Thermostat VISIO KXTT00UXXX
Schrack Technik GmbH · Order number KXTT00UXXX · Heating, Air conditioning, Ventilation › Thermostat › Wall Mounted Devices
Thermostat VISIO
Download .knxprod Thermostat VISIO 1.2 · 77 KB
Product
| Manufacturer | Schrack Technik GmbH |
|---|---|
| Product name | Thermostat VISIO |
| Order number | KXTT00UXXX |
| Hardware | HW Thermostat STD |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Certified · 2022-08-24 |
| Languages | de-DE, en-US |
| Catalog entry | M-014F_H-805431.2DP-1-O008B_HP-0203-12-74DA-O008B_CI-KXTT00UXXX-1 |
| Fingerprint | 74DA |
| SHA-256 | 667d02a5786d55a02dd9538c7fc68c3b3b18c66219989c2e5567bce5494339c5 |
| First seen | 2026-11-25 |
| Markets | 35 markets |
Application program: Thermostat VISIO 1.2
| Application number | $0203 |
|---|---|
| Version | 1.2 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 54 |
| Group objects | 32 |
Group objects (32)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Actual temperature value | Transmit actual value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 1 | Current operation mode | Indicate operation mode | 1 Byte | 20.102 HVAC mode | CRWT |
| 2 | Presence Input | Input for presence signal | 1 Bit | 1.1 switch | CRW |
| 3 | Window State | Input for window contact | 1 Bit | 1.1 switch | CRW |
| 4 | Heating base setpoint | Define set point value | 2 Bytes | 9.1 temperature (°C) | CRW |
| 5 | Cooling base setpoint | Define set point value | 2 Bytes | 9.1 temperature (°C) | CRW |
| 6 | Current Setpoint | Indicate/adjust set point | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 7 | Heating Switching Control Value | Transmit actuating value | 1 Bit | 1.1 switch | CRT |
| 7 | Heating Continuous Control Value | Transmit actuating value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | Cooling Switching Control Value | Transmit actuating value | 1 Bit | 1.1 switch | CRT |
| 8 | Cooling Continuous Control Value | Transmit actuating value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 9 | Switchover between heating and cooling | heating=1, cooling=0 | 1 Bit | 1.1 switch | CRWT |
| 9 | Report heating or cooling mode | heating=1 cooling=0 | 1 Bit | 1.1 switch | CRT |
| 10 | Reset manual operations | Reset=1 | 1 Bit | 1.1 switch | CRW |
| 11 | Fan mode (manual/auto) | 1=manual, 0=auto | 1 Bit | 1.1 switch | CRWT |
| 11 | Fan mode (manual/auto) | 0=manual, 1=auto | 1 Bit | 1.1 switch | CRWT |
| 12 | Fan level | send/receive fan level 0-100 % | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 12 | Fan level | send/receive fan level 0-3 | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 13 | LCD backlight | on/off backlight | 1 Bit | 1.1 switch | CRW |
| 14 | Time | Receive time | 3 Bytes | 10.1 time of day | CRW |
| 15 | Time query | Request for time | 1 Bit | 1.2 boolean | CRT |
| 16 | Date | Receive date | 3 Bytes | 11.1 date | CRW |
| 17 | Date query | Request for date | 1 Bit | 1.2 boolean | CRT |
| 18 | Switching program lock | Lock=1 | 1 Bit | 1.1 switch | CRW |
| 19 | Heating PWM Control Value | Transmit actuating value | 1 Bit | 1.1 switch | CRT |
| 20 | Cooling PWM Control Value | Transmit actuating value | 1 Bit | 1.1 switch | CRT |
| 21 | Fan level | send/receive fan level 1 | 1 Bit | 1.1 switch | CRWTU |
| 22 | Fan level | send/receive fan level 2 | 1 Bit | 1.1 switch | CRWTU |
| 23 | Fan level | send/receive fan level 3 | 1 Bit | 1.1 switch | CRWTU |
| 24 | Fan unit | send on/off | 1 Bit | 1.1 switch | CT |
| 29 | Object 29 | debug 1 | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
| 30 | Object 30 | debug 2 | 1 Byte | 5.10 counter pulses (0..255) | CRWTU |
Parameters (53)
| Parameter | Type | Default |
|---|---|---|
| Operation mode after reset | list | Standby |
| Control function | list | Heating |
