Kermi RVU KNX interface 3000246
KERMI · Order number 3000246 · Heating, cooling and ventilation
Kermi RVU KNX interface
Download .knxprod AKRVUKNX 0.1 · 69 KB
Product
| Manufacturer | KERMI |
|---|---|
| Product name | Kermi RVU KNX interface |
| Order number | 3000246 |
| Hardware | Kermi RVU KNX interface |
| Medium | Twisted Pair |
| Bus current (mA) | 12 |
| Rail mounted | No |
| Registration | Registered · 2019-04-08 |
| Languages | de-DE, fr-FR, it-IT |
| Catalog entry | M-011A_H-000001-1_HP-4B52-01-FCD1_CI-3000246-2 |
| Fingerprint | FCD1 |
| SHA-256 | 31f973d52f5dd9aa683a47ec1a7ed03d6f54c31dbfacb1d7e8fde39b65292bae |
| First seen | 2026-11-25 |
| Markets | Austria, Germany, Switzerland |
Application program: AKRVUKNX 0.1
| Application number | $4B52 |
|---|---|
| Version | 0.1 |
| Mask version | MV-0705 (7.5) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 23 |
| Group objects | 61 |
Group objects (61)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Controller model | 2 Bytes | DPT.7 | CRT | |
| 1 | Firmware Release | 2 Bytes | DPT.7 | CRT | |
| 2 | T-EP Firmware Release | 2 Bytes | DPT.7 | CRT | |
| 3 | Probe 1 temperature | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 4 | Probe 2 temperature | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 5 | Probe 3 temperature | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 6 | Probe 4 temperature | 2 Bytes | 9.1 temperature (°C) | CRT | |
| 7 | Remote OFF active | 1 Bit | 1.11 state | CRT | |
| 8 | Bypass active | 1 Bit | 1.11 state | CRT | |
| 9 | Electric Pre Heater active | 1 Bit | 1.11 state | CRT | |
| 10 | Water pre-heating active | 1 Bit | 1.11 state | CRT | |
| 11 | Boost active | 1 Bit | 1.11 state | CRT | |
| 12 | Defrost cycle active | 1 Bit | 1.11 state | CRT | |
| 13 | Party Mode active | 1 Bit | 1.11 state | CRT | |
| 14 | On status | 1 Bit | 1.11 state | CRT | |
| 15 | Winter setting | 1 Bit | 1.2 boolean | CRT | |
| 16 | Humidity setpoint | 2 Bytes | 9.7 humidity (%) | CRT | |
| 17 | Filter counter | 2 Bytes | 7.7 time (h) | CRT | |
| 18 | Input C1 status | 1 Bit | 1.11 state | CRT | |
| 19 | Input C2 status | 1 Bit | 1.11 state | CRT | |
| 20 | Input C3 status | 1 Bit | 1.11 state | CRT | |
| 21 | Input C4 status | 1 Bit | 1.11 state | CRT | |
| 22 | General Alarm | 1 Bit | 1.5 alarm | CRT | |
| 23 | T1 probe failure alarm | 1 Bit | 1.5 alarm | CRT | |
| 24 | T2 probe failure alarm | 1 Bit | 1.5 alarm | CRT | |
| 25 | T3 probe failure alarm | 1 Bit | 1.5 alarm | CRT | |
| 26 | T4 probe failure alarm | 1 Bit | 1.5 alarm | CRT | |
| 27 | Timekeeper failure alarm | 1 Bit | 1.5 alarm | CRT | |
| 28 | Frost alarm | 1 Bit | 1.5 alarm | CRT | |
| 29 | Frost alarm (from T2 probe) | 1 Bit | 1.5 alarm | CRT | |
| 30 | Fireplace Alarm | 1 Bit | 1.5 alarm | CRT | |
| 31 | Pressure transducer failure alarm | 1 Bit | 1.5 alarm | CRT | |
