6-fold switch actuator 16A 230V current monitoring TYA606E
Hager Electro · Order number TYA606E · Sorties › 6 sorties binaires
TYA606E
Download .knxprod STYA606E 0.1 · 422 KB
Product
| Manufacturer | Hager Electro |
|---|---|
| Product name | 6-fold switch actuator 16A 230V current monitoring |
| Order number | TYA606E |
| Product text | 6 sorties ON/OFF 16A 230V AC, mesure de courant |
| Hardware | TYA606E |
| Medium | Twisted Pair |
| Bus current (mA) | 7 |
| Rail mounted | Yes |
| Registration | Registered |
| Languages | fr-FR, da-DK, de-DE, en-US, it-IT, nl-NL, pt-PT, nb-NO, sv-SE |
| Catalog entry | M-0009_H-9.20.2F.2F.20TYA606E-1_HP-5000-01-420A_CI-TYA606E-1 |
| Fingerprint | 420A |
| SHA-256 | 940a3a494a0cf6e0b60811460249dc2a7d0c85f7ace632890c344022851c6495 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: STYA606E 0.1
| Application number | $5000 |
|---|---|
| Version | 0.1 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 3.0f |
| Parameters | 2033 |
| Group objects | 221 |
Group objects (221)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Sortie 1 | ON/OFF | 1 Bit | 1.1 switch | CRW |
| 1 | Sortie 1 | Alternance minuterie/télérupt. | 1 Bit | 1.1 switch | CRW |
| 2 | Sortie 1 | Télérupteur temporisé | 1 Bit | 1.1 switch | CRW |
| 3 | Sortie 1 | Indication d'état ON/OFF | 1 Bit | 1.1 switch | CRT |
| 4 | Sortie 1 | Minuterie | 1 Bit | 1.10 start/stop | CRW |
| 5 | Sortie 1 | Durée minuterie | 3 Bytes | 10.1 time of day | CRW |
| 6 | Sortie 1 | Scène | 1 Byte | CRW | |
| 7 | Sortie 1 | Preset 1 | 1 Bit | CRW | |
| 8 | Sortie 1 | Preset 2 | 1 Bit | CRW | |
| 9 | Sortie 1 | Autorisation preset 1 | 1 Bit | 1.3 enable | CRW |
| 10 | Sortie 1 | Autorisation preset 2 | 1 Bit | 1.3 enable | CRW |
| 11 | Sortie 1 | Blocage 1 | 1 Bit | 1.3 enable | CRW |
| 12 | Sortie 1 | Blocage 2 | 1 Bit | 1.3 enable | CRW |
| 13 | Sortie 1 | Indication d'état blocage | 1 Bit | CRT | |
| 14 | Sortie 1 | Forçage | 2 Bit | 2.2 boolean control | CRW |
| 15 | Sortie 1 | Indication d'état forçage | 1 Bit | CRT | |
| 16 | Sortie 1 | Valeur comptage heures | 2 Bytes | CRT | |
| 17 | Sortie 1 | Init. valeur comptage heures | 1 Bit | CRW | |
| 18 | Sortie 1 | Seuil comptage heures atteint | 1 Bit | CRT | |
| 19 | Sortie 1 | Seuil de comptage heures | 2 Bytes | CRW | |
| 20 | Sortie 1 | Seuil de courant 1 | 2 Bytes | CRW | |
| 21 | Sortie 1 | Seuil de courant 2 | 2 Bytes | CRW | |
| 22 | Sortie 1 | Courant > Seuil 1 | 1 Bit | CRT | |
| 23 | Sortie 1 | Seuil 2 < Courant < Seuil 1 | 1 Bit | CRT | |
| 24 | Sortie 1 | Courant < Seuil 2 | 1 Bit | CRT | |
| 25 | Sortie 1 | Absence courant | 1 Bit | CRT | |
| 26 | Sortie 1 | Valeur comptage commutations | 2 Bytes | 7.1 pulses | CRT |
| 27 | Sortie 1 | Init. valeur comptage commut. | 1 Bit | CRW | |
| 28 | Sortie 1 | Seuil comptage commut. atteint | 1 Bit | CRT | |
| 29 | Sortie 1 | Seuil de comptage commut. | 2 Bytes | 7.1 pulses | CRW |
