Switch actuator 12-fold SW0010/SW0012
SICS · Order number SW0010/SW0012 · Actuator › Switch Actuator
Switch actuator, Staircase, Meter current 12f
Download .knxprod Switch actuator, Staircase, Meter current, 12f 1.0 · 218 KB
Product
| Manufacturer | SICS |
|---|---|
| Product name | Switch actuator 12-fold |
| Order number | SW0010/SW0012 |
| Hardware | Switch actuator 12-fold |
| Medium | Twisted Pair |
| Bus current (mA) | 12 |
| Rail mounted | Yes |
| Width (mm) | 216 |
| Registration | Certified · 2026-05-20 |
| Languages | en-US, it-IT |
| Catalog entry | M-0277_H-04-1_HP-0004-10-7C5F_CI-SW0010.2FSW0012-1 |
| Fingerprint | 7C5F |
| SHA-256 | 85b99f190ed7d85cf7e5a2f45a970377f9dfb58b561d0a92f28ee3a3e8e764fa |
| First seen | 2026-11-25 |
| Markets | 68 markets |
Application program: Switch actuator, Staircase, Meter current, 12f 1.0
| Application number | $0004 |
|---|---|
| Version | 1.0 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0f |
| Parameters | 1367 |
| Group objects | 321 |
Group objects (321)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Channel A | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 1 | Channel A | Staircase | 1 Bit | 1.1 switch | CW |
| 2 | Channel A | Block | 1 Bit | 1.3 enable | CW |
| 3 | Channel A | Forced | 2 Bit | 2.1 switch control | CW |
| 4 | Channel A | Scene | 1 Byte | 18.1 scene control | CW |
| 5 | Channel A | State | 1 Bit | 1.11 state | CRT |
| 6 | Channel A | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 7 | Channel A | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 8 | Channel A | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 8 | Channel A | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 9 | Channel A | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 9 | Channel A | Reset service | 1 Bit | 1.15 reset | CW |
| 10 | Channel A | Service required | 1 Bit | 1.2 boolean | CRT |
| 11 | Channel A | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 11 | Channel A | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 11 | Channel A | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 11 | Channel A | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 12 | Channel A | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 13 | Channel A | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 14 | Channel A | Load faulty | 1 Bit | 1.11 state | CRT |
| 14 | Channel A | Fault current | 1 Bit | 1.11 state | CRT |
| 14 | Channel A | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 15 | Channel A | Reset power meter | 1 Bit | 1.3 enable | CW |
| 16 | Channel A | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 16 | Channel A | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 17 | CO_dummyA2 | 1 Bit | CRT | ||
| 18 | Channel B | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 19 | Channel B | Staircase | 1 Bit | 1.1 switch | CW |
| 20 | Channel B | Block | 1 Bit | 1.3 enable | CW |
| 21 | Channel B | Forced | 2 Bit | 2.1 switch control | CW |
| 22 | Channel B | Scene | 1 Byte | 18.1 scene control | CW |
| 23 | Channel B | State | 1 Bit | 1.11 state | CRT |
| 24 | Channel B | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 25 | Channel B | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 26 | Channel B | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 26 | Channel B | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 27 | Channel B | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 27 | Channel B | Reset service | 1 Bit | 1.15 reset | CW |
| 28 | Channel B | Service required | 1 Bit | 1.2 boolean | CRT |
| 29 | Channel B | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 29 | Channel B | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 29 | Channel B | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 29 | Channel B | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 30 | Channel B | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 31 | Channel B | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 32 | Channel B | Fault current | 1 Bit | 1.11 state | CRT |
| 32 | Channel B | Load faulty | 1 Bit | 1.11 state | CRT |
| 32 | Channel B | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 33 | Channel B | Reset power meter | 1 Bit | 1.3 enable | CW |
| 34 | Channel B | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 34 | Channel B | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 35 | CO_dummyB2 | 1 Bit | CRT | ||
| 36 | Channel C | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 37 | Channel C | Staircase | 1 Bit | 1.1 switch | CW |