| 32 | Filter alarm | 1 Bit | 1.5 alarm | CRT | |
| 33 | Fans failure | 1 Bit | 1.5 alarm | CRT | |
| 34 | RH or CO2 sensor failure alarm | 1 Bit | 1.5 alarm | CRT | |
| 35 | Fan thermic input alarm | 1 Bit | 1.5 alarm | CRT | |
| 36 | Pre Heating alarm | 1 Bit | 1.5 alarm | CRT | |
| 37 | Pre frost alarm (T2) | 1 Bit | 1.5 alarm | CRT | |
| 38 | CO2 reading | 2 Bytes | 9.8 parts/million (ppm) | CRT | |
| 39 | RH reading | 2 Bytes | 9.7 humidity (%) | CRT | |
| 40 | IAQ Used | 1 Bit | 1.2 boolean | CRT | |
| 41 | Post treatment used | 1 Bit | 1.2 boolean | CRT | |
| 42 | HE used | 1 Bit | 1.2 boolean | CRT | |
| 43 | Boiler boost mode used | 1 Bit | 1.2 boolean | CRT | |
| 44 | CO2 sensor present | 1 Bit | 1.2 boolean | CRT | |
| 45 | Differential pressure sensor present | 1 Bit | 1.2 boolean | CRT | |
| 46 | RH sensor present | 1 Bit | 1.2 boolean | CRT | |
| 47 | Reverse mounting | 1 Bit | 1.2 boolean | CRT | |
| 48 | Manual Speed command | 1 Byte | DPT.5 | CWU | |
| 49 | Manual Speed status | 1 Byte | DPT.5 | CRT | |
| 50 | On/Off Command | 1 Bit | 1.1 switch | CWU | |
| 51 | On/Off status | 1 Bit | 1.11 state | CRT | |
| 52 | Manual mode command | 1 Bit | 1.1 switch | CWU | |
| 53 | Manual mode status | 1 Bit | 1.11 state | CRT | |
| 54 | Holiday mode command | 1 Bit | 1.1 switch | CWU | |
| 55 | Holiday mode status | 1 Bit | 1.11 state | CRT | |
| 56 | Party mode command | 1 Bit | 1.1 switch | CWU | |
| 57 | Party mode status | 1 Bit | 1.11 state | CRT | |
| 58 | Auto mode command | 1 Bit | 1.1 switch | CWU | |
| 59 | Auto mode status | 1 Bit | 1.11 state | CRT | |
| 60 | Time | 3 Bytes | 10.1 time of day | CRWTU |
Parameters (20)
| Parameter | Type | Default |
|---|---|---|
| Speed 1 | unsignedInt 0…35 | 25 |
| Speed 2 | unsignedInt 35…70 | 45 |
| Speed 3 | unsignedInt 45…100 | 70 |
| Speed 4 | unsignedInt 100…110 | 100 |
| Boost Speed | unsignedInt 110…130 | 130 |
| Fan 2 unbalance | signedInt -20…20 | 0 |
| Humidity samples for setpoint | unsignedInt 1…96 | 96 |
| Summer T Setpoint | unsignedInt 10…30 | 26 |
| Winter T setpoint | unsignedInt 10…30 | 14 |
| Temp for free cooling | unsignedInt 10…30 | 18 |
| Temp for free heating | unsignedInt 10…30 | 24 |
| Boost time | unsignedInt 60…240 | 60 |
| Filter life | unsignedInt 30…360 | 180 |
| CO2 min | unsignedInt 400…600 | 500 |
| CO2 nom | unsignedInt 900…1100 | 1000 |
| CO2 max | unsignedInt 1500…2000 | 1800 |
| CO2 Sensor range | unsignedInt 2000…30000 | 2000 |
| RH Low value | unsignedInt 20…30 | 25 |
| RH Standard value | unsignedInt 40…50 | 45 |
| RH Hi value | unsignedInt 60…80 | 60 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| AKRVUKNX 0.1 latest | $4B52 | FCD1 | 2026-11-25 | 69 KB | Download |
About this file
This is the official ETS product database for the KERMI Kermi RVU KNX interface (3000246), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.