MK2061
Moorgen Deutschland GmbH · Order number MK2061 · Actuator › Fan coil
Download .knxprod 6-Channel Heating Actuator/1.0 1.0 · 218 KB
Product
| Manufacturer | Moorgen Deutschland GmbH |
|---|---|
| Product name | MK2061 |
| Order number | MK2061 |
| Product text | 6-Channel Heating Actuator |
| Hardware | 6-Channel Heating Actuator |
| Medium | Twisted Pair |
| Bus current (mA) | 13.5 |
| Rail mounted | Yes |
| Width (mm) | 72 |
| Registration | Certified · 2026-03-27 |
| Languages | en-US |
| Catalog entry | M-01B9_H-AF22FE-1-O0085_HP-008C-10-78BA-O0085_CI-MK2061-1 |
| Fingerprint | 78BA |
| SHA-256 | 5b1cf3d078c68cf873bfc7d6cdf2e146913bce24710f09eee732b44e290aa59d |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: 6-Channel Heating Actuator/1.0 1.0
| Application number | $008C |
|---|---|
| Version | 1.0 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | Yes |
| Minimum ETS version | 5.0 |
| Parameters | 788 |
| Group objects | 261 |
Group objects (261)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | General | In operation | 1 Bit | 1.1 switch | CRT |
| 2 | General | Summer/Winter mode | 1 Bit | 1.1 switch | CWTU |
| 3 | General | Status of operating voltage failure | 1 Bit | 1.5 alarm | CRT |
| 4 | Output 1-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 4 | Output 1-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 5 | Output 1-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 6 | Output 1-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 7 | Output 1-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 8 | Output 1-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 9 | Output 1-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 10 | Output 1-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 11 | Output 1-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 14 | Output 2-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 14 | Output 2-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 15 | Output 2-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 16 | Output 2-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 17 | Output 2-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 18 | Output 2-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 19 | Output 2-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 20 | Output 2-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 21 | Output 2-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 24 | Output 3-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 24 | Output 3-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 25 | Output 3-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 26 | Output 3-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 27 | Output 3-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 28 | Output 3-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 29 | Output 3-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 30 | Output 3-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 31 | Output 3-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 34 | Output 4-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 34 | Output 4-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 35 | Output 4-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 36 | Output 4-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 37 | Output 4-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 38 | Output 4-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 39 | Output 4-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 40 | Output 4-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 41 | Output 4-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 44 | Output 5-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 44 | Output 5-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 45 | Output 5-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 46 | Output 5-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 47 | Output 5-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 48 | Output 5-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 49 | Output 5-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 50 | Output 5-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 51 | Output 5-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 54 | Output 6-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 54 | Output 6-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 55 | Output 6-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 56 | Output 6-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 57 | Output 6-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 58 | Output 6-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 59 | Output 6-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 60 | Output 6-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 61 | Output 6-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 64 | Controller 1-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 65 | Controller 1-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 66 | Controller 1-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 67 | Controller 1-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 67 | Controller 1-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 68 | Controller 1-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 69 | Controller 1-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 70 | Controller 1-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 71 | Controller 1-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 72 | Controller 1-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 73 | Controller 1-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 74 | Controller 1-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 75 | Controller 1-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 76 | Controller 1-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 77 | Controller 1-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 78 | Controller 1-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 79 | Controller 1-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 80 | Controller 1-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 81 | Controller 1-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 82 | Controller 1-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 83 | Controller 1-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 84 | Controller 1-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Controller 1-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 86 | Controller 1-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 87 | Controller 1-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 88 | Controller 1-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 89 | Controller 1-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 90 | Controller 1-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 91 | Controller 