Kbox MDA ON-KBOX-MDA
Kbox · Order number ON-KBOX-MDA · Ac Gateways
Download .knxprod Kbox MDA Application Program 1.0 · 119 KB
Product
| Manufacturer | Kbox |
|---|---|
| Product name | Kbox MDA |
| Order number | ON-KBOX-MDA |
| Product text | KBOX-MDA |
| Hardware | Kbox MDA Hardware |
| Medium | Twisted Pair |
| Bus current (mA) | 1 |
| Rail mounted | No |
| Registration | Registered · 2026-03-11 |
| Languages | en-US |
| Catalog entry | M-023E_H-KBOXMDA-1_HP-0001-10-A536_CI-ON.2DKBOX.2DMDA-1 |
| Fingerprint | A536 |
| SHA-256 | 05f9f1ecb10a5161de963c5bafb0dcc681e2de6c833d9fe345caf9d7d70178e7 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: Kbox MDA Application Program 1.0
| Application number | $0001 |
|---|---|
| Version | 1.0 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 133 |
| Group objects | 103 |
Group objects (103)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | General | Alive Notification | 1 Bit | 1.11 state | CRT |
| 2 | Ac General | On/Off | 1 Bit | 1.1 switch | CWU |
| 3 | Ac General | On / Off Feedback | 1 Bit | 1.1 switch | CRT |
| 4 | AC General | Error Status | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 5 | AC General | Error Alarm | 1 Bit | 1.5 alarm | CRT |
| 6 | AC Mode | Mode - 0:Auto, 1:Heat, 3:Cool, 9:Fan, 14:Dry | 1 Byte | 20.105 HVAC control mode | CWU |
| 7 | AC Mode | Mode Feedback - 0:Auto, 1:Heat, 3:Cool, 9:Fan, 14:Dry | 1 Byte | 20.105 HVAC control mode | CRT |
| 8 | AC Mode | Mode +/- | 1 Bit | 1.7 step | CWU |
| 9 | AC Mode | Heat/Cool Mode Set - 0:Cool, 1:Heat | 1 Bit | 1.100 cooling/heating | CWU |
| 10 | AC Mode | Heat/Cool Mode Feedback 0:Cool, 1:Heat | 1 Bit | 1.100 cooling/heating | CRT |
| 11 | AC Mode | Cool Mode Set | 1 Bit | 1.11 state | CWU |
| 12 | AC Mode | Heat Mode Set | 1 Bit | 1.11 state | CWU |
| 13 | AC Mode | Dry Mode Set | 1 Bit | 1.11 state | CWU |
| 14 | AC Mode | Fan Mode Set | 1 Bit | 1.11 state | CWU |
| 15 | AC Mode | Auto Mode Set | 1 Bit | 1.11 state | CWU |
| 16 | AC Mode | Cool Mode Feedback | 1 Bit | 1.11 state | CRT |
| 17 | AC Mode | Heat Mode Feedback | 1 Bit | 1.11 state | CRT |
| 18 | AC Mode | Dry Mode Feedback | 1 Bit | 1.11 state | CRT |
| 19 | AC Mode | Fan Mode Feedback | 1 Bit | 1.11 state | CRT |
| 20 | AC Mode | Auto Mode Feedback | 1 Bit | 1.11 state | CRT |
| 21 | AC Fan | Fan Level | 1 Byte | 5.100 fan stage (0..255) | CWU |
| 21 | AC Fan | Fan Level | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 22 | AC Fan | Fan Level Feedback | 1 Byte | 5.100 fan stage (0..255) | CRT |
| 22 | AC Fan | Fan Level Feedback | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 23 | AC Fan | Fan Level +/- Set | 1 Bit | 1.7 step | CWU |
| 24 | AC Fan | Fan Auto Set | 1 Bit | 1.11 state | CWU |
| 25 | AC Fan | Fan Level 1 Set | 1 Bit | 1.11 state | CWU |