| 38 | Channel C | Block | 1 Bit | 1.3 enable | CW |
| 39 | Channel C | Forced | 2 Bit | 2.1 switch control | CW |
| 40 | Channel C | Scene | 1 Byte | 18.1 scene control | CW |
| 41 | Channel C | State | 1 Bit | 1.11 state | CRT |
| 42 | Channel C | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 43 | Channel C | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 44 | Channel C | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 44 | Channel C | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 45 | Channel C | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 45 | Channel C | Reset service | 1 Bit | 1.15 reset | CW |
| 46 | Channel C | Service required | 1 Bit | 1.2 boolean | CRT |
| 47 | Channel C | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 47 | Channel C | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 47 | Channel C | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 47 | Channel C | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 48 | Channel C | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 49 | Channel C | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 50 | Channel C | Fault current | 1 Bit | 1.11 state | CRT |
| 50 | Channel C | Load faulty | 1 Bit | 1.11 state | CRT |
| 50 | Channel C | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 51 | Channel C | Reset power meter | 1 Bit | 1.3 enable | CW |
| 52 | Channel C | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 52 | Channel C | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 53 | CO_dummyC2 | 1 Bit | CRT | ||
| 54 | Channel D | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 55 | Channel D | Staircase | 1 Bit | 1.1 switch | CW |
| 56 | Channel D | Block | 1 Bit | 1.3 enable | CW |
| 57 | Channel D | Forced | 2 Bit | 2.1 switch control | CW |
| 58 | Channel D | Scene | 1 Byte | 18.1 scene control | CW |
| 59 | Channel D | State | 1 Bit | 1.11 state | CRT |
| 60 | Channel D | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 61 | Channel D | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 62 | Channel D | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 62 | Channel D | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 63 | Channel D | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 63 | Channel D | Reset service | 1 Bit | 1.15 reset | CW |
| 64 | Channel D | Service required | 1 Bit | 1.2 boolean | CRT |
| 65 | Channel D | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 65 | Channel D | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 65 | Channel D | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 65 | Channel D | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 66 | Channel D | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 67 | Channel D | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 68 | Channel D | Fault current | 1 Bit | 1.11 state | CRT |
| 68 | Channel D | Load faulty | 1 Bit | 1.11 state | CRT |
| 68 | Channel D | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 69 | Channel D | Reset power meter | 1 Bit | 1.3 enable | CW |
| 70 | Channel D | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 70 | Channel D | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 71 | CO_dummyD2 | 1 Bit | CRT | ||
| 72 | Channel E | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 73 | Channel E | Staircase | 1 Bit | 1.1 switch | CW |
| 74 | Channel E | Block | 1 Bit | 1.3 enable | CW |
| 75 | Channel E | Forced | 2 Bit | 2.1 switch control | CW |
| 76 | Channel E | Scene | 1 Byte | 18.1 scene control | CW |
| 77 | Channel E | State | 1 Bit | 1.11 state | CRT |
| 78 | Channel E | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 79 | Channel E | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 80 | Channel E | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 80 | Channel E | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 81 | Channel E | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 81 | Channel E | Reset service | 1 Bit | 1.15 reset | CW |
| 82 | Channel E | Service required | 1 Bit | 1.2 boolean | CRT |
| 83 | Channel E | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 83 | Channel E | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 83 | Channel E | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 83 | Channel E | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 84 | Channel E | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 85 | Channel E | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 86 | Channel E | Fault current | 1 Bit | 1.11 state | CRT |
| 86 | Channel E | Load faulty | 1 Bit | 1.11 state | CRT |