| 30 | Sortie 1 | Valeur de courant | 2 Bytes | CRT | |
| 30 | Sortie 1 | Valeur de courant | 2 Bytes | 9.21 current (mA) | CRT |
| 30 | Sortie 1 | Valeur de courant | 4 Bytes | 14.19 electric current (A) | CRT |
| 31 | Sortie 1 | Courant dans contact ouvert | 1 Bit | CRT | |
| 32 | Sortie 2 | ON/OFF | 1 Bit | 1.1 switch | CRW |
| 33 | Sortie 2 | Alternance minuterie/télérupt. | 1 Bit | 1.1 switch | CRW |
| 34 | Sortie 2 | Télérupteur temporisé | 1 Bit | 1.1 switch | CRW |
| 35 | Sortie 2 | Indication d'état ON/OFF | 1 Bit | 1.1 switch | CRT |
| 36 | Sortie 2 | Minuterie | 1 Bit | 1.10 start/stop | CRW |
| 37 | Sortie 2 | Durée minuterie | 3 Bytes | 10.1 time of day | CRW |
| 38 | Sortie 2 | Scène | 1 Byte | CRW | |
| 39 | Sortie 2 | Preset 1 | 1 Bit | CRW | |
| 40 | Sortie 2 | Preset 2 | 1 Bit | CRW | |
| 41 | Sortie 2 | Autorisation preset 1 | 1 Bit | 1.3 enable | CRW |
| 42 | Sortie 2 | Autorisation preset 2 | 1 Bit | 1.3 enable | CRW |
| 43 | Sortie 2 | Blocage 1 | 1 Bit | 1.3 enable | CRW |
| 44 | Sortie 2 | Blocage 2 | 1 Bit | 1.3 enable | CRW |
| 45 | Sortie 2 | Indication d'état blocage | 1 Bit | CRT | |
| 46 | Sortie 2 | Forçage | 2 Bit | 2.2 boolean control | CRW |
| 47 | Sortie 2 | Indication d'état forçage | 1 Bit | CRT | |
| 48 | Sortie 2 | Valeur comptage heures | 2 Bytes | CRT | |
| 49 | Sortie 2 | Init. valeur comptage heures | 1 Bit | CRW | |
| 50 | Sortie 2 | Seuil comptage heures atteint | 1 Bit | CRT | |
| 51 | Sortie 2 | Seuil de comptage heures | 2 Bytes | CRW | |
| 52 | Sortie 2 | Seuil de courant 1 | 2 Bytes | CRW | |
| 53 | Sortie 2 | Seuil de courant 2 | 2 Bytes | CRW | |
| 54 | Sortie 2 | Courant > Seuil 1 | 1 Bit | CRT | |
| 55 | Sortie 2 | Seuil 2 < Courant < Seuil 1 | 1 Bit | CRT | |
| 56 | Sortie 2 | Courant < Seuil 2 | 1 Bit | CRT | |
| 57 | Sortie 2 | Absence courant | 1 Bit | CRT | |
| 58 | Sortie 2 | Valeur comptage commutations | 2 Bytes | 7.1 pulses | CRT |
| 59 | Sortie 2 | Init. valeur comptage commut. | 1 Bit | CRW | |
| 60 | Sortie 2 | Seuil comptage commut. atteint | 1 Bit | CRT | |
| 61 | Sortie 2 | Seuil de comptage commut. | 2 Bytes | 7.1 pulses | CRW |
| 62 | Sortie 2 | Valeur de courant | 2 Bytes | CRT | |
| 62 | Sortie 2 | Valeur de courant | 2 Bytes | 9.21 current (mA) | CRT |
| 62 | Sortie 2 | Valeur de courant | 4 Bytes | 14.19 electric current (A) | CRT |
| 63 | Sortie 2 | Courant dans contact ouvert | 1 Bit | CRT | |
| 64 | Sortie 3 | ON/OFF | 1 Bit | 1.1 switch | CRW |
| 65 | Sortie 3 | Alternance minuterie/télérupt. | 1 Bit | 1.1 switch | CRW |
| 66 | Sortie 3 | Télérupteur temporisé | 1 Bit | 1.1 switch | CRW |
| 67 | Sortie 3 | Indication d'état ON/OFF | 1 Bit | 1.1 switch | CRT |
| 68 | Sortie 3 | Minuterie | 1 Bit | 1.10 start/stop | CRW |
| 69 | Sortie 3 | Durée minuterie | 3 Bytes | 10.1 time of day | CRW |
| 70 | Sortie 3 | Scène | 1 Byte | CRW | |
| 71 | Sortie 3 | Preset 1 | 1 Bit | CRW | |
| 72 | Sortie 3 | Preset 2 | 1 Bit | CRW | |