| 26 | AC Fan | Fan Level 2 Set | 1 Bit | 1.11 state | CWU |
| 27 | AC Fan | Fan Level 3 Set | 1 Bit | 1.11 state | CWU |
| 28 | AC Fan | Fan Level 4 Set | 1 Bit | 1.11 state | CWU |
| 29 | AC Fan | Fan Level 5 Set | 1 Bit | 1.11 state | CWU |
| 30 | AC Fan | Fan Level 6 Set | 1 Bit | 1.11 state | CWU |
| 31 | AC Fan | Fan Level 7 Set | 1 Bit | 1.11 state | CWU |
| 32 | AC Fan | Fan Level Auto Feedback | 1 Bit | 1.11 state | CRT |
| 33 | AC Fan | Fan Level 1 Feedback | 1 Bit | 1.11 state | CRT |
| 34 | AC Fan | Fan Level 2 Feedback | 1 Bit | 1.11 state | CRT |
| 35 | AC Fan | Fan Level 3 Feedback | 1 Bit | 1.11 state | CRT |
| 36 | AC Fan | Fan Level 4 Feedback | 1 Bit | 1.11 state | CRT |
| 37 | AC Fan | Fan Level 5 Feedback | 1 Bit | 1.11 state | CRT |
| 38 | AC Fan | Fan Level 6 Feedback | 1 Bit | 1.11 state | CRT |
| 39 | AC Fan | Fan Level 7 Feedback | 1 Bit | 1.11 state | CRT |
| 40 | AC Up-Down Wing | Up-Down Wing | 1 Byte | CWU | |
| 40 | AC Up-Down Wing | Up-Down Wing | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 41 | AC Up-Down Wing | Up-Down Wing Feedback | 1 Byte | CRT | |
| 41 | AC Up-Down Wing | Up-Down Wing Feedback | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 42 | AC Up-Down Wing | Up-Down Wing +/- Set | 1 Bit | 1.7 step | CWU |
| 43 | AC Up-Down Wing | Up-Down Swing On/Off Set | 1 Bit | 1.11 state | CWU |
| 44 | AC Up-Down Wing | HIDDEN-Up-Down Position Auto Set | 1 Bit | 1.11 state | CWU |
| 45 | AC Up-Down Wing | Up-Down Position Swing Set | 1 Bit | 1.11 state | CWU |
| 46 | AC Up-Down Wing | Up-Down Position 1 Set | 1 Bit | 1.11 state | CWU |
| 47 | AC Up-Down Wing | Up-Down Position 2 Set | 1 Bit | 1.11 state | CWU |
| 48 | AC Up-Down Wing | Up-Down Position 3 Set | 1 Bit | 1.11 state | CWU |
| 49 | AC Up-Down Wing | Up-Down Position 4 Set | 1 Bit | 1.11 state | CWU |
| 50 | AC Up-Down Wing | Up-Down Position 5 Set | 1 Bit | 1.11 state | CWU |
| 51 | AC Up-Down Wing | Up-Down Position 6 Set | 1 Bit | 1.11 state | CWU |
| 52 | AC Up-Down Wing | Up-Down Position 7 Set | 1 Bit | 1.11 state | CWU |
| 53 | AC Up-Down Wing | Up-Down Swing On/Off Feedback | 1 Bit | 1.11 state | CRT |
| 54 | AC Up-Down Wing | HIDDEN-Up-Down Position Auto Feedback | 1 Bit | 1.11 state | CRT |
| 55 | AC Up-Down Wing | Up-Down Position Swing Feedback | 1 Bit | 1.11 state | CRT |
| 56 | AC Up-Down Wing | Up-Down Position 1 Feedback | 1 Bit | 1.11 state | CRT |
| 57 | AC Up-Down Wing | Up-Down Position 2 Feedback | 1 Bit | 1.11 state | CRT |
| 58 | AC Up-Down Wing | Up-Down Position 3 Feedback | 1 Bit | 1.11 state | CRT |
| 59 | AC Up-Down Wing | Up-Down Position 4 Feedback | 1 Bit | 1.11 state | CRT |
| 60 | AC Up-Down Wing | Up-Down Position 5 Feedback | 1 Bit | 1.11 state | CRT |
| 61 | AC Up-Down Wing | Up-Down Position 6 Feedback | 1 Bit | 1.11 state | CRT |
