KNX FANCOIL ACTUATOR WRKT71445NC
Panasonic · Order number WRKT71445NC · Heating, A/C, ventilation › fan coil
Switching, fan coil 20B011
Download .knxprod Switching, fan coil 20B011 1.1 · 184 KB
Product
| Manufacturer | Panasonic |
|---|---|
| Product name | KNX FANCOIL ACTUATOR |
| Order number | WRKT71445NC |
| Hardware | REG 2007 FanCoil Aktor 1/2fach |
| Medium | Twisted Pair |
| Bus current (mA) | 6 |
| Rail mounted | Yes |
| Width (mm) | 72 |
| Registration | Registered · 2018-04-18 |
| Languages | en-US |
| Catalog entry | M-008B_H-139.20.2F.2F.20WRKT71445NC-1-O000A_HP-20B0-11-05AC-O000A_CI-WRKT71445NC-1 |
| Fingerprint | 05AC |
| SHA-256 | 3300d9c30975538915431ebba92deb9f9a51f2dec91eb30a38a255739472a24a |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Switching, fan coil 20B011 1.1
| Application number | $20B0 |
|---|---|
| Version | 1.1 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 1159 |
| Group objects | 108 |
Group objects (108)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Manual control | Disabling | 1 Bit | CW | |
| 0 | Object 1 | 1 Bit | CW | ||
| 1 | Manual control | Status | 1 Bit | CT | |
| 1 | Object 2 | 1 Bit | CT | ||
| 2 | Object 3 | 1 Byte | CW | ||
| 2 | Channel 1 | Command value for heating | 1 Byte | CW | |
| 3 | Object 4 | 1 Byte | CW | ||
| 3 | Channel 1 | Command value for cooling | 1 Byte | CW | |
| 4 | Object 5 | 1 Bit | CW | ||
| 4 | Channel 1 | Heating/cooling change-over | 1 Bit | CW | |
| 4 | Channel 1 | Heating/cooling change-over | 1 Bit | CWTU | |
| 5 | Object 6 | 1 Bit | CT | ||
| 5 | Channel 1 | Feedback for fan coil active | 1 Bit | CT | |
| 6 | Object 7 | 1 Bit | CT | ||
| 6 | Channel 1 | Feedback for fan level 1 | 1 Bit | CT | |
| 6 | Channel 1 | Feedback for fan level 1 | 1 Bit | CR | |
| 7 | Object 8 | 1 Bit | CT | ||
| 7 | Channel 1 | Feedback for fan level 2 | 1 Bit | CT | |
| 7 | Channel 1 | Feedback for fan level 2 | 1 Bit | CR | |
| 8 | Object 9 | 1 Bit | CT | ||
| 8 | Channel 1 | Feedback for fan level 3 | 1 Bit | CT | |
| 8 | Channel 1 | Feedback for fan level 3 | 1 Bit | CR | |
| 9 | Object 10 | 1 Bit | CT | ||
| 9 | Channel 1 | Feedback for fan level 4 | 1 Bit | CT | |
| 9 | Channel 1 | Feedback for fan level 4 | 1 Bit | CR | |
| 10 | Object 11 | 1 Bit | CT | ||
| 10 | Channel 1 | Feedback for fan level 5 | 1 Bit | CT | |
| 10 | Channel 1 | Feedback for fan level 5 | 1 Bit | CR | |
| 11 | Object 12 | 1 Bit | CT | ||
| 11 | Channel 1 | Feedback for fan level 6 | 1 Bit | CR | |
| 11 | Channel 1 | Feedback for fan level 6 | 1 Bit | CT | |
| 12 | Object 13 | 1 Byte | CT | ||
| 12 | Channel 1 | Feedback for active fan level | 1 Byte | CT | |
| 12 | Channel 1 | Feedback for active fan level | 1 Byte | CR | |
| 13 | Object 14 | 1 Bit | CW | ||
| 13 | Channel 1 | Request feedback | 1 Bit | CW | |
| 14 | Object 15 | 1 Bit | CW | ||
| 14 | Channel 1 | Disabling function | 1 Bit | CW | |
| 15 | Object 16 | 1 Bit | CT | ||
| 15 | Channel 1 | Fault messg. for cycl. monit. | 1 Bit | CT | |
| 16 | Object 17 | 1 Bit | CW | ||
| 16 | Channel 1 | Enable fan protection | 1 Bit | CW | |
| 17 | Object 18 | 1 Bit | CW | ||
| 17 | Channel 1 | Level limitation | 1 Bit | CW | |
| 18 | Object 19 | 1 Bit | CW | ||
| 18 | Channel 1 | Man. fan lev. active/inactive | 1 Bit | CW | |
| 18 | Channel 1 | Deactivate man. fan lev. | 1 Bit | CW | |
| 19 | Object 20 | 1 Byte | CW | ||
| 19 | Channel 1 | Man. fan lev. specification | 1 Byte | CW | |
| 20 | Object 21 | 1 Bit | CW | ||
