KNX Database

Sensor LC-MLD02CX

LightControl · Order number LC-MLD02CX · Sensors

Download .knxprod Sensor 0.1 · 127 KB

Product

ManufacturerLightControl
Product nameSensor
Order numberLC-MLD02CX
HardwareSensor
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2025-07-22
Languagesen-US
Catalog entryM-0160_H-00014B070402-2-O014B_HP-0704-01-75FF-O014B_CI-LC.2DMLD02CX-1
Fingerprint75FF
SHA-2566f5465790425ab9d21087e5422e09d242d0bd1b8f0c992a8e03020a08a1e0bfb
First seen2026-11-25
MarketsGermany

Application program: Sensor 0.1

Application number$0704
Version0.1
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version5.0
Parameters194
Group objects58
Group objects (58)
NoNameFunctionSizeDPTFlags
0Brightness value (calibration)(-L...+L)2 Bytes9.4 lux (Lux)CRWTU
1Brightness value (output)value in lux2 Bytes9.4 lux (Lux)CRWTU
2Light control block Ablock/unblock1 Bit1.1 switchCRWTU
3Overwrite light threshold Avalue in lux2 Bytes9.4 lux (Lux)CRWTU
4External brightness value A (input)value in lux2 Bytes9.4 lux (Lux)CRWTU
5Light control 1-bit output AOn/Off1 Bit1.1 switchCRWTU
6Light control 4-bit output A4-bit value4 Bit3.7 dimming controlCRWTU
7Light control 1-byte output A1-byte value1 Byte5.1 percentage (0..100%)CRWTU
8Light control block Bblock/unblock1 Bit1.1 switchCRWTU
9Overwrite light threshold Bvalue in lux2 Bytes9.4 lux (Lux)CRWTU
10External brightness value B (input)value in lux2 Bytes9.4 lux (Lux)CRWTU
11Light control 1-bit output BOn/Off1 Bit1.1 switchCRWTU
12Light control 4-bit output B4-bit value4 Bit3.7 dimming controlCRWTU
13Light control 1-byte output B1-byte value1 Byte5.1 percentage (0..100%)CRWTU
14Motion control blockblock/unblock1 Bit1.1 switchCRWTU
15Motion sensor trigger locklock/unlock1 Bit1.1 switchCRWTU
16Motion, Overwrite light thresholdvalue in lux2 Bytes9.4 lux (Lux)CRWTU
17Motion, External brightness value (input)value in lux2 Bytes9.4 lux (Lux)CRWTU
18Motion, Master inputOn/Off1 Bit1.1 switchCRWTU
19Start of motion, 1-bit outputOn/Off1 Bit1.1 switchCRWTU
20Start of motion, 4-bit output4-bit value4 Bit3.7 dimming controlCRWTU
21Start of motion, 1-byte output1-byte value1 Byte5.1 percentage (0..100%)CRWTU
22Motion, Overwrite follow-up timein seconds2 Bytes7.5 time (s)CRWTU
23End of motion, 1-bit outputOn/Off1 Bit1.1 switchCRWTU
24End of motion, 4-bit output4-bit value4 Bit3.7 dimming controlCRWTU
25End of motion, 1-byte output1-byte value1 Byte5.1 percentage (0..100%)CRWTU
26Motion control pausepause/continue1 Bit1.1 switchCRWTU
27Motion control abortOn/Off1 Bit1.1 switchCRWTU
28Motion, Slave outputOn/Off1 Bit1.1 switchCRWTU
29Temperature value (calibration)(-T...+T)2 Bytes9.1 temperature (°C)CRWTU
30Temperature value (output)2-byte value2 Bytes9.1 temperature (°C)CRWTU
31Temperature control block Ablock/unblock1 Bit1.1 switchCRWTU
32Overwrite temperature threshold A2-byte value2 Bytes9.1 temperature (°C)CRWTU
33External temperature value A (input)2-byte value2 Bytes9.1 temperature (°C)CRWTU
34Temperature control 1-bit output AOn/Off1 Bit1.1 switchCRWTU
35Temperature control 4-bit output A4-bit value4 Bit3.8 blind controlCRWTU
36Temperature control 1-byte output A1-byte value1 Byte5.1 percentage (0..100%)CRWTU
37Temperature control block Bblock/unblock1 Bit1.1 switchCRWTU
38Overwrite temperature threshold B2-byte value2 Bytes9.1 temperature (°C)CRWTU
39External temperature value B (input)2-byte value2 Bytes9.1 temperature (°C)CRWTU
40Temperature control 1-bit output BOn/Off1 Bit1.1 switchCRWTU
41Temperature control 4-bit output B4-bit value4 Bit3.8 blind controlCRWTU
42Temperature control 1-byte output B1-byte value1 Byte5.1 percentage (0..100%)CRWTU
43Humidity value (calibration)(-H...+H)2 Bytes9.7 humidity (%)CRWTU
44Humidity value (output)2-byte value2 Bytes9.7 humidity (%)CRWTU
45Humidity control block Ablock/unblock1 Bit1.1 switchCRWTU
46Overwrite humidity threshold A2-byte value2 Bytes9.7 humidity (%)CRWTU
47External humidity value A (input)2-byte value2 Bytes9.7 humidity (%)CRWTU
48Humidity control 1-bit output AOn/Off1 Bit1.1 switchCRWTU
