4-channel analog actuator TYF684
Hager Electro · Order number TYF684 · Sorties › 4-channel analog actuator
TYF684
Download .knxprod STYF684 0.1 · 110 KB
Product
| Manufacturer | Hager Electro |
|---|---|
| Product name | 4-channel analog actuator |
| Order number | TYF684 |
| Hardware | Analogaktor 4 fach |
| Medium | Twisted Pair |
| Rail mounted | Yes |
| Width (mm) | 70 |
| Registration | Certified |
| Languages | fr-FR, de-DE, en-US |
| Catalog entry | M-0009_H-9.20.2F.2F.20TYF684-1-O00F4_HP-209D-01-8A13-O00F4_CI-TYF684-1 |
| Fingerprint | 8A13 |
| SHA-256 | e9ccf4c5894cac400caa79088cc4372122de95f41621c7eb0045dddde2b3a797 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: STYF684 0.1
| Application number | $209D |
|---|---|
| Version | 0.1 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Parameters | 435 |
| Group objects | 74 |
Group objects (74)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Input value output 1 | Analog output | 1 Byte | CWU | |
| 0 | Input value output 1 | Analog output | 2 Bytes | CWU | |
| 1 | Input value output 2 | Analog output | 1 Byte | CWU | |
| 1 | Input value output 2 | Analog output | 2 Bytes | CWU | |
| 2 | Input value output 3 | Analog output | 2 Bytes | CWU | |
| 2 | Input value output 3 | Analog output | 1 Byte | CWU | |
| 3 | Input value output 4 | Analog output | 2 Bytes | CWU | |
| 3 | Input value output 4 | Analog output | 1 Byte | CWU | |
| 4 | Status output 1 | Analog output | 2 Bytes | CRTU | |
| 4 | Status output 1 | Analog output | 1 Byte | CRTU | |
| 5 | Status output 2 | Analog output | 2 Bytes | CRTU | |
| 5 | Status output 2 | Analog output | 1 Byte | CRTU | |
| 6 | Status output 3 | Analog output | 2 Bytes | CRTU | |
| 6 | Status output 3 | Analog output | 1 Byte | CRTU | |
| 7 | Status output 4 | Analog output | 2 Bytes | CRTU | |
| 7 | Status output 4 | Analog output | 1 Byte | CRTU | |
| 8 | Forced control 1 output 1 | Analog output | 1 Bit | CWU | |
| 9 | Forced control 2 output 1 | Analog output | 1 Bit | CWU | |
| 10 | Forced control 1 output 2 | Analog output | 1 Bit | CWU | |
| 11 | Forced control 2 output 2 | Analog output | 1 Bit | CWU | |
| 12 | Forced control 1 output 3 | Analog output | 1 Bit | CWU | |
| 13 | Forced control 2 output 3 | Analog output | 1 Bit | CWU | |
| 14 | Forced control 1 output 4 | Analog output | 1 Bit | CWU | |
| 15 | Forced control 2 output 4 | Analog output | 1 Bit | CWU | |
| 16 | Switching output 1 | Analog output | 1 Bit | CWU | |
| 17 | Switching output 2 | Analog output | 1 Bit | CWU | |
| 18 | Switching output 3 | Analog output | 1 Bit | CWU | |
| 19 | Switching output 4 | Analog output | 1 Bit | CWU | |
| 20 | Dimming output 1 | Analog output | 4 Bit | CWU | |
| 21 | Dimming output 2 | Analog output | 4 Bit | CWU | |
| 22 | Dimming output 3 | Analog output | 4 Bit | CWU | |
| 23 | Dimming output 4 | Analog output | 4 Bit | CWU | |
| 24 | Alarm output 1 | Analog output | 1 Bit | CTU | |
| 25 | Alarm output 2 | Analog output | 1 Bit | CTU | |
| 26 | Alarm output 3 | Analog output | 1 Bit | CTU | |
| 27 | Alarm output 4 | Analog output | 1 Bit | CTU | |
| 28 | Alarm | Analog output | 1 Bit | CU | |
| 29 | Input value output 5 | Extension module | 2 Bytes | CWU | |
| 29 | Input value output 5 | Extension module | 1 Byte | CWU | |
| 30 | Input value output 6 | Extension module | 2 Bytes | CWU | |
| 30 | Input value output 6 | Extension module | 1 Byte | CWU | |
| 31 | Input value output 7 | Extension module | 2 Bytes | CWU | |
| 31 | Input value output 7 | Extension module | 1 Byte | CWU | |
| 32 | Input value output 8 | Extension module | 2 Bytes | CWU | |
| 32 | Input value output 8 | Extension module | 1 Byte | CWU | |
| 33 | Status output 5 | Extension module | 2 Bytes | CRTU | |
| 33 | Status output 5 | Extension module | 1 Byte | CRTU | |
| 34 | Status output 6 | Extension module | 2 Bytes | CRTU | |
| 34 | Status output 6 | Extension module | 1 Byte | CRTU | |
| 35 | Status output 7 | Extension module | 2 Bytes | CRTU | |
