GRDM-2CH-KNX-M UNIVERSAL DIMMER DIN MODULE 2 CHANNELS - 2X300W / 1X500W GRDM-2CH-KNX-M
Johnson Controls · Order number GRDM-2CH-KNX-M · Light Control › Dimmer
Download .knxprod Dimmer 2 Ch 1.1 · 133 KB
Product
| Manufacturer | Johnson Controls |
|---|---|
| Product name | GRDM-2CH-KNX-M UNIVERSAL DIMMER DIN MODULE 2 CHANNELS - 2X300W / 1X500W |
| Order number | GRDM-2CH-KNX-M |
| Product text | Dimmer 2 Ch 300W / 1 Ch 500W |
| Hardware | GRDM-2CH-KNX-M |
| Medium | Twisted Pair |
| Bus current (mA) | 5 |
| Rail mounted | Yes |
| Width (mm) | 72 |
| Registration | Certified · 2020-05-07 |
| Languages | en-US, de-DE, es-ES, fr-FR, it-IT |
| Catalog entry | M-019C_H-GRDM.2D2CH.2DKNX.2DM-1-O006C_HP-0702-11-D0B6-O006C_CI-GRDM.2D2CH.2DKNX.2DM-1 |
| Fingerprint | D0B6 |
| SHA-256 | 977e23fcaae97f562fa25737ad54a902dcc495c3f65428fa636a3e09c931c6fe |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Dimmer 2 Ch 1.1
| Application number | $0702 |
|---|---|
| Version | 1.1 |
| Mask version | MV-0021 (2.1) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 179 |
| Group objects | 31 |
Group objects (31)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | <Channel 1> Switching (at once) | Off/On | 1 Bit | 1.1 switch | CW |
| 1 | <Channel 1> Switching (smooth) | Off/On | 1 Bit | 1.1 switch | CW |
| 2 | <Channel 1> Switching (timing) | Off/On | 1 Bit | 1.1 switch | CW |
| 3 | <Channel 1> Dimming | Dimming Control | 4 Bit | 3.7 dimming control | CW |
| 4 | <Channel 1> Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 4 | <Channel 1> Status | Off/On | 1 Bit | 1.1 switch | CR |
| 5 | <Channel 1> Dimming Value | Value % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 6 | <Channel 1> Dimming Status | Feedback % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 7 | <Channel 1> Logic Function | Logic | 1 Bit | 1.1 switch | CW |
| 7 | <Channel 1> Lock Function | Lock | 1 Bit | 1.1 switch | CW |
| 8 | <Channel 1> Scene | Scene | 1 Byte | 18.1 scene control | CW |
| 9 | <Channel 1> Alarm Function 1 Byte | Alarm | 1 Byte | 21.601 lighting actuator error information | CRT |
| 9 | <Channel 1> Alarm Function 1 Bit | Alarm | 1 Bit | 1.5 alarm | CRT |
| 10 | <Channel 1> Economical Mode | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 11 | <Channel 1> Actual Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 12 | <Channel 2> Switching (at once) | Off/On | 1 Bit | 1.1 switch | CW |
| 13 | <Channel 2> Switching (smooth) | Off/On | 1 Bit | 1.1 switch | CW |
| 14 | <Channel 2> Switching (timing) | Off/On | 1 Bit | 1.1 switch | CW |
| 15 | <Channel 2> Dimming | Dimming Control | 4 Bit | 3.7 dimming control | CW |
| 16 | <Channel 2> Status | Off/On | 1 Bit | 1.1 switch | CRT |
| 16 | <Channel 2> Status | Off/On | 1 Bit | 1.1 switch | CR |
| 17 | <Channel 2> Dimming Value | Value % | 1 Byte | 5.1 percentage (0..100%) | CW |
| 18 | <Channel 2> Dimming Status | Feedback % | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 19 | <Channel 2> Logic Function | Logic | 1 Bit | 1.1 switch | CW |
| 19 | <Channel 2> Lock Function | Lock | 1 Bit | 1.1 switch | CW |
| 20 | <Channel 2> Scene | Scene | 1 Byte | 18.1 scene control | CW |
| 21 | <Channel 2> Alarm Function 1 Byte | Alarm | 1 Byte | 21.601 lighting actuator error information | CRT |