49Humidity control 4-bit output A4-bit value4 Bit3.8 blind controlCRWTU
50Humidity control 1-byte output A1-byte value1 Byte5.1 percentage (0..100%)CRWTU
51Humidity control block Bblock/unblock1 Bit1.1 switchCRWTU
52Overwrite humidity threshold B2-byte value2 Bytes9.7 humidity (%)CRWTU
53External humidity value B (input)2-byte value2 Bytes9.7 humidity (%)CRWTU
54Humidity control 1-bit output BOn/Off1 Bit1.1 switchCRWTU
55Humidity control 4-bit output B4-bit value4 Bit3.8 blind controlCRWTU
56Humidity control 1-byte output B1-byte value1 Byte5.1 percentage (0..100%)CRWTU
57Device status1-byte value1 ByteCRWTU
Parameters (80)
ParameterTypeDefault
Illumination detectorlistDisabled
Calibrationlistwith correction value
Send brightness valuelistNo
The mode for sending valuelisttransmit value in cycles
Correction value(lux)signedInt -200…2000
The time in cycleslist2 minutes
Send brightness value on changelistchange >= 25 Lux
Light control AlistDisabled
Blocking functionlistDisabled
Blocking valuelistblocking = 1, unblocking = 0
Blocking value after voltage recoverylistunblocking
Threshold value(lux)signedInt 0…1200500
Controlling conditionlisthigher than threshold value
Overwrite threshold value via objectlistNo
Source for brightness valuelistinternal value
Brightness tolerancelist50 Lux
1-bit output objectlistDisabled
1-bit valuelistOn
4-bit output objectlistDisabled
4-bit valuelistIncrease, Break
1-byte output objectlistDisabled
1-byte typelistscene number(1..64)
Scene numberunsignedInt 1…641
Percentagelist0%
Unsigned valueunsignedInt 0…2550
Delay time for output(s)unsignedInt 0…2550
Transmission mode for outputlistone-time transmission
Cyclic time for outputlist30 seconds
Light control BlistDisabled
Threshold value(lux)signedInt 0…1200100
Controlling conditionlistlower than threshold value
1-bit valuelistOff
4-bit valuelistDecrease, Break
Temperature detectorlistDisabled
Send temperature valuelistNo
Correction valuesignedInt -50…500
Send temperature value on changelistchange >= 2.0
Temperature control AlistDisabled
Threshold valuesignedInt -20…8025
Source for temperature valuelistinternal value
Temperature tolerancelist1
4-bit valuelistDown, Break
Cyclic time for outputlist30 minutes
Temperature control BlistDisabled
Threshold valuesignedInt -20…8015
4-bit valuelistUp, Break
Humidity detectorlistDisabled
Send humidity valuelistNo
Correction value(%)signedInt -50…500
Send humidity value on changelistchange >= 5%
Humidity control AlistDisabled
Threshold value(%)signedInt 0…10080
Source for humidity valuelistinternal value
Humidity tolerancelist5%
Humidity control BlistDisabled
Threshold value(%)signedInt 0…10030
Motion detectorlistDisabled
Function for blocking the motionlistDisabled
Relationship with brightnesslistnot related with brightness
Device works aslistnone
Device works aslistas single device
Input value as masterlistOn
Output value as slavelistOn
Dead time after triggering(s)unsignedInt 0…2555
Follow-up time in hoursunsignedInt 0…230
Follow-up time in minutesunsignedInt 0…590
Follow-up time in secondsunsignedInt 0…5930
Overwrite follow-up time via objectlistNo
Motion trigger during follow-up timelistrecalculate follow-up time when triggering
Function for pausing operationlistDisabled
For current operationlistpause = 0, continue = 1
Function for aborting operationlistDisabled
For current operationlistabort when receiving 0
Function for locking internal triggerlistDisabled
Locking valuelistlocking = 1, unlocking = 0
Locking value after bus voltage recoverylistunlocking
Dead time after end of motion(s)unsignedInt 0…2552
Device status feedbacklistDisabled
Cycle time for feedbacklist30 seconds
System stability timelist40s start up time for device

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Sensor 0.1 latest$070475FF2026-11-25127 KBDownload

About this file

This is the official ETS product database for the LightControl Sensor (LC-MLD02CX), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from LightControl

All LightControl products