| 86 | Channel E | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 87 | Channel E | Reset power meter | 1 Bit | 1.3 enable | CW |
| 88 | Channel E | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 88 | Channel E | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 89 | CO_dummyE2 | 1 Bit | CRT | ||
| 90 | Channel F | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 91 | Channel F | Staircase | 1 Bit | 1.1 switch | CW |
| 92 | Channel F | Block | 1 Bit | 1.3 enable | CW |
| 93 | Channel F | Forced | 2 Bit | 2.1 switch control | CW |
| 94 | Channel F | Scene | 1 Byte | 18.1 scene control | CW |
| 95 | Channel F | State | 1 Bit | 1.11 state | CRT |
| 96 | Channel F | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 97 | Channel F | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 98 | Channel F | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 98 | Channel F | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 99 | Channel F | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 99 | Channel F | Reset service | 1 Bit | 1.15 reset | CW |
| 100 | Channel F | Service required | 1 Bit | 1.2 boolean | CRT |
| 101 | Channel F | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 101 | Channel F | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 101 | Channel F | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 101 | Channel F | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 102 | Channel F | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 103 | Channel F | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 104 | Channel F | Fault current | 1 Bit | 1.11 state | CRT |
| 104 | Channel F | Load faulty | 1 Bit | 1.11 state | CRT |
| 104 | Channel F | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 105 | Channel F | Reset power meter | 1 Bit | 1.3 enable | CW |
| 106 | Channel F | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 106 | Channel F | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 107 | CO_dummyF2 | 1 Bit | CRT | ||
| 108 | Channel G | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 109 | Channel G | Staircase | 1 Bit | 1.1 switch | CW |
| 110 | Channel G | Block | 1 Bit | 1.3 enable | CW |
| 111 | Channel G | Forced | 2 Bit | 2.1 switch control | CW |
| 112 | Channel G | Scene | 1 Byte | 18.1 scene control | CW |
| 113 | Channel G | State | 1 Bit | 1.11 state | CRT |
| 114 | Channel G | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 115 | Channel G | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 116 | Channel G | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 116 | Channel G | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 117 | Channel G | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 117 | Channel G | Reset service | 1 Bit | 1.15 reset | CW |
| 118 | Channel G | Service required | 1 Bit | 1.2 boolean | CRT |
| 119 | Channel G | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 119 | Channel G | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 119 | Channel G | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 119 | Channel G | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 120 | Channel G | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 121 | Channel G | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 122 | Channel G | Fault current | 1 Bit | 1.11 state | CRT |
| 122 | Channel G | Load faulty | 1 Bit | 1.11 state | CRT |
| 122 | Channel G | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 123 | Channel G | Reset power meter | 1 Bit | 1.3 enable | CW |
| 124 | Channel G | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 124 | Channel G | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 125 | CO_dummyG2 | 1 Bit | CRT | ||
| 126 | Channel H | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 127 | Channel H | Staircase | 1 Bit | 1.1 switch | CW |
| 128 | Channel H | Block | 1 Bit | 1.3 enable | CW |
| 129 | Channel H | Forced | 2 Bit | 2.1 switch control | CW |
| 130 | Channel H | Scene | 1 Byte | 18.1 scene control | CW |
| 131 | Channel H | State | 1 Bit | 1.11 state | CRT |
| 132 | Channel H | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 133 | Channel H | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 134 | Channel H | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 134 | Channel H | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 135 | Channel H | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 135 | Channel H | Reset service | 1 Bit | 1.15 reset | CW |
| 136 | Channel H | Service required | 1 Bit | 1.2 boolean | CRT |