1-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 91 | Controller 1-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 91 | Controller 1-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 91 | Controller 1-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 92 | Controller 1-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 92 | Controller 1-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 98 | Controller 2-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 99 | Controller 2-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 100 | Controller 2-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 101 | Controller 2-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 101 | Controller 2-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 102 | Controller 2-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 103 | Controller 2-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 104 | Controller 2-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 105 | Controller 2-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 106 | Controller 2-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 107 | Controller 2-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 108 | Controller 2-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 109 | Controller 2-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 110 | Controller 2-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 111 | Controller 2-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 112 | Controller 2-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 113 | Controller 2-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 114 | Controller 2-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 115 | Controller 2-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 116 | Controller 2-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 117 | Controller 2-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 118 | Controller 2-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 119 | Controller 2-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 120 | Controller 2-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 121 | Controller 2-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 122 | Controller 2-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 123 | Controller 2-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 124 | Controller 2-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 125 | Controller 2-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 125 | Controller 2-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 125 | Controller 2-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 125 | Controller 2-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 126 | Controller 2-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 126 | Controller 2-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 132 | Controller 3-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 133 | Controller 3-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 134 | Controller 3-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 135 | Controller 3-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 135 | Controller 3-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 136 | Controller 3-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 137 | Controller 3-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 138 | Controller 3-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 139 | Controller 3-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 140 | Controller 3-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 141 | Controller 3-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 142 | Controller 3-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 143 | Controller 3-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 144 | Controller 3-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 145 | Controller 3-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 146 | Controller 3-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 147 | Controller 3-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 148 | Controller 3-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 149 | Controller 3-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 150 | Controller 3-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 151 | Controller 3-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 152 | Controller 3-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 153 | Controller 3-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 154 | Controller 3-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 155 | Controller 3-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 156 | Controller 3-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 157 | Controller 3-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 158 | Controller 3-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 159 | Controller 3-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 159 | Controller 3-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 159 | Controller 3-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 159 | Controller 3-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 160 | Controller 3-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 160 | Controller 3-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 166 | Controller 4-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 167 | Controller 4-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 168 | Controller 4-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 169 | Controller 4-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 169 | Controller 4-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 170 | Controller 4-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 171 | Controller 4-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 172 | Controller 4-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 173 | Controller 4-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 174 | Controller 4-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 175 | Controller 4-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 176 | Controller 4-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 177 | Controller 4-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 178 | Controller 4-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 179 | Controller 4-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 180 | Controller 4-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 181 | Controller 4-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 182 | Controller 4-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 183 | Controller 4-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 184 | Controller 4-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 185 | Controller 4-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 186 | Controller 4-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 