KNX_Board 4500875479
PROLUX · Order number 4500875479 · FanCoil_KNX
FanCoil_KNX
Download .knxprod FanCoil_KNX 0.2 · 71 KB
Product
| Manufacturer | PROLUX |
|---|---|
| Product name | KNX_Board |
| Order number | 4500875479 |
| Product text | FanCoil_KNX |
| Hardware | KNX_module |
| Medium | Twisted Pair |
| Bus current (mA) | 100 |
| Rail mounted | No |
| Registration | Registered · 2019-08-19 |
| Languages | en-US, de-DE, it-IT, ru-RU, fr-FR, pl-PL |
| Catalog entry | M-011B_H-73241011-1-O0119_HP-0001-02-D9EC-O0119_CI-4500875479-1 |
| Fingerprint | D9EC |
| SHA-256 | 85f2f348422df97644868602ab33892deaa6741393b34f81a156d9297f8ae5e3 |
| First seen | 2026-11-25 |
| Markets | Austria, Czech Republic, France, Germany, Italy, Netherlands, Poland, Russia, Spain, Switzerland, Ukraine, United Kingdom |
Application program: FanCoil_KNX 0.2
| Application number | $0001 |
|---|---|
| Version | 0.2 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 11 |
| Group objects | 20 |
Group objects (20)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | ON/Standby | ON/Standby | 1 Bit | 1.1 switch | CRWTU |
| 2 | ChangeOver | Change over heating/cooling | 1 Bit | 1.100 heating/cooling | CW |
| 3 | Set Temp | Set point Temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 4 | Act Temp | Room temp. | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 5 | Yheating(0-100%) | Control value Heating/cooling | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 6 | Ycooling(0-100%) | Control value cooling | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 7 | Speed Limit | Speed limiter | 1 Byte | 5.1 percentage (0..100%) | CRWT |
| 8 | Boost | Boost | 1 Bit | 1.1 switch | CRWTU |
| 9 | Ventilation | Ventilation | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 10 | RegulArt | Control type | 1 Bit | 1.6 binary value | CRWTU |
| 11 | Act Rotation | Act. Rotation | 1 Byte | 5.1 percentage (0..100%) | CRWTU |
| 12 | Alarrm bit | Alarm bit | 1 Bit | 1.5 alarm | CRT |
| 13 | Condensate | Alarm condensate/dew point | 1 Bit | 1.1 switch | CRT |
| 14 | Alarm Txt | Alarm Text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 15 | Warning Txt | Warning Txt | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 16 | Op Mode Txt | Operation mode Txt | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 17 | COMode Txt | Change over state Text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 18 | wMode Txt | ON/Standby stateText | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 19 | FCU Name Txt | FanCoil Type Text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 20 | Regul Art Txt | Control type Text | 14 Bytes | 16.0 Character String (ASCII) | CRT |
Parameters (11)
| Parameter | Type | Default |
|---|---|---|
| Use of condensate pump/monitor | list | NO, without pump |
| Flow cooling | list | 10 |
| Duration Boost | list | 15 |
| Speed Limiter | list | 100 |
| Flow heating | list | 55 |
| Duration Ventilation | list | 15 |
| Configuration ext.Control | list | Only heating |
| Type of controlling | list | 2-controller principle (Rhigh) |
| Type of actors | list | ON/OFF |
| cyclic request room temp | list | 0 = No request |
| Polarity of ON/Standby | list | 0(OFF)=working;1(ON)=Standby |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| FanCoil_KNX 0.2 latest | $0001 | D9EC | 2026-11-25 | 71 KB | Download |
About this file
This is the official ETS product database for the PROLUX KNX_Board (4500875479), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from PROLUX
- Function board KNX 2920935