| 73 | Sortie 3 | Autorisation preset 1 | 1 Bit | 1.3 enable | CRW |
| 74 | Sortie 3 | Autorisation preset 2 | 1 Bit | 1.3 enable | CRW |
| 75 | Sortie 3 | Blocage 1 | 1 Bit | 1.3 enable | CRW |
| 76 | Sortie 3 | Blocage 2 | 1 Bit | 1.3 enable | CRW |
| 77 | Sortie 3 | Indication d'état blocage | 1 Bit | CRT | |
| 78 | Sortie 3 | Forçage | 2 Bit | 2.2 boolean control | CRW |
| 79 | Sortie 3 | Indication d'état forçage | 1 Bit | CRT | |
| 80 | Sortie 3 | Valeur comptage heures | 2 Bytes | CRT | |
| 81 | Sortie 3 | Init. valeur comptage heures | 1 Bit | CRW | |
| 82 | Sortie 3 | Seuil comptage heures atteint | 1 Bit | CRT | |
| 83 | Sortie 3 | Seuil de comptage heures | 2 Bytes | CRW | |
| 84 | Sortie 3 | Seuil de courant 1 | 2 Bytes | CRW | |
| 85 | Sortie 3 | Seuil de courant 2 | 2 Bytes | CRW | |
| 86 | Sortie 3 | Courant > Seuil 1 | 1 Bit | CRT | |
| 87 | Sortie 3 | Seuil 2 < Courant < Seuil 1 | 1 Bit | CRT | |
| 88 | Sortie 3 | Courant < Seuil 2 | 1 Bit | CRT | |
| 89 | Sortie 3 | Absence courant | 1 Bit | CRT | |
| 90 | Sortie 3 | Valeur comptage commutations | 2 Bytes | 7.1 pulses | CRT |
| 91 | Sortie 3 | Init. valeur comptage commut. | 1 Bit | CRW | |
| 92 | Sortie 3 | Seuil comptage commut. atteint | 1 Bit | CRT | |
| 93 | Sortie 3 | Seuil de comptage commut. | 2 Bytes | 7.1 pulses | CRW |
| 94 | Sortie 3 | Valeur de courant | 2 Bytes | CRT | |
| 94 | Sortie 3 | Valeur de courant | 2 Bytes | 9.21 current (mA) | CRT |
| 94 | Sortie 3 | Valeur de courant | 4 Bytes | 14.19 electric current (A) | CRT |
| 95 | Sortie 3 | Courant dans contact ouvert | 1 Bit | CRT | |
| 96 | Sortie 4 | ON/OFF | 1 Bit | 1.1 switch | CRW |
| 97 | Sortie 4 | Alternance minuterie/télérupt. | 1 Bit | 1.1 switch | CRW |
| 98 | Sortie 4 | Télérupteur temporisé | 1 Bit | 1.1 switch | CRW |
| 99 | Sortie 4 | Indication d'état ON/OFF | 1 Bit | 1.1 switch | CRT |
| 100 | Sortie 4 | Minuterie | 1 Bit | 1.10 start/stop | CRW |
| 101 | Sortie 4 | Durée minuterie | 3 Bytes | 10.1 time of day | CRW |
| 102 | Sortie 4 | Scène | 1 Byte | CRW | |
| 103 | Sortie 4 | Preset 1 | 1 Bit | CRW | |
| 104 | Sortie 4 | Preset 2 | 1 Bit | CRW | |
| 105 | Sortie 4 | Autorisation preset 1 | 1 Bit | 1.3 enable | CRW |
| 106 | Sortie 4 | Autorisation preset 2 | 1 Bit | 1.3 enable | CRW |
| 107 | Sortie 4 | Blocage 1 | 1 Bit | 1.3 enable | CRW |
| 108 | Sortie 4 | Blocage 2 | 1 Bit | 1.3 enable | CRW |
| 109 | Sortie 4 | Indication d'état blocage | 1 Bit | CRT | |
| 110 | Sortie 4 | Forçage | 2 Bit | 2.2 boolean control | CRW |
| 111 | Sortie 4 | Indication d'état forçage | 1 Bit | CRT | |
| 112 | Sortie 4 | Valeur comptage heures | 2 Bytes | CRT | |
| 113 | Sortie 4 | Init. valeur comptage heures | 1 Bit | CRW | |
| 114 | Sortie 4 | Seuil comptage heures atteint | 1 Bit | CRT | |
| 115 | Sortie 4 | Seuil de comptage heures | 2 Bytes | CRW | |
| 116 | Sortie 4 | Seuil de courant 1 | 2 Bytes | CRW | |