| 62 | AC Up-Down Wing | Up-Down Position 7 Feedback | 1 Bit | 1.11 state | CRT |
| 63 | AC Left-Right Wing | Left-Right Wing | 1 Byte | CWU | |
| 63 | AC Left-Right Wing | Left-Right Wing | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 64 | AC Left-Right Wing | Left-Right Wing Feedback | 1 Byte | CRT | |
| 64 | AC Left-Right Wing | Left-Right Wing Feedback | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 65 | AC Left-Right Wing | Left-Right Wing +/- Set | 1 Bit | 1.7 step | CWU |
| 66 | AC Left-Right Wing | Left-Right Swing On/Off Set | 1 Bit | 1.11 state | CWU |
| 67 | AC Left-Right Wing | HIDDEN-Left-Right Position Auto Set | 1 Bit | 1.11 state | CWU |
| 68 | AC Left-Right Wing | Left-Right Position Swing Set | 1 Bit | 1.11 state | CWU |
| 69 | AC Left-Right Wing | Left-Right Position 1 Set | 1 Bit | 1.11 state | CWU |
| 70 | AC Left-Right Wing | Left-Right Position 2 Set | 1 Bit | 1.11 state | CWU |
| 71 | AC Left-Right Wing | Left-Right Position 3 Set | 1 Bit | 1.11 state | CWU |
| 72 | AC Left-Right Wing | Left-Right Position 4 Set | 1 Bit | 1.11 state | CWU |
| 73 | AC Left-Right Wing | Left-Right Position 5 Set | 1 Bit | 1.11 state | CWU |
| 74 | AC Left-Right Wing | Left-Right Position 6 Set | 1 Bit | 1.11 state | CWU |
| 75 | AC Left-Right Wing | Left-Right Position 7 Set | 1 Bit | 1.11 state | CWU |
| 76 | AC Left-Right Wing | Left-Right Swing On/Off Feedback | 1 Bit | 1.11 state | CRT |
| 77 | AC Left-Right Wing | HIDDEN-Left-Right Position Auto Feedback | 1 Bit | 1.11 state | CRT |
| 78 | AC Left-Right Wing | Left-Right Position Swing Feedback | 1 Bit | 1.11 state | CRT |
| 79 | AC Left-Right Wing | Left-Right Position 1 Feedback | 1 Bit | 1.11 state | CRT |
| 80 | AC Left-Right Wing | Left-Right Position 2 Feedback | 1 Bit | 1.11 state | CRT |
| 81 | AC Left-Right Wing | Left-Right Position 3 Feedback | 1 Bit | 1.11 state | CRT |
| 82 | AC Left-Right Wing | Left-Right Position 4 Feedback | 1 Bit | 1.11 state | CRT |
| 83 | AC Left-Right Wing | Left-Right Position 5 Feedback | 1 Bit | 1.11 state | CRT |
| 84 | AC Left-Right Wing | Left-Right Position 6 Feedback | 1 Bit | 1.11 state | CRT |
| 85 | AC Left-Right Wing | Left-Right Position 7 Feedback | 1 Bit | 1.11 state | CRT |
| 86 | AC Temperature | Setpoint Temperature | 2 Bytes | 9.1 temperature (°C) | CWU |
| 87 | AC Temperature | Setpoint Temperature Feedback | 2 Bytes | 9.1 temperature (°C) | CRT |
| 88 | AC Temperature | Setpoint Temperature +/- | 1 Bit | 1.7 step | CWU |
| 89 | AC Temperature | Ambient Temperature(Min:8 Celcius, Max:39 Celcius) | 2 Bytes | 9.1 temperature (°C) | CWU |
| 90 | AC Temperature | Ambient Temperature Feedback | 2 Bytes | 9.1 temperature (°C) | CRT |
| 91 | AC Extra | Remote Controller Lock | 1 Bit | 1.3 enable | CWU |