| 137 | Channel H | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 137 | Channel H | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 137 | Channel H | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 137 | Channel H | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 138 | Channel H | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 139 | Channel H | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 140 | Channel H | Fault current | 1 Bit | 1.11 state | CRT |
| 140 | Channel H | Load faulty | 1 Bit | 1.11 state | CRT |
| 140 | Channel H | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 141 | Channel H | Reset power meter | 1 Bit | 1.3 enable | CW |
| 142 | Channel H | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 142 | Channel H | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 143 | CO_dummyH2 | 1 Bit | CRT | ||
| 144 | Channel I | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 145 | Channel I | Staircase | 1 Bit | 1.1 switch | CW |
| 146 | Channel I | Block | 1 Bit | 1.3 enable | CW |
| 147 | Channel I | Forced | 2 Bit | 2.1 switch control | CW |
| 148 | Channel I | Scene | 1 Byte | 18.1 scene control | CW |
| 149 | Channel I | State | 1 Bit | 1.11 state | CRT |
| 150 | Channel I | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 151 | Channel I | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 152 | Channel I | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 152 | Channel I | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 153 | Channel I | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 153 | Channel I | Reset service | 1 Bit | 1.15 reset | CW |
| 154 | Channel I | Service required | 1 Bit | 1.2 boolean | CRT |
| 155 | Channel I | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 155 | Channel I | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 155 | Channel I | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 155 | Channel I | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 156 | Channel I | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 157 | Channel I | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 158 | Channel I | Fault current | 1 Bit | 1.1 switch | CRT |
| 158 | Channel I | Load faulty | 1 Bit | 1.11 state | CRT |
| 158 | Channel I | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 158 | Channel I | Fault current | 1 Bit | 1.11 state | CRT |
| 159 | Channel I | Reset power meter | 1 Bit | 1.3 enable | CW |
| 160 | Channel I | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 160 | Channel I | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 161 | CO_dummyI2 | 1 Bit | CRT | ||
| 162 | Channel J | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 163 | Channel J | Staircase | 1 Bit | 1.1 switch | CW |
| 164 | Channel J | Block | 1 Bit | 1.3 enable | CW |
| 165 | Channel J | Forced | 2 Bit | 2.1 switch control | CW |
| 166 | Channel J | Scene | 1 Byte | 18.1 scene control | CW |
| 167 | Channel J | State | 1 Bit | 1.11 state | CRT |
| 168 | Channel J | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 169 | Channel J | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 170 | Channel J | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 170 | Channel J | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 171 | Channel J | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 171 | Channel J | Reset service | 1 Bit | 1.15 reset | CW |
| 172 | Channel J | Service required | 1 Bit | 1.2 boolean | CRT |
| 173 | Channel J | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 173 | Channel J | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 173 | Channel J | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 173 | Channel J | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 174 | Channel J | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 175 | Channel J | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 176 | Channel J | Fault current | 1 Bit | 1.11 state | CRT |
| 176 | Channel J | Load faulty | 1 Bit | 1.11 state | CRT |
| 176 | Channel J | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 177 | Channel J | Reset power meter | 1 Bit | 1.3 enable | CW |
| 178 | Channel J | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 178 | Channel J | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 179 | CO_dummyJ2 | 1 Bit | CRT | ||
| 180 | Channel K | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 181 | Channel K | Staircase | 1 Bit | 1.1 switch | CW |
| 182 | Channel K | Block | 1 Bit | 1.3 enable | CW |
