFFlistdisable
Invert object for manual modelistNo
Send levels on requestlistdisable
Send levels on change of levellistenable
Value change since last sent (%)unsignedInt 0…2553
Block time for sending of levelstime0
Send levels cyclicallytime0
Control signal level 0 (%)unsignedInt 0…1000
Control signal level 0 (%)unsignedInt 0…2550
Control signal level 1 (%)unsignedInt 0…10035
Control signal level 1 (%)unsignedInt 0…25589
Control signal level 2 (%)unsignedInt 0…10070
Control signal level 2 (%)unsignedInt 0…255179
Control signal level 3 (%)unsignedInt 0…100100
Control signal level 3 (%)unsignedInt 0…255255
Control signal level 4 (%)unsignedInt 0…100100
Control signal level 4 (%)unsignedInt 0…255255
Control signal level 5 (%)unsignedInt 0…100100
Control signal level 5 (%)unsignedInt 0…255255
Value change since last sent (%)unsignedInt 0…1001
Block time for sending of valuetime0
Active level if overriddenunsignedInt 0…10
Active level if overriddenunsignedInt 0…20
Active level if overriddenunsignedInt 0…33
Active level if overriddenunsignedInt 0…43
Active level if overriddenunsignedInt 0…53
Status switching pointslistdisable
Value change since last sent (% r.h.)unsignedInt 0…42949672950
Setpoint (% r.h.)float 0…10040
Change setpoint via objectlistdisable
Reset setpoint at controller OFFlistdisable
Status humidity setpointlistdisable
Proportional range (% r.h.)float 1…10012
Standard switching point level 1 (%)unsignedInt 0…1000
Standard switching point level 2 (%)unsignedInt 0…10035
Standard switching point level 3 (%)unsignedInt 0…10070
Standard switching point level 4 (%)unsignedInt 0…100100
Standard switching point level 5 (%)unsignedInt 0…100100
Active control value if overridden (%)unsignedInt 1…100100
Active control value if overridden (%)unsignedInt 0…255255
Source of actual CO2 valuelistCO2 sensor
Standard switching point level 1 (ppm)float 0…670760800
Standard switching point level 2 (ppm)float 0…6707601000
Standard switching point level 3 (ppm)float 0…6707601500
Standard switching point level 4 (ppm)float 0…6707602000
Standard switching point level 5 (ppm)float 0…6707602500
Hysteresis (ppm)float 10…670760200
Value change since last sent (ppm)unsignedInt 0…42949672950
Setpoint (ppm)float 0…670760800
Status setpoint air qualitylistdisable
Proportional range (ppm)float 50…1000400
Calculation typelistMaximal value
Value countunsignedInt 2…62
Source for input valuelistExternal object
dummylistdisable
Offset of external value 1unsignedInt 0…2550
Offset of external value 1 (lx)float -671088.6…670760.90
Offset of external value 1 (K)float -10…100
Offset of external value 1 (% r.h.)float -100…1000
Offset of external value 1 (ppm)float -671088.6…670760.90
Control value selectionlistHeating control value (%)
Control value selectionlistCooling control value (%)
Control value selectionlistHeating/cooling control value (%)
WeightunsignedInt 1…2551
Offset of external value 2unsignedInt 0…2550
Offset of external value 2 (lx)float -671088.6…670760.90
Offset of external value 2 (K)float -10…100
Offset of external value 2 (% r.h.)float -100…1000
Offset of external value 2 (ppm)float -671088.6…670760.90
Offset of external value 3unsignedInt 0…2550
Offset of external value 3 (lx)float -671088.6…670760.90
Offset of external value 3 (K)float -10…100
Offset of external value 3 (% r.h.)float -100…1000
Offset of external value 3 (ppm)float -671088.6…670760.90
Offset of external value 4unsignedInt 0…2550
Offset of external value 4 (lx)float -671088.6…670760.90
Offset of external value 4 (K)float -10…100
Offset of external value 4 (% r.h.)float -100…1000
Offset of external value 4 (ppm)float -671088.6…670760.90
Offset of external value 5unsignedInt 0…2550
Offset of external value 5 (lx)float -671088.6…670760.90
Offset of external value 5 (K)float -10…100
Offset of external value 5 (% r.h.)float -100…1000
Offset of external value 5 (ppm)float -671088.6…670760.90
Offset of external value 6unsignedInt 0…2550
Offset of external value 6 (lx)float -671088.6…670760.90
Offset of external value 6 (K)float -10…100
Offset of external value 6 (% r.h.)float -100…1000
Offset of external value 6 (ppm)float -671088.6…670760.90
Object "Result"listenable
Value change since last sent (K)float 0…6707600.5
Value change since last sent (lx)float 0…67076010
Value change since last sent (% r.h.)float 0…10010
Value change since last sent (ppm)float 0…67076010
Value change since last sent (%)unsignedInt 0…1000
Value change since last sentunsignedInt 0…2550
Comparator 1listDeactivated
Comparator 2listDeactivated
Comparator 3listDeactivated
OperationlistW1 == W2
Start value of W1listOff
Start value of W2listOff
Start value external measured value on bus voltage recoverylistAs before bus voltage failure
Tolerance for comparison (%)unsignedInt 0…1000
Tolerance for comparisonunsignedInt 0…2550
Select calculatorlistCalculator 1, result (%)
Starting value of W1 (%)unsignedInt 0…1000
Start value of W1unsignedInt 0…2550
Starting value of W2 (%)unsignedInt 0…1000
Start value of W2unsignedInt 0…2550
Tolerance for comparison (K)float 0…6707601
Start value of W1 (°C)float -273…6707600
Start value of W2 (°C)float -273…6707600
Tolerance for comparison (lx)float 0…6707601
Select calculatorlistCalculator 1, result (lx)
Start value of W1 (lx)float 0…6707600
Start value of W2 (lx)float 0…6707600
Tolerance for comparison (% r.h.)float 0…1001
Start value of W1 (% r.h.)float 0…1000
Start value of W2 (% r.h.)float 0…1000
Tolerance for comparison (ppm)float 0…6707601
Start value of W1 (ppm)float 0…6707600
Start value of W2 (ppm)float 0…6707600
Tolerance for comparisonunsignedInt 0…655350
Start value of W1unsignedInt 0…655350
Start value of W2unsignedInt 0…655350
Tolerance for comparisonunsignedInt 0…42949672950
Start value of W1unsignedInt 0…42949672950
Start value of W2unsignedInt 0…42949672950

Version history

ApplicationApp noFingerprintFirst seenSizeFile
QMX6.P74 1.1 latest$9204D6F72026-11-25962 KBDownload

About this file

This is the official ETS product database for the Siemens HVAC QMX6.P74 Room Unit (QMX6.P74), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.