| 117 | Sortie 4 | Seuil de courant 2 | 2 Bytes | CRW | |
| 118 | Sortie 4 | Courant > Seuil 1 | 1 Bit | CRT | |
| 119 | Sortie 4 | Seuil 2 < Courant < Seuil 1 | 1 Bit | CRT | |
| 120 | Sortie 4 | Courant < Seuil 2 | 1 Bit | CRT | |
| 121 | Sortie 4 | Absence courant | 1 Bit | CRT | |
| 122 | Sortie 4 | Valeur comptage commutations | 2 Bytes | 7.1 pulses | CRT |
| 123 | Sortie 4 | Init. valeur comptage commut. | 1 Bit | CRW | |
| 124 | Sortie 4 | Seuil comptage commut. atteint | 1 Bit | CRT | |
| 125 | Sortie 4 | Seuil de comptage commut. | 2 Bytes | 7.1 pulses | CRW |
| 126 | Sortie 4 | Valeur de courant | 2 Bytes | CRT | |
| 126 | Sortie 4 | Valeur de courant | 2 Bytes | 9.21 current (mA) | CRT |
| 126 | Sortie 4 | Valeur de courant | 4 Bytes | 14.19 electric current (A) | CRT |
| 127 | Sortie 4 | Courant dans contact ouvert | 1 Bit | CRT | |
| 128 | Sortie 5 | ON/OFF | 1 Bit | 1.1 switch | CRW |
| 129 | Sortie 5 | Alternance minuterie/télérupt. | 1 Bit | 1.1 switch | CRW |
| 130 | Sortie 5 | Télérupteur temporisé | 1 Bit | 1.1 switch | CRW |
| 131 | Sortie 5 | Indication d'état ON/OFF | 1 Bit | 1.1 switch | CRT |
| 132 | Sortie 5 | Minuterie | 1 Bit | 1.10 start/stop | CRW |
| 133 | Sortie 5 | Durée minuterie | 3 Bytes | 10.1 time of day | CRW |
| 134 | Sortie 5 | Scène | 1 Byte | CRW | |
| 135 | Sortie 5 | Preset 1 | 1 Bit | CRW | |
| 136 | Sortie 5 | Preset 2 | 1 Bit | CRW | |
| 137 | Sortie 5 | Autorisation preset 1 | 1 Bit | 1.3 enable | CRW |
| 138 | Sortie 5 | Autorisation preset 2 | 1 Bit | 1.3 enable | CRW |
| 139 | Sortie 5 | Blocage 1 | 1 Bit | 1.3 enable | CRW |
| 140 | Sortie 5 | Blocage 2 | 1 Bit | 1.3 enable | CRW |
| 141 | Sortie 5 | Indication d'état blocage | 1 Bit | CRT | |
| 142 | Sortie 5 | Forçage | 2 Bit | 2.2 boolean control | CRW |
| 143 | Sortie 5 | Indication d'état forçage | 1 Bit | CRT | |
| 144 | Sortie 5 | Valeur comptage heures | 2 Bytes | CRT | |
| 145 | Sortie 5 | Init. valeur comptage heures | 1 Bit | CRW | |
| 146 | Sortie 5 | Seuil comptage heures atteint | 1 Bit | CRT | |
| 147 | Sortie 5 | Seuil de comptage heures | 2 Bytes | CRW | |
| 148 | Sortie 5 | Seuil de courant 1 | 2 Bytes | CRW | |
| 149 | Sortie 5 | Seuil de courant 2 | 2 Bytes | CRW | |
| 150 | Sortie 5 | Courant > Seuil 1 | 1 Bit | CRT | |
| 151 | Sortie 5 | Seuil 2 < Courant < Seuil 1 | 1 Bit | CRT | |
| 152 | Sortie 5 | Courant < Seuil 2 | 1 Bit | CRT | |
| 153 | Sortie 5 | Absence courant | 1 Bit | CRT | |
| 154 | Sortie 5 | Valeur comptage commutations | 2 Bytes | 7.1 pulses | CRT |
| 155 | Sortie 5 | Init. valeur comptage commut. | 1 Bit | CRW | |
| 156 | Sortie 5 | Seuil comptage commut. atteint | 1 Bit | CRT | |
| 157 | Sortie 5 | Seuil de comptage commut. | 2 Bytes | 7.1 pulses | CRW |
| 158 | Sortie 5 | Valeur de courant | 2 Bytes | CRT | |
| 158 | Sortie 5 | Valeur de courant | 2 Bytes | 9.21 current (mA) | CRT |
| 158 | Sortie 5 | Valeur de courant | 4 Bytes | 14.19 electric current (A) | CRT |