| Control function after ETS download | list | Heating |
| Transmit actual temperature at change | list | inactive |
| Transmit actual temperature cyclically | list | not cyclically, only at change |
| Heating setpoint base | unsignedInt 15…32 | 20 |
| Heating reduction standby | unsignedInt 1…10 | 3 |
| Heating reduction night | unsignedInt 1…10 | 5 |
| Heating setpoint frost protection | unsignedInt 1…15 | 5 |
| Cooling setpoint base | unsignedInt 15…32 | 20 |
| Cooling increase standby | unsignedInt 1…10 | 3 |
| Cooling increase night | unsignedInt 1…10 | 5 |
| Cooling setpoint heat protection | unsignedInt 30…40 | 37 |
| Minimum distance between heating and cooling | list | 1K |
| Transmit current setpoint cyclically | list | not cyclically, only at change |
| Heating trasmit control value cyclically | list | not cyclically, only at change |
| Heating controller type | list | 2 Step |
| Heating hysteresis | list | 0.2K |
| Heating control value invert | list | yes |
| Heating PI parameter type | list | Via type of system |
| Heating type of the system | list | Warm water heating |
| Heating PWM cyclic time (Min) | unsignedInt 1…60 | 1 |
| Heating propotional band | list | 4.0K |
| Transmit control value at change of | list | 1% |
| Cooling integral reset time | unsignedInt 0…250 | 0 |
| Cooling propotional band | list | 4.0K |
| Cooling PWM cyclic time (Min) | unsignedInt 1…60 | 1 |
| Cooling type of the system | list | Cool ceiling |
| Cooling PI parameter type | list | Via type of system |
| Cooling control value invert | list | yes |
| Cooling hysteresis | list | 0.2K |
| Cooling controller type | list | 2 Step |
| Cooling transmit control value cyclically | list | not cyclically, only at change |
| Settings menu on device | list | Disable |
| Fan control | list | Disable |
| Transmit operation mode and fan step | list | not cyclically, only at change |
| Switching program after reset | list | No program |
| Language after download | list | English |
| Switchover between heating and cooling | list | Automatically |
| Offset for temperature sensor 0.1K Steps ( -50..50 ) | signedInt -50…50 | 0 |
| Maximum allowed setpoint offset | list | manual adjustment not allowed |
| Value for fan level 1 | unsignedInt 0…200 | 0 |
| Value for fan level 2 | unsignedInt 0…200 | 0 |
| Value for fan level 3 | unsignedInt 0…200 | 0 |
| Switchover fan auto and manual mode | list | Via object "Fan auto/manual", auto is 0 |
| Heating integral reset time | unsignedInt 0…250 | 0 |
| Show extra objects | list | no |
| Ets data loaded | list | yes |
| Heating transmit control value cyclically | list | not cyclically, only at change |
| Select date-time object | list | Time object only |
| Fan level object type | list | 1-Byte object, percentage value 0-100 % |
| Use heating control object | list | No ( 4 pipe system ) |
| ( with 2 step control cooling and heating hystereses is add to value ) | text |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Thermostat VISIO 1.2 latest | $0203 | 74DA | 2026-11-25 | 77 KB | Download |
About this file
This is the official ETS product database for the Schrack Technik GmbH Thermostat VISIO (KXTT00UXXX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Schrack Technik GmbH
- Actuator for thermal positioners KXHK66RL-- KXHK66RL--
- KNX/DALI Gateway Twin KXDD02RV-- KXDD02RV--
- Universal dimmer KXDK02RLED KXDK02RLED
- Binary input device KXEK08RM-- KXEK08RM--
- Push button interface KXEK44UP-- KXEK44UP--
- Binary input device KXEKF0RN-- KXEKF0RN--
- Binary input device KXEKF0RP-- KXEKF0RP--
- IP-Router KXIK00RR-- KXIK00RR--
- Interface USB KXIK00RU-- KXIK00RU--
- Venetian blind actuator KXJK04RD-- KXJK04RD--
- Venetian blind actuator KXJK04RE-- KXJK04RE--
- Venetian blind actuator KXJK08RD-- KXJK08RD--