| 21 | <Channel 2> Alarm Function 1 Bit | Alarm | 1 Bit | 1.5 alarm | CRT |
| 22 | <Channel 2> Economical Mode | Disable/Enable | 1 Bit | 1.3 enable | CW |
| 23 | <Channel 2> Actual Temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 48 | <General> Dynamic Scene | Disable/Enable | 1 Bit | 1.3 enable | CW |
Parameters (91)
| Parameter | Type | Default |
|---|---|---|
| Delay to send telegrams on power up [s] | unsignedInt 5…15 | 5 |
| Channel 1 Enable temperature object | list | false |
| Channel 1 Sending interval | list | no sending |
| Channel 1 Send if variation >= 5°C | list | true |
| Channel 1 and Channel 2 | list | independent |
| Enable channel 2 | list | disabled |
| Channel 2 Enable temperature object | list | false |
| Channel 2 Sending interval | list | no sending |
| Channel 2 Send if variation >= 5°C | list | true |
| Enable dynamic scene object | list | false |
| Economy mode: switch OFF leds after 1 minute | list | false |
| Type of load | list | capacitive / resistive |
| Local button | list | disabled |
| Brightness from local button [%] | unsignedInt 1…100 | 75 |
| Internal Relay management [Recommended for small loads] | list | enabled |
| Maximum dimming value [50...100%] | unsignedInt 50…100 | 100 |
| Minimum dimming value [0...45%] | unsignedInt 0…45 | 0 |
| Ramp Time 0-100% [s] | unsignedInt 0…255 | 10 |
| Behaviour on KNX bus power down [0...100%] (101=no action) | unsignedInt 0…101 | 101 |
| Behaviour on KNX bus power up [0...100%] (101=previous state) | unsignedInt 0…101 | 101 |
| Brightness at switch on [1...100%] (101=previous state) | unsignedInt 1…101 | 100 |
| Enable switch off with dimming object (4 bit) | list | enabled |
| Absolute value object [0...100%] | list | disabled |
| Additional function | list | no function |
| Switching object activation telegram | list | telegram "1" |
| Timing function | list | timing function disabled |
| Dimming time from 0% to 100% [s] | unsignedInt 0…255 | 10 |
| Delay on activation | list | false |
| Delay on activation (Base time) | list | 1 second |
| Delay on activation (Factor) | unsignedInt 0…255 | 1 |
| Timing function | list | false |
| Timing (Base time) | list | 1 second |
| Timing (Factor) | unsignedInt 0…255 | 1 |
| Delay on deactivation | list | false |
| Delay on deactivation (Base time) | list | 1 second |
| Delay on deactivation (Factor) | unsignedInt 0…255 | 1 |
| Timing can be stopped | list | false |
| Warning function | list | false |
| Warning time (seconds before time ends) | list | 15 seconds |
| Switch off time | list | 1.0 s |
| Receiving on when timing is active | list | trigger mode |
| Maximum number of time extension | list | 4 times |
| Scene | list | disabled |
| Economical mode | list | disabled |
| Maximum dimming value in economical mode [20...90%] | unsignedInt 20…90 | 80 |
| Timing economical object [h] (0=time unlimited) | unsignedInt 0…255 | 0 |
| Status sending | list | always |
| Scene A [0...63] (64=not active) | unsignedInt 0…64 | 1 |
| Initial value scene A [0...100%] | unsignedInt 0…100 | 10 |
| Dimming time scene A from 0% to 100% [s] | unsignedInt 0…255 | 10 |
| Scene B [0...63] (64=not active) | unsignedInt 0…64 | 2 |
| Initial value scene B [0...100%] | unsignedInt 0…100 | 25 |
| Dimming time scene B from 0% to 100% [s] | unsignedInt 0…255 | 10 |