| 20 | Channel 1 | Man. fan lev. specification | 1 Bit | CW | |
| 21 | Object 22 | 1 Bit | CT | ||
| 21 | Channel 1 | Man. fan lev. feedback | 1 Bit | CT | |
| 22 | Object 23 | 1 Byte | CW | ||
| 22 | Channel 2 | Command value for heating | 1 Byte | CW | |
| 23 | Object 24 | 1 Byte | CW | ||
| 23 | Channel 2 | Command value for cooling | 1 Byte | CW | |
| 24 | Object 25 | 1 Bit | CW | ||
| 24 | Channel 2 | Heating/cooling change-over | 1 Bit | CWTU | |
| 24 | Channel 2 | Heating/cooling change-over | 1 Bit | CW | |
| 25 | Object 26 | 1 Bit | CT | ||
| 25 | Channel 2 | Feedback for fan coil active | 1 Bit | CT | |
| 26 | Object 27 | 1 Bit | CT | ||
| 26 | Channel 2 | Feedback for fan level 1 | 1 Bit | CT | |
| 26 | Channel 2 | Feedback for fan level 1 | 1 Bit | CR | |
| 27 | Object 28 | 1 Bit | CT | ||
| 27 | Channel 2 | Feedback for fan level 2 | 1 Bit | CT | |
| 27 | Channel 2 | Feedback for fan level 2 | 1 Bit | CR | |
| 28 | Object 29 | 1 Bit | CT | ||
| 28 | Channel 2 | Feedback for fan level 3 | 1 Bit | CT | |
| 28 | Channel 2 | Feedback for fan level 3 | 1 Bit | CR | |
| 29 | Object 30 | 1 Bit | RWTU | ||
| 30 | Object 31 | 1 Bit | RWTU | ||
| 31 | Object 32 | 1 Bit | RWTU | ||
| 32 | Object 33 | 1 Byte | CT | ||
| 32 | Channel 2 | Feedback for active fan level | 1 Byte | CT | |
| 32 | Channel 2 | Feedback for active fan level | 1 Byte | CR | |
| 33 | Object 34 | 1 Bit | CW | ||
| 33 | Channel 2 | Request feedback | 1 Bit | CW | |
| 34 | Object 35 | 1 Bit | CW | ||
| 34 | Channel 2 | Disabling function | 1 Bit | CW | |
| 35 | Object 36 | 1 Bit | CT | ||
| 35 | Channel 2 | Fault messg. for cycl. monit. | 1 Bit | CT | |
| 36 | Object 37 | 1 Bit | CW | ||
| 36 | Channel 2 | Enable fan protection | 1 Bit | CW | |
| 37 | Object 38 | 1 Bit | CW | ||
| 37 | Channel 2 | Level limitation | 1 Bit | CW | |
| 38 | Object 39 | 1 Bit | CW | ||
| 38 | Channel 2 | Deactivate man. fan lev. | 1 Bit | CW | |
| 38 | Channel 2 | Man. fan lev. active/inactive | 1 Bit | CW | |
| 39 | Object 40 | 1 Byte | CW | ||
| 39 | Channel 2 | Man. fan lev. specification | 1 Byte | CW | |
| 40 | Object 41 | 1 Bit | CW | ||
| 40 | Channel 2 | Man. fan lev. specification | 1 Bit | CW | |
| 41 | Object 42 | 1 Bit | CT | ||
| 41 | Channel 2 | Man. fan lev. feedback | 1 Bit | CT | |
| 42 | Object 43 | 1 Bit | CW | ||
| 42 | Output 8 | Switching | 1 Bit | CW | |
| 43 | Object 44 | 1 Bit | CW | ||
| 43 | Output 7 | Switching | 1 Bit | CW | |
| 44 | Object 45 | 1 Bit | CW | ||
| 44 | Output 6 | Switching | 1 Bit | CW | |
| 45 | Object 46 | 1 Bit | CW | ||
| 45 | Output 5 | Switching | 1 Bit | CW | |
| 46 | Object 47 | 1 Bit | CW | ||
| 46 | Output 4 | Switching | 1 Bit | CW | |
| 47 | Object 48 | 1 Bit | CW | ||
| 47 | Output 3 | Switching | 1 Bit | CW |
Parameters (107)
| Parameter | Type | Default |
|---|---|---|
| Number of fan coil channels | list | 1 fan coil channel (maximum of 6 fan levels) |
| Type of fan coil system Channel 1 | list | 2-pipe only heating |
| Type of fan coil system | list | 2-pipe only heating |
| Type of fan coil system Channel 2 | list | 2-pipe only heating |
| Delay after bus voltage return Minutes (0...59) | unsignedInt 0…59 | 0 |
| Seconds (0...59) | unsignedInt 0…59 | 17 |
| Time cycl. transm. of feedback telegrams Hours (0...23) | unsignedInt 0…23 | 0 |
| Minutes (0...59) | unsignedInt 0…59 | 2 |
| Behaviour after ETS programming | list | switch off all valve & fan outputs |