| 92 | AC Extra | Remote Controller Lock Feedback | 1 Bit | 1.3 enable | CRT |
| 93 | AC Extra | Object Control Lock | 1 Bit | 1.3 enable | CWU |
| 94 | AC Extra | Object Control Lock Feedback | 1 Bit | 1.3 enable | CRT |
| 95 | Digital Input | Digital Input 1 | 1 Bit | 1.1 switch | CWU |
| 96 | Digital Input | Digital Input 2 | 1 Bit | 1.1 switch | CWU |
| 97 | Digital Input | Digital Input 3 | 1 Bit | 1.1 switch | CWU |
Parameters (103)
| Parameter | Type | Default |
|---|---|---|
| ApplicationLoadControlWord | unsignedInt 0…65535 | 4386 |
| AcUnitCount_Byte | unsignedInt 0…255 | 1 |
| Alive Notification | list | Disabled |
| Period | unsignedInt 0…65535 | 15 |
| RESERVED_StartupDelay_Word | unsignedInt 0…65535 | 0 |
| RESERVED_AfterBusVoltageFailureBehaviour_Parameter | unsignedInt 0…255 | 0 |
| Indoor Unit ID | unsignedInt 0…255 | 0 |
| Outdoor Unit ID | unsignedInt 0…255 | 0 |
| ModeValueControl | list | Enabled |
| ModeCoolValue_ParameterTypeByte | unsignedInt 0…255 | 3 |
| ModeHeatValue_ParameterTypeByte | unsignedInt 0…255 | 1 |
| ModeDryValue_ParameterTypeByte | unsignedInt 0…255 | 14 |
| ModeFanValue_ParameterTypeByte | unsignedInt 0…255 | 9 |
| ModeAutoValue_ParameterTypeByte | unsignedInt 0…255 | 0 |
| Mode +/- Object | list | Disabled |
| ModePlusMinusBehaviour_PT_PlusMinusBehaviour | list | Plus:1 / Minus:0 |
| Heat/Cool Mode Object | list | Disabled |
| ModeHeatCoolBehaviour_PT_ModeHeatCoolBehaviour | list | Heat:1 / Cool:0 |
| Mode Individual Objects | list | Disabled |
| Cool Mode | list | Enabled |
| Heat Mode | list | Enabled |
| Dry Mode | list | Enabled |
| Fan Mode | list | Enabled |
| Auto Mode | list | Enabled |
| Fan Value Type | list | Scaling |
| Fan Auto | list | Enabled |
| Fan 1 | list | Enabled |
| Fan 2 | list | Enabled |
| Fan 3 | list | Enabled |
| Fan 4 | list | Enabled |
| Fan 5 | list | Enabled |
| Fan 6 | list | Enabled |
| Fan 7 | list | Enabled |
| FanValueControl_ParameterTypeBit | list | Disabled |
| Fan Level Auto Limit | unsignedInt 0…255 | 0 |
| Fan Level 1 Limit | unsignedInt 1…100 | 1 |
| Fan Level 2 Limit | unsignedInt 1…100 | 2 |
| Fan Level 3 Limit | unsignedInt 1…100 | 3 |
| Fan Level 4 Limit | unsignedInt 1…100 | 4 |
| Fan Level 5 Limit | unsignedInt 1…100 | 5 |
| Fan Level 6 Limit | unsignedInt 1…100 | 6 |
| Fan Level 7 Limit | unsignedInt 1…100 | 7 |
| Fan Level +/- Object | list | Disabled |
| FanPlusMinusBehaviour_ParameterTypePlusMinusBehaviour | list | Plus:1 / Minus:0 |
| Fan Level Individual Objects | list | Disabled |
| Fan Control | unsignedInt 0…1 | 1 |
| Up-Down Wing Control | unsignedInt 0…1 | 1 |
| Up-Down Wing +/- Object | list | Disabled |
| UDWingPlusMinusControl_ParameterTypeBit | list | Plus:1 / Minus:0 |
| Up-Down Wing Individual Objects | list | Disabled |
| Swing On/Off | list | Disabled |
| Auto | list | Disabled |