| Scene C [0...63] (64=not active) | unsignedInt 0…64 | 3 |
| Initial value scene C [0...100%] | unsignedInt 0…100 | 40 |
| Dimming time scene C from 0% to 100% [s] | unsignedInt 0…255 | 10 |
| Scene D [0...63] (64=not active) | unsignedInt 0…64 | 4 |
| Initial value scene D [0...100%] | unsignedInt 0…100 | 50 |
| Dimming time scene D from 0% to 100% [s] | unsignedInt 0…255 | 10 |
| Scene E [0...63] (64=not active) | unsignedInt 0…64 | 5 |
| Initial value scene E [0...100%] | unsignedInt 0…100 | 60 |
| Dimming time scene E from 0% to 100% [s] | unsignedInt 0…255 | 10 |
| Scene F [0...63] (64=not active) | unsignedInt 0…64 | 6 |
| Initial value scene F [0...100%] | unsignedInt 0…100 | 75 |
| Dimming time scene F from 0% to 100% [s] | unsignedInt 0…255 | 10 |
| Scene G [0...63] (64=not active) | unsignedInt 0…64 | 7 |
| Initial value scene G [0...100%] | unsignedInt 0…100 | 90 |
| Dimming time scene G from 0% to 100% [s] | unsignedInt 0…255 | 10 |
| Scene H [0...63] (64=not active) | unsignedInt 0…64 | 8 |
| Initial value scene H [0...100%] | unsignedInt 0…100 | 100 |
| Dimming time scene H from 0% to 100% [s] | unsignedInt 0…255 | 10 |
| Learn scene | list | enabled |
| Submit to dynamic scene function | list | false |
| Keep scenes value after download | list | disabled |
| Logic function | list | AND |
| Initial value for logic object | list | last value received |
| Initial value for lock object | list | last value received |
| Telegram for lock activation | list | telegram "1" |
| Brightness value % when lock is active (101=no action) | unsignedInt 0…101 | 0 |
| Position when lock ends | list | fixed value |
| Brightness value % when lock ends (101=no action) | unsignedInt 0…101 | 0 |
| Alarm object | list | 8 bit object |
| Alarm sending interval | list | no sending |
| Suggestion for | list | resistive load ( incandescent lamps ) |
| Driving mode | list | Trailing |
| Curve type | list | Linear |
| Minimum on time | list | 15 |
| Maximum on time | list | 8 |
| Warming up | list | Off |
| Trailing | picture | |
| Leading | picture |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Dimmer 2 Ch 1.1 latest | $0702 | D0B6 | 2026-11-25 | 133 KB | Download |
About this file
This is the official ETS product database for the Johnson Controls GRDM-2CH-KNX-M UNIVERSAL DIMMER DIN MODULE 2 CHANNELS - 2X300W / 1X500W (GRDM-2CH-KNX-M), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Johnson Controls
- GRDM-4CH-KNX-M UNIVERSAL DIMMER DIN MODULE 4 CHANNELS - 4X300W / 2X500W GRDM-4CH-KNX-M
- GRDM-CVL-KNX Dimmer LED 4 Channels Constant Voltage RGB - White GRDM-CVL-KNX
- GRAC-TH-Jxx-KNX Transponder Holder GRAC-TH-Jxx-KNX
- GRAC-TR-Jxx-KNX Transponder Reader GRAC-TR-Jxx-KNX
- GRACKPJ2x-KNX Numeric Keypad for Access Control GRACKPJ2x-KNX
- GRACKPJxx-KNX Numeric Keypad for Access Control GRACKPJxx-KNX
- GRACKPODJ2x-KNX Outdoor Numeric Keypad for Access Control GRACKPODJ2x-KNX
- GRACTHJ2x-KNX Transponder Holder GRACTHJ2x-KNX
- GRACTHSJxx-KNX Transponder Holder - 2 In / 2 Out GRACTHSJxx-KNX
- GRACTRJ2x-KNX Transponder Reader - 3 Buttons - BLE - KNX Secure GRACTRJ2x-KNX
- GRACTRODJ2x-KNX Outdoor Transponder Reader - 3 Buttons - BLE - KNX Secure GRACTRODJ2x-KNX
- GRACTRSJxx-KNX Transponder Reader - 2 In / 2 Out GRACTRSJxx-KNX