| 183 | Channel K | Forced | 2 Bit | 2.1 switch control | CW |
| 184 | Channel K | Scene | 1 Byte | 18.1 scene control | CW |
| 185 | Channel K | State | 1 Bit | 1.11 state | CRT |
| 186 | Channel K | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 187 | Channel K | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 188 | Channel K | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 188 | Channel K | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 189 | Channel K | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 189 | Channel K | Reset service | 1 Bit | 1.15 reset | CW |
| 190 | Channel K | Service required | 1 Bit | 1.2 boolean | CRT |
| 191 | Channel K | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 191 | Channel K | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 191 | Channel K | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 191 | Channel K | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 192 | Channel K | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 193 | Channel K | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 194 | Channel K | Fault current | 1 Bit | 1.11 state | CRT |
| 194 | Channel K | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 194 | Channel K | Load faulty | 1 Bit | 1.11 state | CRT |
| 195 | Channel K | Reset power meter | 1 Bit | 1.3 enable | CW |
| 196 | Channel K | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 196 | Channel K | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 197 | CO_dummyK2 | 1 Bit | CRT | ||
| 198 | Channel L | Switch On/Off | 1 Bit | 1.1 switch | CW |
| 199 | Channel L | Staircase | 1 Bit | 1.1 switch | CW |
| 200 | Channel L | Block | 1 Bit | 1.3 enable | CW |
| 201 | Channel L | Forced | 2 Bit | 2.1 switch control | CW |
| 202 | Channel L | Scene | 1 Byte | 18.1 scene control | CW |
| 203 | Channel L | State | 1 Bit | 1.11 state | CRT |
| 204 | Channel L | Logic 1 | 1 Bit | 1.2 boolean | CW |
| 205 | Channel L | Logic 2 | 1 Bit | 1.2 boolean | CW |
| 206 | Channel L | Response operating hours | 4 Bytes | 13.100 time lag (s) | CRT |
| 206 | Channel L | Time to the next service | 4 Bytes | 13.100 time lag (s) | CRT |
| 207 | Channel L | Reset operating hours | 1 Bit | 1.15 reset | CW |
| 207 | Channel L | Reset service | 1 Bit | 1.15 reset | CW |
| 208 | Channel L | Service required | 1 Bit | 1.2 boolean | CRT |
| 209 | Channel L | Current value | 2 Bytes | 7.12 current (mA) | CRT |
| 209 | Channel L | Current value | 2 Bytes | 9.21 current (mA) | CRT |
| 209 | Channel L | Current value | 4 Bytes | 14.19 electric current (A) | CRT |
| 209 | Channel L | Current value | 2 Bytes | 9.24 power (kW) | CRT |
| 210 | Channel L | Exceedance of load | 1 Bit | 1.1 switch | CRT |
| 211 | Channel L | Lower deviation of load | 1 Bit | 1.1 switch | CRT |
| 212 | Channel L | Load faulty | 1 Bit | 1.11 state | CRT |
| 212 | Channel L | Fault current | 1 Bit | 1.11 state | CRT |
| 212 | Channel L | Fault current/Load faulty | 1 Bit | 1.11 state | CRT |
| 213 | Channel L | Reset power meter | 1 Bit | 1.3 enable | CW |
| 214 | Channel L | Active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 214 | Channel L | Active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 215 | CO_dummyL2 | 1 Bit | CRT | ||
| 218 | Central function | In operation | 1 Bit | 1.2 boolean | CRT |
| 219 | Central function | Total active energy (kWh) | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 219 | Central function | Total active energy (Wh) | 4 Bytes | 13.10 active energy (Wh) | CRT |
| 220 | Central function | Value of total current | 2 Bytes | 9.21 current (mA) | CRT |
| 220 | Central function | Value of total current | 4 Bytes | 14.19 electric current (A) | CRT |
| 220 | Central function | Value of total current | 2 Bytes | 9.24 power (kW) | CRT |
| 221 | Central function | Exceedance of total load | 1 Bit | 1.1 switch | CRT |
| 222 | Central function | Switch On/Off | 1 Bit | 1.1 switch | CW |
Parameters (104)
| Parameter | Type | Default |
|---|---|---|
| Disabled objects | unsignedInt 0…255 | 1 |
| Startup timeout | list | 1 s |
| Total current | list | not active |
| Object selection for the current measurement | list | Floating value in mA (DPT 9.021) |
| Faktor=1 | list | On |
| Factor for conversion into theoretical wattage kW: Current value x Factor | unsignedInt 100…250 | 230 |
| Send current value after changes value | list | not active |
| Cyclic send | list | not active |
| Monitoring exceedance of load | list | active |
| Lastüberwachung inaktiv | list | Off |
| Factor for load monitoring [A] | unsignedInt 1…200 | 1 |
