Room temper. contr. 1-fold with adjustment knob AP SCN-RT1APE.01
MDT technologies GmbH · Order number SCN-RT1APE.01 · Archive › Temperature Controller › Room Temperature Controller
Room Temp. Contr. with adjustment knob surface mounted
Download .knxprod Room temperature controller with adjustment knob 1.4 · 101 KB
Product
| Manufacturer | MDT technologies GmbH |
|---|---|
| Product name | Room temper. contr. 1-fold with adjustment knob AP |
| Order number | SCN-RT1APE.01 |
| Hardware | Raumtemperaturregler mit Einstellrad |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | No |
| Registration | Registered |
| Languages | de-DE, en-US, es-ES, fr-FR |
| Catalog entry | M-0083_H-66-1_HP-0044-14-7E32_CI-SCN.2DRT1APE.2E01-2 |
| Fingerprint | 7E32 |
| SHA-256 | 98726622f1636843d52907cb3a894ee0264cd51865db003c44051bca99c99e82 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Room temperature controller with adjustment knob 1.4
| Application number | $0044 |
|---|---|
| Version | 1.4 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 123 |
| Group objects | 47 |
Group objects (47)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Current temperature value | Transmit temperature value | 2 Bytes | 9.1 temperature (°C) | CRT |
| 1 | Higher message value | Send message | 1 Bit | CRT | |
| 2 | Below message value | Send message | 1 Bit | CRT | |
| 3 | Frost alarm | Send alarm | 1 Bit | CRT | |
| 4 | Heat alarm | Send alarm | 1 Bit | CRT | |
| 5 | External sensor | Read external sensor | 2 Bytes | 9.1 temperature (°C) | CW |
| 6 | Setpoint comfort | Set setpoint | 2 Bytes | 9.1 temperature (°C) | CRWT |
| 7 | Manual set point value offset | Reduction / increase | 2 Bytes | 9.2 temperature difference (K) | CW |
| 7 | Manual set point value offset | Reduction / increase | 2 Bytes | 9.2 temperature difference (K) | CWT |
| 8 | Control value heating | Send control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | Control value heating | Send control value | 1 Bit | CRT | |
| 8 | Control value heating/cooling | Send control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 8 | Control value heating/cooling | Send control value | 1 Bit | CRT | |
| 9 | Control value additional heating | Send control value | 1 Bit | CRT | |
| 10 | Control value cooling | Send control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 10 | Control value cooling | Send control value | 1 Bit | CRT | |
| 10 | Status Cooling / Heating | 0=Cooling 1=Heating | 1 Bit | CRT | |
| 11 | Mode comfort | Switch mode | 1 Bit | 1.1 switch | CW |
| 12 | Mode night | Switch mode | 1 Bit | 1.1 switch | CW |
| 13 | Mode frost protection | Switch mode | 1 Bit | 1.1 switch | CW |
| 13 | Mode heat protection | Switch mode | 1 Bit | 1.1 switch | CW |
| 13 | Mode frost/heat protection | Switch mode | 1 Bit | 1.1 switch | CW |
| 14 | Heating disable object | Disable heating | 1 Bit | 1.3 enable | CW |
| 15 | Cooling disable object | Disable cooling | 1 Bit | 1.3 enable | CW |
| 16 | Object 16 | 1 Bit | |||
| 17 | Heating request | Send request | 1 Bit | 1.1 switch | CRT |
| 18 | Cooling request | Send request | 1 Bit | 1.1 switch | CRT |
| 19 | Heating/cooling switchover | 0=Cooling 1=Heating | 1 Bit | CWT | |
| 20 | Guiding value | Setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 21 | Max memory value | Read memory | 2 Bytes | 9.1 temperature (°C) | CRT |
| 22 | Min memory value | Read memory | 2 Bytes | 9.1 temperature (°C) | CRT |
| 23 | Min/max memory reset | Reset memory | 1 Bit | 1.3 enable | CW |
| 24 | Reset setpoint value | Parameter read in | 1 Bit | 1.3 enable | CW |
| 25 | DPT_HVAC Status | Send controller status | 1 Byte | CRT | |
| 26 | Object 26 | 1 Byte | |||
| 27 | LCD backlight | Backlight on | 1 Bit | 1.1 switch | CW |
| 28 | Error external sensor | Error message | 1 Bit | CRT | |
| 29 | Current setpoint | Send setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 30 | RHCC Status | Send controller status | 2 Bytes | CRT | |
| 31 | mode selection | select mode | 1 Byte | CRWTU | |
| 31 | mode selection | select mode | 1 Byte | CW | |
| 32 | Manual set point value offset | Increase / Reduction (1=+/0=-) | 1 Bit | CW | |
| 33 | Flow temperature | Read external sensor | 2 Bytes | 9.1 temperature (°C) | CWT |
| 34 | Object 34 | 1 Byte | |||
| 35 | Object 35 | 1 Byte | |||
| 36 | Object 36 | 1 Byte | |||
| 37 | Object 37 | 1 Byte |
