KNX Database

Kermi RVU KNX interface 3000246

KERMI · Order number 3000246 · Heating, cooling and ventilation

Kermi RVU KNX interface

Download .knxprod AKRVUKNX 0.1 · 69 KB

Product

ManufacturerKERMI
Product nameKermi RVU KNX interface
Order number3000246
HardwareKermi RVU KNX interface
MediumTwisted Pair
Bus current (mA)12
Rail mountedNo
RegistrationRegistered · 2019-04-08
Languagesde-DE, fr-FR, it-IT
Catalog entryM-011A_H-000001-1_HP-4B52-01-FCD1_CI-3000246-2
FingerprintFCD1
SHA-25631f973d52f5dd9aa683a47ec1a7ed03d6f54c31dbfacb1d7e8fde39b65292bae
First seen2026-11-25
MarketsAustria, Germany, Switzerland

Application program: AKRVUKNX 0.1

Application number$4B52
Version0.1
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version4.0
Parameters23
Group objects61
Group objects (61)
NoNameFunctionSizeDPTFlags
0Controller model2 BytesDPT.7CRT
1Firmware Release2 BytesDPT.7CRT
2T-EP Firmware Release2 BytesDPT.7CRT
3Probe 1 temperature2 Bytes9.1 temperature (°C)CRT
4Probe 2 temperature2 Bytes9.1 temperature (°C)CRT
5Probe 3 temperature2 Bytes9.1 temperature (°C)CRT
6Probe 4 temperature2 Bytes9.1 temperature (°C)CRT
7Remote OFF active1 Bit1.11 stateCRT
8Bypass active1 Bit1.11 stateCRT
9Electric Pre Heater active1 Bit1.11 stateCRT
10Water pre-heating active1 Bit1.11 stateCRT
11Boost active1 Bit1.11 stateCRT
12Defrost cycle active1 Bit1.11 stateCRT
13Party Mode active1 Bit1.11 stateCRT
14On status1 Bit1.11 stateCRT
15Winter setting1 Bit1.2 booleanCRT
16Humidity setpoint2 Bytes9.7 humidity (%)CRT
17Filter counter2 Bytes7.7 time (h)CRT
18Input C1 status1 Bit1.11 stateCRT
19Input C2 status1 Bit1.11 stateCRT
20Input C3 status1 Bit1.11 stateCRT
21Input C4 status1 Bit1.11 stateCRT
22General Alarm1 Bit1.5 alarmCRT
23T1 probe failure alarm1 Bit1.5 alarmCRT
24T2 probe failure alarm1 Bit1.5 alarmCRT
25T3 probe failure alarm1 Bit1.5 alarmCRT
26T4 probe failure alarm1 Bit1.5 alarmCRT
27Timekeeper failure alarm1 Bit1.5 alarmCRT
28Frost alarm1 Bit1.5 alarmCRT
29Frost alarm (from T2 probe)1 Bit1.5 alarmCRT
30Fireplace Alarm1 Bit1.5 alarmCRT
31Pressure transducer failure alarm1 Bit1.5 alarmCRT
32Filter alarm1 Bit1.5 alarmCRT
33Fans failure1 Bit1.5 alarmCRT
34RH or CO2 sensor failure alarm1 Bit1.5 alarmCRT
35Fan thermic input alarm1 Bit1.5 alarmCRT
36Pre Heating alarm1 Bit1.5 alarmCRT
37Pre frost alarm (T2)1 Bit1.5 alarmCRT
38CO2 reading2 Bytes9.8 parts/million (ppm)CRT
39RH reading2 Bytes9.7 humidity (%)CRT
40IAQ Used1 Bit1.2 booleanCRT
41Post treatment used1 Bit1.2 booleanCRT
42HE used1 Bit1.2 booleanCRT
43Boiler boost mode used1 Bit1.2 booleanCRT
44CO2 sensor present1 Bit1.2 booleanCRT
45Differential pressure sensor present1 Bit1.2 booleanCRT
46RH sensor present1 Bit1.2 booleanCRT
47Reverse mounting1 Bit1.2 booleanCRT
48Manual Speed command1 ByteDPT.5CWU
49Manual Speed status1 ByteDPT.5CRT
50On/Off Command1 Bit1.1 switchCWU
51On/Off status1 Bit1.11 stateCRT
52Manual mode command1 Bit1.1 switchCWU
53Manual mode status1 Bit1.11 stateCRT
54Holiday mode command1 Bit1.1 switchCWU
55Holiday mode status1 Bit1.11 stateCRT
56Party mode command1 Bit1.1 switchCWU
57Party mode status1 Bit1.11 stateCRT
58Auto mode command1 Bit1.1 switchCWU
59Auto mode status1 Bit1.11 stateCRT
60Time3 Bytes10.1 time of dayCRWTU
Parameters (20)
ParameterTypeDefault
Speed 1unsignedInt 0…3525
Speed 2unsignedInt 35…7045
Speed 3unsignedInt 45…10070
Speed 4unsignedInt 100…110100
Boost SpeedunsignedInt 110…130130
Fan 2 unbalancesignedInt -20…200
Humidity samples for setpointunsignedInt 1…9696
Summer T SetpointunsignedInt 10…3026
Winter T setpointunsignedInt 10…3014
Temp for free coolingunsignedInt 10…3018
Temp for free heatingunsignedInt 10…3024
Boost timeunsignedInt 60…24060
Filter lifeunsignedInt 30…360180
CO2 minunsignedInt 400…600500
CO2 nomunsignedInt 900…11001000
CO2 maxunsignedInt 1500…20001800
CO2 Sensor rangeunsignedInt 2000…300002000
RH Low valueunsignedInt 20…3025
RH Standard valueunsignedInt 40…5045
RH Hi valueunsignedInt 60…8060

Version history

ApplicationApp noFingerprintFirst seenSizeFile
AKRVUKNX 0.1 latest$4B52FCD12026-11-2569 KBDownload

About this file

This is the official ETS product database for the KERMI Kermi RVU KNX interface (3000246), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.