| Behaviour in case of bus voltage failure: | list | switch off all valve & fan outputs |
| Behaviour after bus or mains voltage return | list | switch off all valve & fan outputs |
| Read request to "Heating/cooling change-over" object? | list | no |
| Delay time for read request Seconds (0...59) | unsignedInt 0…59 | 30 |
| Valve protection | list | deactivated |
| Fan protection | list | deactivated |
| Number of fan levels | list | 6 |
| Number of fan levels | list | 3 |
| Controlling the fan levels | list | only one fan output switches (change-over princip) |
| Command value lower limit for fan level 1 (1...100 %) | unsignedInt 1…100 | 5 |
| Command value lower limit for fan level 2 (1...100 %) | unsignedInt 1…100 | 20 |
| Command value lower limit for fan level 3 (1...100 %) | unsignedInt 1…100 | 40 |
| Command value lower limit for fan level 4 (1...100 %) | unsignedInt 1…100 | 60 |
| Command value lower limit for fan level 5 (1...100 %) | unsignedInt 1…100 | 80 |
| Command value lower limit for fan level 6 (1...100 %) | unsignedInt 1…100 | 95 |
| Hysteresis for level change-over (0...20 %; 0 = hysteresis deactivated) | unsignedInt 0…20 | 10 |
| Fan level when the fan is switched on | list | fan level 1 |
| Fan level when the fan is switched on | list | as specified by command value lower limit |
| Switch on to switch-on level | list | 2 |
| Dwell time for switch-on level Seconds (1...59) | unsignedInt 1…59 | 15 |
| Fan switch-on delay for heating Minutes (0...59) | unsignedInt 0…59 | 0 |
| Seconds (0...59) | unsignedInt 0…59 | 30 |
| Fan switch-off delay for cooling Minutes (0...59) | unsignedInt 0…59 | 0 |
| Pause "OFF" for level change-over Seconds (0...2) | unsignedInt 0…2 | 1 |
| Dwell time for level change-over Seconds (0...2) | unsignedInt 0…2 | 1 |
| Milliseconds (1...9 * 100 ms) | unsignedInt 1…9 | 1 |
| Level limitation via object | list | disabled |
| Fan level with limitation | list | switch off fan |
| Fan level with limitation | list | 1 |
| Feedback for the active fan level | list | no |
| Type of feedback | list | fan levels via value |
| Feedback object "Fan coil active" | list | disabled |
| Time delay for feedback telegrams after bus voltage return? | list | no |
| Time delay for feedback "Fan coil active" after bus vltg ret.? | list | no |
| Time delay for feedback "active fan lev" after bus vltg ret.? | list | no |
| Cyclical transmission of the feedback telegrams? | list | no (transmit only in the event of an update) |
| Cyclical transmission of the feedback "Fan coil active"? | list | no (transmit only in the event of an update) |
| Cyclical transmission of the feedback "active fan level"? | list | no (transmit only in the event of an update) |
| Request object for feedback "active fan level" | list | disabled |
| Request object for feedback "Fan coil active" | list | disabled |
| Request object for feedback telegrams | list | disabled |
| Manual fan control | list | disabled |
| Activation of manual fan control | list | via object "Man. fan lev. active/inactive" |
| Fan level change-over in case of manual specification via | list | switching direction object (1 bit) |
| Manual fan control only with active heating? | list | no |
| Manual fan control only with active cooling? | list | no |
| Manual fan control only with active heating/cooling? | list | no |
| Activate manual fan control after bus or mains vltg. return? | list | no |
| Cyclical monitoring of the command values | list | deactivated |