| 159 | Sortie 5 | Courant dans contact ouvert | 1 Bit | CRT | |
| 160 | Sortie 6 | ON/OFF | 1 Bit | 1.1 switch | CRW |
| 161 | Sortie 6 | Alternance minuterie/télérupt. | 1 Bit | 1.1 switch | CRW |
| 162 | Sortie 6 | Télérupteur temporisé | 1 Bit | 1.1 switch | CRW |
| 163 | Sortie 6 | Indication d'état ON/OFF | 1 Bit | 1.1 switch | CRT |
| 164 | Sortie 6 | Minuterie | 1 Bit | 1.10 start/stop | CRW |
| 165 | Sortie 6 | Durée minuterie | 3 Bytes | 10.1 time of day | CRW |
| 166 | Sortie 6 | Scène | 1 Byte | CRW | |
| 167 | Sortie 6 | Preset 1 | 1 Bit | CRW | |
| 168 | Sortie 6 | Preset 2 | 1 Bit | CRW | |
| 169 | Sortie 6 | Autorisation preset 1 | 1 Bit | 1.3 enable | CRW |
| 170 | Sortie 6 | Autorisation preset 2 | 1 Bit | 1.3 enable | CRW |
| 171 | Sortie 6 | Blocage 1 | 1 Bit | 1.3 enable | CRW |
| 172 | Sortie 6 | Blocage 2 | 1 Bit | 1.3 enable | CRW |
| 173 | Sortie 6 | Indication d'état blocage | 1 Bit | CRT | |
| 174 | Sortie 6 | Forçage | 2 Bit | 2.2 boolean control | CRW |
| 175 | Sortie 6 | Indication d'état forçage | 1 Bit | CRT | |
| 176 | Sortie 6 | Valeur comptage heures | 2 Bytes | CRT | |
| 177 | Sortie 6 | Init. valeur comptage heures | 1 Bit | CRW | |
| 178 | Sortie 6 | Seuil comptage heures atteint | 1 Bit | CRT | |
| 179 | Sortie 6 | Seuil de comptage heures | 2 Bytes | CRW | |
| 180 | Sortie 6 | Seuil de courant 1 | 2 Bytes | CRW | |
| 181 | Sortie 6 | Seuil de courant 2 | 2 Bytes | CRW | |
| 182 | Sortie 6 | Courant > Seuil 1 | 1 Bit | CRT | |
| 183 | Sortie 6 | Seuil 2 < Courant < Seuil 1 | 1 Bit | CRT | |
| 184 | Sortie 6 | Courant < Seuil 2 | 1 Bit | CRT | |
| 185 | Sortie 6 | Absence courant | 1 Bit | CRT | |
| 186 | Sortie 6 | Valeur comptage commutations | 2 Bytes | 7.1 pulses | CRT |
| 187 | Sortie 6 | Init. valeur comptage commut. | 1 Bit | CRW | |
| 188 | Sortie 6 | Seuil comptage commut. atteint | 1 Bit | CRT | |
| 189 | Sortie 6 | Seuil de comptage commut. | 2 Bytes | 7.1 pulses | CRW |
| 190 | Sortie 6 | Valeur de courant | 2 Bytes | CRT | |
| 190 | Sortie 6 | Valeur de courant | 2 Bytes | 9.21 current (mA) | CRT |
| 190 | Sortie 6 | Valeur de courant | 4 Bytes | 14.19 electric current (A) | CRT |
| 191 | Sortie 6 | Courant dans contact ouvert | 1 Bit | CRT | |
| 192 | Sorties 1-6 | Désactivation mode manuel | 1 Bit | 1.3 enable | CRW |
| 193 | Sorties 1-6 | Indication d'état mode manuel | 1 Bit | CRT | |
| 194 | Bloc logique 1 | Autorisation | 1 Bit | 1.3 enable | CRW |
| 195 | Bloc logique 1 | Entrée 1 | 1 Bit | 1.2 boolean | CRW |
| 196 | Bloc logique 1 | Entrée 2 | 1 Bit | 1.2 boolean | CRW |
| 197 | Bloc logique 1 | Entrée 3 | 1 Bit | 1.2 boolean | CRW |
| 198 | Bloc logique 1 | Entrée 4 | 1 Bit | 1.2 boolean | CRW |
| 199 | Bloc logique 1 | Résultat logique | 1 Bit | 1.2 boolean | CRT |
| 200 | Bloc logique 2 | Autorisation | 1 Bit | 1.3 enable | CRW |
| 201 | Bloc logique 2 | Entrée 1 | 1 Bit | 1.2 boolean | CRW |