| 35 | Status output 7 | Extension module | 1 Byte | CRTU | |
| 36 | Status output 8 | Extension module | 2 Bytes | CRTU | |
| 36 | Status output 8 | Extension module | 1 Byte | CRTU | |
| 37 | Forced control 1 output 5 | Extension module | 1 Bit | CWU | |
| 38 | Forced control 2 output 5 | Extension module | 1 Bit | CWU | |
| 39 | Forced control 1 output 6 | Extension module | 1 Bit | CWU | |
| 40 | Forced control 2 output 6 | Extension module | 1 Bit | CWU | |
| 41 | Forced control 1 output 7 | Extension module | 1 Bit | CWU | |
| 42 | Forced control 2 output 7 | Extension module | 1 Bit | CWU | |
| 43 | Forced control 1 output 8 | Extension module | 1 Bit | CWU | |
| 44 | Forced control 2 output 8 | Extension module | 1 Bit | CWU | |
| 45 | Switching output 5 | Extension module | 1 Bit | CWU | |
| 46 | Switching output 6 | Extension module | 1 Bit | CWU | |
| 47 | Switching output 7 | Extension module | 1 Bit | CWU | |
| 48 | Switching output 8 | Extension module | 1 Bit | CWU | |
| 49 | Dimming output 5 | Extension module | 4 Bit | CWU | |
| 50 | Dimming output 6 | Extension module | 4 Bit | CWU | |
| 51 | Dimming output 7 | Extension module | 4 Bit | CWU | |
| 52 | Dimming output 8 | Extension module | 4 Bit | CWU | |
| 53 | Alarm output 5 | Extension module | 1 Bit | CTU | |
| 54 | Alarm output 6 | Extension module | 1 Bit | CTU | |
| 55 | Alarm output 7 | Extension module | 1 Bit | CTU | |
| 56 | Alarm output 8 | Extension module | 1 Bit | CTU | |
| 57 | Alarm | Extension module | 1 Bit | CTU |
Parameters (31)
| Parameter | Type | Default |
|---|---|---|
| General parameters | list | no |
| Signal output 1 | list | no function |
| Signal output 2 | list | no function |
| Signal output 3 | list | no function |
| Signal output 4 | list | no function |
| Extension module existing | list | no |
| Signal output 5 | list | no function |
| Signal output 6 | list | no function |
| Signal output 7 | list | no function |
| Signal output 8 | list | no function |
| Input format | list | 16-bit |
| Input value for 0% output value (-32768...32767) | signedInt -32768…32767 | 0 |
| Input value for 0% output value | signedInt 0…255 | 0 |
| Input value for 100% output value (-32768...32767) | signedInt -32768…32767 | 1000 |
| Input value for 100% output value | signedInt 0…255 | 255 |
| Factor of input value | list | input value * 0.01 |
| Output value after initialization in % (0...100) | unsignedInt 0…100 | 0 |
| Response to bus voltage failure | list | last value |
| Output value in % (0...100) | unsignedInt 0…100 | 0 |
| Response on return of bus voltage | list | no response |
| Input object request on new start | list | no |
| Forced control object 1 | list | not existing |
| Output value in case of forced control 1 in % | unsignedInt 0…100 | 50 |
| Forced control object 2 | list | not existing |
| Output value in case of forced control 2 in % | unsignedInt 0…100 | 50 |
| Cyclical monitoring | list | no monitoring |
| Time factor for cyclical monitoring (1...255, base = 10s) | unsignedInt 1…255 | 6 |
| Output value after exceeding of the monitoring time in % | unsignedInt 0…100 | 0 |
| Time between 2 of 255 dimming steps base | list | 10 ms |
| Time between 2 of 255 dimming steps (factor 1...255) | unsignedInt 1…255 | 2 |
| Response on reception of value | list | direct approach |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| STYF684 0.1 latest | $209D | 8A13 | 2026-11-25 | 110 KB | Download |
About this file
This is the official ETS product database for the Hager Electro 4-channel analog actuator (TYF684), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Hager Electro
- 4 sorties 4A TX204A
- 4 sorties 10A TX204B
- 4 sorties 16A TX204C
- 6 sorties 4A TX206A
- 6 sorties 4A - Version a1 TX206A - a1
- 6 sorties 10A TX206B
- 6 sorties 10A - Version a1 TX206B - a1
- 6 sorties 16A TX206C
- 6 sorties 16A - Version a1 TX206C - a1
- 6 sorties 3x6A + 3x16A TX206D
- 6 sorties 3x6A + 3x16A - Version a1 TX206D - a1
- 4-output module 4A Lighting Heating TXA204A