| Monitoring time Hours (0...23) | unsignedInt 0…23 | 0 |
| Minutes (1...59) | unsignedInt 1…59 | 30 |
| Reaction at the end of the monitoring time | list | switch off all valve & fan outputs |
| Fan level | list | 1 |
| Fault message at the end of the monitoring time | list | disabled |
| Disabling function | list | deactivated |
| Polarity of the disabling object | list | 0 = enabled; 1 = disabled |
| Reaction at the beginning of the disabling function | list | switch off all valve & fan outputs |
| Reaction at the end of the disabling function | list | switch off all valve & fan outputs |
| Command value lower limit for fan level 2 (1...100 %) | unsignedInt 1…100 | 30 |
| Command value lower limit for fan level 3 (1...100 %) | unsignedInt 1…100 | 60 |
| Manual control in case of bus voltage failure | list | enabled |
| Manual control during bus operation | list | enabled |
| Disabling function ? | list | no |
| Polarity of disabling object | list | 0 = enabled; 1 = disabled |
| Transmit status ? | list | no |
| Status object function and polarity | list | 0 = inactive; 1 = manual control active |
| Behaviour at the end of permanent manual control during bus operation | list | no change |
| Bus control of the channels during bus oper. can be disabled ? | list | no |
| Bus control of the channels can be disabled during bus oper. ? | list | no |
| Output 1 | list | valve for cooling |
| Output 1 | list | Channel 1: valve for heating |
| Output 1 | list | combined valve for heating/cooling |
| Output 1 | list | valve for heating |
| Output 1 | list | Channel 1: valve for cooling |
| Output 1 | list | Channel 1: combined valve for heating/cooling |
| Output 2 | list | unused |
| Output 2 | list | valve for heating |
| Output 2 | list | Channel 1: fan level 1 |
| Output 3 | list | Channel 1: fan level 2 |
| Output 3 | list | simple switching output |
| Output 3 | list | fan level 1 |
| Output 4 | list | fan level 2 |
| Output 4 | list | simple switching output |
| Output 4 | list | Channel 1: fan level 3 |
| Output 5 | list | simple switching output |
| Output 5 | list | fan level 3 |
| Output 5 | list | Channel 2: valve for cooling |
| Output 5 | list | Channel 2: combined valve for heating/cooling |
| Output 5 | list | Channel 2: valve for heating |
| Output 6 | list | fan level 4 |
| Output 6 | list | simple switching output |
| Output 6 | list | Channel 2: fan level 1 |
| Output 7 | list | fan level 5 |
| Output 7 | list | simple switching output |
| Output 7 | list | Channel 2: fan level 2 |
| Output 8 | list | fan level 6 |
| Output 8 | list | simple switching output |
| Output 8 | list | Channel 2: fan level 3 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Switching, fan coil 20B011 1.1 latest | $20B0 | 05AC | 2026-11-25 | 184 KB | Download |
About this file
This is the official ETS product database for the Panasonic KNX FANCOIL ACTUATOR (WRKT71445NC), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Panasonic
- KNX HEATING ACTUATOR WITH CONTROLLER 6 GANG WRKT72645NC
- KNX POWER SUPPLY UNIT 320 mA WRKT20145NC
- KNX POWER SUPPLY UNIT 640 mA WRKT20275NC
- KNX Power Supply 320mA PS132 WRKT20305NC
- KNX Power Supply 640 mA PS164 WRKT20315NC
- KNX AREA/LINE COUPLER WRKT21015NC
- KNX AREA / LINE COUPLER WRKT21025NC
- KNX SECURE AREA/LINE COUPLER WZ WRKT21035NC
- KNX DALI GATEWAY GV 1/2 Channel WRKT22145/22155NC
- KNX IP INTERFACE WRKT23305NC
- KNX IP ROUTER WRKT23315NC
- KNX SECURE IP INTERFACE WZ WRKT23505NC