187 | Controller 4-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 188 | Controller 4-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 189 | Controller 4-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 190 | Controller 4-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 191 | Controller 4-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 192 | Controller 4-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 193 | Controller 4-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 193 | Controller 4-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 193 | Controller 4-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 193 | Controller 4-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 194 | Controller 4-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 194 | Controller 4-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 200 | Controller 5-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 201 | Controller 5-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 202 | Controller 5-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 203 | Controller 5-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 203 | Controller 5-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 204 | Controller 5-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 205 | Controller 5-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 206 | Controller 5-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 207 | Controller 5-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 208 | Controller 5-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 209 | Controller 5-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 210 | Controller 5-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 211 | Controller 5-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 212 | Controller 5-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 213 | Controller 5-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 214 | Controller 5-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 215 | Controller 5-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 216 | Controller 5-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 217 | Controller 5-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 218 | Controller 5-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 219 | Controller 5-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 220 | Controller 5-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 221 | Controller 5-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 222 | Controller 5-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 223 | Controller 5-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 224 | Controller 5-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 225 | Controller 5-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 226 | Controller 5-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 227 | Controller 5-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 227 | Controller 5-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 227 | Controller 5-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 227 | Controller 5-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 228 | Controller 5-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 228 | Controller 5-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 234 | Controller 6-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 235 | Controller 6-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 236 | Controller 6-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 237 | Controller 6-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 237 | Controller 6-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 238 | Controller 6-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 239 | Controller 6-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 240 | Controller 6-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 241 | Controller 6-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 242 | Controller 6-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 243 | Controller 6-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 244 | Controller 6-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 245 | Controller 6-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 246 | Controller 6-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 247 | Controller 6-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 248 | Controller 6-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 249 | Controller 6-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 250 | Controller 6-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 251 | Controller 6-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 252 | Controller 6-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 253 | Controller 6-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 254 | Controller 6-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 255 | Controller 6-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 256 | Controller 6-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 257 | Controller 6-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 258 | Controller 6-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 259 | Controller 6-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 260 | Controller 6-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 261 | Controller 6-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 261 | Controller 6-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 261 | Controller 6-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 261 | Controller 6-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 262 | Controller 6-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 262 | Controller 6-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
Parameters (117)
| Parameter | Type | Default |
|---|---|---|
| Send delay after voltage recovery [0..15] | unsignedInt 0…15 | 5 |
| Send cycle of "In operation" telegram [1..240,0=inactive] | unsignedInt 0…240 | 0 |
| Thermal driving | list | 230V AC |
| Report operating voltage failure status | unsignedInt 0…1 | 1 |
| Number of valve outputs | list | 6 |
| Number of room temperature controllers | list | 6 |
| Manual operation | unsignedInt 0…1 | 1 |
| Manual to automatic by | list | Both long press and automatic delay time |
| Delay time [10..6000] | unsignedInt 10…6000 | 10 |
| Summer/Winter mode | list | Disable |
| Summer/Winter mode after download | list | Unchange |
| Description (max 30char.) | text | |
| Controller from | list | Local controller 1 |
| Control value for valve output (1bit/1byte) | list | Control value of cooling |
| Control value for valve output (1bit) | list | Control value of cooling |
| Monitoring control value | unsignedInt 0…1 | 0 |
| Monitoring period of control value [10..65535] | unsignedInt 10…65535 | 60 |