Parameters (65)
| Parameter | Type | Default |
|---|---|---|
| Startup delaytime | list | 0 s |
| Select hardware | list | SCN-RT1xPE.xx with setwheel |
| Send actual value after change of | list | Disable |
| Send actual temperature cyclically | list | Disable |
| Send min/max value | list | Disable |
| Internal sensor correction value (value * 0.1K) | signedInt -50…50 | 0 |
| Internal/external sensor | list | 100 % intern |
| Alarm | list | inactive |
| Frostalarm if value < | list | 7 °C |
| Heatalarm if value > | list | 35 °C |
| Messages | list | inactive |
| Message if value > | list | 26 °C |
| Message if value < | list | 13 °C |
| Controller type | list | Heating |
| Priority | list | Frost(Heat protection)/Comfort/Night/Standby |
| Basic comfort setpoint (°C) | list | 21,0 °C |
| Standby reduction (K) | list | 3,0 K |
| Night reduction (K) | list | 2,0 K |
| Setpoint frost protection (°C) | list | 7 °C |
| Setpoint offset with set wheel | list | inactive |
| Set point value offset via 2Byte object | list | inactive |
| Send status of setpoint offset | list | inactive |
| Advanced function can be apply only for hardware starting from version R3.5 | text | <- TIP |
| Set point value offset via 1Bit object | list | inactive |
| Advanced function can be apply only for hardware starting from version R3.2 | text | <- TIP |
| Step range | list | 0,5 K |
| Max setpoint offset | list | 3,0 K |
| Max setpoint offset vaild for | list | Comfort |
| Reset setpoint offset after change of mode | list | No |
| Send setpoint change | list | No |
| Flow temperature | list | inactive |
| Advanced function can be apply only for hardware starting from version R3.6 | text | <- TIP |
| Flow temperature limit | list | 40 °C |
| Operating mode after reset | list | Comfort with parameterized set point |
| Send status on object 31 "Mode selection" | list | No |
| Heating disable object | list | inactive |
| Heating request object enabled | list | No |
| Guiding | list | inactive |
| Guiding value minimum (°C) | signedInt -100…100 | 28 |
| Guiding value maximum (°C) | signedInt -100…100 | 38 |
| Setpoint variation at maximum guiding value (°C) | signedInt -100…100 | 10 |
| Standby increase (K) | list | 3,0 K |
| Night increase (K) | list | 2,0 K |
| Setpoint heat protection (°C) | list | 35 °C |
| Cooling disable object | list | inactive |
| Cooling request object enabled | list | No |
| Dead zone between heating and cooling (K) | list | 2,0 K |
| Setpoint | list | PI control continuous |
| Direction of controller | list | normal |
| Max value of control value | list | 100% |
| Heating system | list | Adjustment via control parameter |
| Heating system | list | Underfloor heating (4K / 150min) |
| Proportional range (K) | list | 2 K |
| Reset time (min) | list | 150 min |
| Send control value cyclic | list | Disable |
| PWM cycletime (min) | list | 10 min |
| Hysteresis (K) | list | 2,0 K |
| Use additional level | list | No |
| Setpoint | list | 2-step control (switching) |
| Distance (K) | list | 2,0 K |
| Cooling system | list | Adjustment via control parameter |
| Cooling system | list | Cooling ceiling (4K / 150min) |
| System | list | 2 Pipe system |
| Heating/cooling switch over | list | automatically |
| Send control value for heating and cooling cyclic | list | Disable |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Room temperature controller with adjustment knob 1.4 latest | $0044 | 7E32 | 2026-11-25 | 101 KB | Download |
About this file
This is the official ETS product database for the MDT technologies GmbH Room temper. contr. 1-fold with adjustment knob AP (SCN-RT1APE.01), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from MDT technologies GmbH
- AKD-0224V.01 LED Controller 2 channel AKD-0224V.01
- AKD-0324V.01 RGB LED Controller AKD-0324V.01
- AKD-0410V.01 Dimming Control Unit 4-f, 4TE, 1-10V AKD-0410V.01
- AKD-0424R.01 RGBW LED Controller, MDRC AKD-0424R.01
- AKD-0424V.01 RGBW LED Controller AKD-0424V.01
- AKH-0400.01 Heating actuator 4-fold, 2SU,24/230VAC AKH-0400.01
- AKH-0800.01 Heating actuator 8-fold, 4SU,24/230VAC AKH-0800.01
- AKK-01UP.01 Switch Actuator 1-fold, UP, 16A AKK-01UP.01
- AKK-0216.01 Switch Actuator 2-fold, 2SU, 16A AKK-0216.01
- AKK-0216.02 Switch Actuator 2-fold, 2SU, 16A AKK-0216.02
- AKK-02UP.01 Switch Actuator 2-fold, UP, 6A AKK-02UP.01
- AKK-03UP.01 Switch Actuator 3fold, FanCoil AKK-03UP.01