| Swing | list | Enabled |
| Position 1 | list | Enabled |
| Position 2 | list | Enabled |
| Position 3 | list | Enabled |
| Position 4 | list | Enabled |
| Position 5 | list | Enabled |
| Position 6 | list | Enabled |
| Position 7 | list | Enabled |
| UDWingValueControl_ParameterTypeBit | list | Enabled |
| Auto Limit | unsignedInt 0…255 | 1 |
| Swing Limit | unsignedInt 0…255 | 0 |
| Position 1 Limit | unsignedInt 1…99 | 2 |
| Position 2 Limit | unsignedInt 1…99 | 3 |
| Position 3 Limit | unsignedInt 1…99 | 4 |
| Position 4 Limit | unsignedInt 1…99 | 5 |
| Position 5 Limit | unsignedInt 1…99 | 6 |
| Position 6 Limit | unsignedInt 1…99 | 7 |
| Position 7 Limit | unsignedInt 1…99 | 8 |
| Type | list | Scaling |
| Left-Right Wing Control | unsignedInt 0…1 | 1 |
| Left-Right Wing +/- Object | list | Disabled |
| LRWingPlusMinusControl_ParameterTypeBit | list | Plus:1 / Minus:0 |
| Left-Right Wing Individual Objects | list | Disabled |
| LRWingValueControl_ParameterTypeBit | list | Disabled |
| Enable Set Temperature Feedback | list | Enabled |
| Set Temperature Feedback Behaviour | list | On change or on request |
| Set Temperature +/- Object | list | Disabled |
| SetTemperaturePlusMinusBehaviour_ParameterTypePlusMinusBehaviour | list | Plus:1 / Minus:0 |
| Set Temperature Limiting | list | Disabled |
| Cool Mode Maximum | unsignedInt 17…30 | 30 |
| Cool Mode Minimum | unsignedInt 17…30 | 17 |
| Heat Mode Maximum | unsignedInt 17…30 | 30 |
| Heat Mode Minimum | unsignedInt 17…30 | 17 |
| Default Maximum | unsignedInt 17…30 | 30 |
| Default Minimum | unsignedInt 17…30 | 17 |
| Set Point Temperature Step | list | 1 |
| Ambient Temperature Source | list | From bus |
| Enable Ambient Temperature Feedback | list | Enabled |
| Ambient Temperature Feedback Behaviour | list | On change or on request |
| Remote Controller Lock | list | Disabled |
| Object Control Lock | list | Disabled |
| Slave Function | list | Disabled |
| Error Status Feedback Period | unsignedInt 0…65535 | 15 |
| Digital Input Functions | unsignedInt 0…1 | 0 |
| Digital Input 1 | list | Disabled |
| Input Active | list | No Action |
| Input Passive | list | No Action |
| Trigger From | list | Bus Input |
| Binary Input Type | list | Normally Open |
| Digital Input 2 | list | Disabled |
| Digital Input 3 | list | Disabled |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Kbox MDA Application Program 1.0 latest | $0001 | A536 | 2026-11-25 | 119 KB | Download |
About this file
This is the official ETS product database for the Kbox Kbox MDA (ON-KBOX-MDA), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Kbox
- Kbox-AC [SMG, DKN, MITT-CN105, TB15] KBX-AC-001
- Kbox DKN-M-S21 ON-KBOX-DKN-M-S21
- Kbox LGE - Lg, Beko, Arcelik Ac Gateway ON-KBOX-LGE
- Kbox MHVY ON-KBOX-MHVY
- Kbox SMG ON-KBOX-SMG