| Faktor für Lastüberwachung | list | 1 A |
| Hysteresis [%] | unsignedInt 10…100 | 10 |
| Behavior at exceeding | list | Send no telegramm |
| Behavior at not exceeding | list | Send no telegramm |
| Send exceeding cyclical | list | not active |
| Total power meter function (Wh/kWh) | list | not active |
| Object selection for total power meter | list | Value in Wh (DPT 13.010) |
| Sending object value | list | only request |
| Memory of all power meters delete after download of application | list | No |
| Channel A | list | Not active |
| Central function | list | not active |
| Channel activate | list | active |
| Manual control | list | not active |
| Channel B | list | Not active |
| Channel C | list | Not active |
| Channel D | list | Not active |
| Channel E | list | Not active |
| Channel F | list | Not active |
| Channel G | list | Not active |
| Channel H | list | Not active |
| Channel I | list | Not active |
| Channel J | list | Not active |
| Channel K | list | Not active |
| Channel L | list | Not active |
| Mode | list | normaly opend |
| delay on SOO or ADV | list | SOO |
| Time for staircase [s] | unsignedInt 0…30000 | 0 |
| Prewarning time in [s] | unsignedInt 0…30000 | 0 |
| Manual switching off | list | not active |
| Verl?ngern bei Treppenlicht | list | Disable |
| On delay [s] | unsignedInt 0…30000 | 0 |
| Off delay [s] | unsignedInt 0…30000 | 0 |
| Block object | list | active |
| Behaviour when locked | list | no change |
| Behaviour when unlocked | list | no change |
| State at the beginning of the lock state | list | Off |
| State at the end of the lock state | list | Off |
| invertieren des Lock Objektes | list | not inverted |
| Value of the device after bus power down | list | Off |
| Value of the device after bus power up | list | Off |
| Behaviour at bus power up | list | no change |
| Behaviour at bus power down | list | no change |
| Operating hours counter | list | not active |
| Current measurement | list | not active |
| Bus Power Up Message Delay | list | 1 s |
| Logical functions | list | not active |
| active Logic Inputs | list | not active |
| Logic operations | list | OR |
| mode | list | switching |
| Scene | list | not active |
| Type of operating hours counter | list | Operating hours counter |
| Count if | list | Relay ON |
| Send status of operating hours every … hours | unsignedInt 0…10000 | 0 |
| Send status of service hours every … [h] | unsignedInt 0…10000 | 0 |
| Send signal of service at … x10h intervals | unsignedInt 0…250 | 0 |
| Power meter function (Wh/kWh) | list | not active |
| Object selection for power meter | list | Value in Wh (DPT 13.010) |
| Current filter | list | Filter 1. step: meter 2 values than output |
| Object selection for the current measurement | list | Value in mA (DPT 7.012) |
| Add the channel to total current measurement | list | not active |
| Cyclic sending | list | not active |
| Monitoring exceedance of load | list | not active |
| Value range for load monitoring | list | 100mA - 20A |
| Factor for load monitoring x100 mA | unsignedInt 1…200 | 1 |
| Monitoring lower deviation of load | list | not active |
| Behavior at deviating | list | Send no telegramm |
| Behavior at not deviating | list | Send no telegramm |
| Send falling below cyclical | list | not active |
| Message if contact opened | list | not active |
| Switching threshold | list | 20 mA |
| Save scene | list | disabled |
| Scene A | list | Off |
| Scene number A | list | 1 |
| Scene B | list | Off |
| Scene number B | list | 2 |
| Scene C | list | Off |
| Scene number C | list | 3 |
| Scene D | list | Off |
| Scene number D | list | 4 |
| Scene E | list | Off |
| Scene number E | list | 5 |
| Scene F | list | Off |
| Scene number F | list | 6 |
| Scene G | list | Off |
| Scene number G | list | 7 |
| Scene H | list | Off |
| Scene number H | list | 8 |
| Prewarning | list | not active |
| Warning time [s] | unsignedInt 0…30000 | 1 |
| Extend staircase time | list | not active |
| Send communication object "in operation" | list | No |
| Sending cycle time in s[1...65535] | unsignedInt 1…65535 | 60 |
| Behavior of status response | list | after change |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Switch actuator, Staircase, Meter current, 12f 1.0 latest | $0004 | 7C5F | 2026-11-25 | 218 KB | Download |
About this file
This is the official ETS product database for the SICS Switch actuator 12-fold (SW0010/SW0012), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from SICS
- Switch actuator 4-fold SW0001/SW0002/SW0004
- Switch actuator 8-fold SW0006/SW0008