| Control value after fault occurs (at summer) [0..100] | unsignedInt 0…100 | 0 |
| Control value after fault occurs [0..100] | unsignedInt 0…100 | 0 |
| Control value after fault occurs (at winter) [0..100] | unsignedInt 0…100 | 0 |
| Reply mode of Obj. "Control value fault" | list | Respond after change |
| Valve control mode | list | Continuous PWM(use PI control) |
| Valve type | list | Normal(de-energised closed) |
| PWM cycle time [1..255] | unsignedInt 1…255 | 15 |
| Valve position after download | list | Close valve |
| If bus recovery, valve position | list | Unchange |
| Reply mode for valve status | list | Respond after change |
| Minimum limitation of control value | unsignedInt 0…50 | 0 |
| Maximum limitation of control value | unsignedInt 51…100 | 100 |
| Control value lower than the minimum limitation | list | 0%=0%,otherwise=Minimum limitation value |
| Valve purge function | unsignedInt 0…1 | 0 |
| Duration of valve purge time [1..255] | unsignedInt 1…255 | 10 |
| Automatic valve purge | unsignedInt 0…1 | 0 |
| Purge Cycle in weeks [1..12] | unsignedInt 1…12 | 1 |
| Reply mode for valve purge status | list | Respond after change |
| Valve disable function | list | Disable |
| Forced operation function | list | Disable |
| Control value for forced operation (at summer) [0..100] | unsignedInt 0…100 | 30 |
| Control value for forced operation [0..100] | unsignedInt 0…100 | 30 |
| Control value for forced operation (at winter) [0..100] | unsignedInt 0…100 | 70 |
| Report short-circuit/overload status | unsignedInt 0…1 | 0 |
| Room temperature reference from | list | External sensor 1 |
| Period for request external sensor [0..255] | unsignedInt 0…255 | 10 |
| Combination ratio for external sensor 1 to sensor 2 | list | 50% to 50% |
| Send temperature when the result change by | list | 1.0K |
| Cyclically send temperature [0..255] | unsignedInt 0…255 | 0 |
| Control value after temp. error[0..100] (if 2-point control, set value '0'=0, set value '>0'=1) | unsignedInt 0…100 | 0 |
| Room temperature control mode | list | Heating |
| Heating/Cooling switchover | list | Via object |
| Heating/Cooling status after download | list | Heating |
| Heating/Cooling status after voltage recovery | list | As before voltage failure |
| Room temperature control system | list | 4 pipes system |
| Operation mode | unsignedInt 0…1 | 0 |
| Initial setpoint temperature | list | 20.0 |
| Upper dead zone | list | 2.0 |
| Lower dead zone | list | 2.0 |
| Controller status after download | list | Comfort mode |
| Controller status after voltage recovery | list | As before voltage failure |
| Extended comfort mode [0..255,0=inactive] | unsignedInt 0…255 | 0 |
| 1 bit object function for operation mode | unsignedInt 0…1 | 0 |
| 1 bit object for standby mode | unsignedInt 0…1 | 1 |
| Scene function | unsignedInt 0…1 | 0 |
| Window contact input function | unsignedInt 0…1 | 0 |
| Delay for window contact [0..65535] | unsignedInt 0…65535 | 15 |
| Controller mode for open window | list | Frost/heat protection |
| Bus presence detector function | unsignedInt 0…1 | 0 |
| Setpoint method for operating mode | list | Absolute |
| Base setpoint temperature | list | 20.0 |
| Additional setpoint offset for setpoint adjustment | list | Disable |
| Step of setpoint offset | list | 0.5K |
| Min. setpoint offset [-10..0] | signedInt -10…0 | -5 |
| Max. setpoint offset [0..10] | unsignedInt 0…10 | 5 |
| Reduced heating in standby mode [0..10] | list | 2 |
| Reduced heating in economy mode [0..10] | list | 4 |
| Setpoint temperature in frost protection mode [5..10] | list | 7 |
| Increased cooling in standby mode [0..10] | list | 2 |
| Increased cooling in economy mode [0..10] | list | 4 |
| Setpoint temperature in heat protection mode [30..37] | list | 35 |
| Setpoint temperature in comfort mode [5..37] | list | 21 |
| Setpoint temperature in standby mode [5..37] | list | 19 |
| Setpoint temperature in economy mode [5..37] | list | 17 |
| Setpoint temperature in comfort mode [5..37] | list | 23 |
| Setpoint temperature in standby mode [5..37] | list | 25 |
| Setpoint temperature in economy mode [5..37] | list | 27 |
| Minimum zone between heating and cooling setpoint | list | 2.0 |
| Min. setpoint temperature [5..37] | list | 10 |
| Max. setpoint temperature [5..37] | list | 32 |
| Type of heating control | list | Continuous control(use PI control) |
| Invert control value | list | No |
| Lower Hysteresis [0..200] | unsignedInt 0…200 | 10 |
| Upper Hysteresis [0..200] | unsignedInt 0…200 | 10 |
| Heating speed | list | Hot water heating(5K/150min) |
| Proportional range [10..100] | unsignedInt 0…100 | 40 |
| Reset time [0..255] | unsignedInt 0…255 | 150 |
| Cyclically send control value [0..255] | unsignedInt 0…255 | 10 |
| Type of cooling control | list | Continuous control(use PI control) |
| Cooling speed | list | Cooling ceiling (5K/240min) |
| Proportional range [10..100] | unsignedInt 10…100 | 40 |
| Type of heating/cooling control | list | Continuous control(use PI control) |
| Control value after temp. error (at summer) [0..100] (if 2-point control, set value '0'=0, set value '>0'=1) | unsignedInt 0…100 | 0 |
| Control value after temp. error (at winter) [0..100] (if 2-point control, set value '0'=0, set value '>0'=1) | unsignedInt 0…100 | 0 |
| Limit control mode switchover at summer | unsignedInt 0…1 | 0 |
| Limit control mode switchover at winter | unsignedInt 0…1 | 0 |
| 1->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| Temperature | list | Unchange |
| Operation mode | list | Unchange |
| 2->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 3->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 4->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 5->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| Controller from | list | External controller |
| Setpoint Temperature error | unsignedInt 0…1 | 0 |
| Send control value on change by [0..100,0=inactive] | unsignedInt 0…100 | 4 |
| Control value for valve output (1byte) | list | Control value of cooling |
| Evaluate valve open/close times for PWM | unsignedInt 0…1 | 0 |
| Fully open time | unsignedInt 0…600 | 120 |
| Fully close time | unsignedInt 0…600 | 120 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| 6-Channel Heating Actuator/1.0 1.0 latest | $008C | 78BA | 2026-11-25 | 218 KB | Download |
About this file
This is the official ETS product database for the Moorgen Deutschland GmbH MK2061 (MK2061), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Moorgen Deutschland GmbH
- 4-Channel Motor Actuator MK1007
- 8-Channel 16A Switch Actuator MK2016
- 12-Channel 16A Switch Actuator MK2017
- 4-Channel Universal Switch Actuator MK2025
- 8-Channel 10A Universal Switch Actuator MK2026
- 16-Channel 10A Switch Actuator MK2027
- 4-Channel 1-10V Dimming Actuator MK2031
- MK2053(16A/20A) MK2053(16A/20A)
- MK2055(16A/20A) MK2055(16A/20A)
- MK2056(16A/20A) MK2056(16A/20A)
- MK2057 MK2057
- MK2058 MK2058