| 202 | Bloc logique 2 | Entrée 2 | 1 Bit | 1.2 boolean | CRW |
| 203 | Bloc logique 2 | Entrée 3 | 1 Bit | 1.2 boolean | CRW |
| 204 | Bloc logique 2 | Entrée 4 | 1 Bit | 1.2 boolean | CRW |
| 205 | Bloc logique 2 | Résultat logique | 1 Bit | 1.2 boolean | CRT |
| 206 | Sorties 1-6 | Restauration valeur param. ETS | 1 Bit | CRW | |
| 207 | Sorties 1-6 | Extinction LED produit | 1 Bit | 1.1 switch | CRW |
| 208 | Sorties 1-6 | Diagnostic produit | 6 Bytes | CRT |
Parameters (278)
| Parameter | Type | Default |
|---|---|---|
| Sélection de fonctions | list | Actif |
| Mode manuel | list | Actif |
| Indication d'état | list | Actif |
| Bloc logique 1 | list | Inactif |
| Bloc logique 2 | list | Inactif |
| Objet diagnostic produit | list | Inactif |
| Objet restaur. valeurs de paramètre ETS (scènes, minuterie, seuils) | list | Inactif |
| Ecrasement paramètres au téléchargement (scènes, minuterie, seuils) | list | Actif |
| Etat durant la coupure bus | list | Maintenir l'état courant |
| Etat sur retour bus | list | Maintenir l'état courant |
| Etat durant le téléchargement | list | Maintenir l'état courant |
| Etat après le téléchargement | list | Maintenir l'état courant |
| Objet extinction LED produit | list | Inactif |
| Polarité | list | 0 = Indication d'état, 1 = Toujours OFF |
| Dummy_4bit_Def | list | 0 |
| Dummy_16bit_Manual | list | 0 |
| Objet désactivation mode manuel | list | Inactif |
| Polarité | list | 0 = Mode manuel autorisé, 1 = Mode manuel bloqué |
| Objet indication d'état mode manuel | list | Inactif |
| Polarité | list | 0 = Mode manuel inactif, 1 = Mode manuel actif |
| Emission | list | Sur changement d'état |
| Heures (h) | unsignedInt 0…23 | 0 |
| Minutes (min) | unsignedInt 0…59 | 30 |
| Secondes (s) | unsignedInt 0…59 | 0 |
| Etat après mode manuel | list | Maintenir l'état courant |
| Durée d'activation du mode manuel (h) | unsignedInt 0…23 | 0 |
| Durée d'activation du mode manuel (min) | unsignedInt 0…59 | 30 |
| Durée d'activation du mode manuel (s) | unsignedInt 0…59 | 0 |
| Dummy_4bit_Manual | list | 0 |
| Polarité | list | 0 = OFF, 1 = ON |
| Emission durant mode manuel | list | Actif |
| Minutes (min) | unsignedInt 0…59 | 10 |
| Retard à l'émission après retour bus (h) | unsignedInt 0…23 | 0 |
| Retard à l'émission après retour bus (min) | unsignedInt 0…59 | 0 |
| Retard à l'émission après retour bus (s) | unsignedInt 0…59 | 20 |
| Dummy_1bit_StatusInd | list | 0 |
| Type de fonction logique | list | OU |
| Nombre d'entrées logiques | unsignedInt 1…4 | 1 |
| Inverser valeur entrée logique 1 | list | Maintenir l'état courant |
| Inverser valeur entrée logique 2 | list | Maintenir l'état courant |
| Inverser valeur entrée logique 3 | list | Maintenir l'état courant |
| Inverser valeur entrée logique 4 | list | Maintenir l'état courant |
| Valeur à l'initialisation entrée logique 1 | list | Valeur avant initialisation |
| Valeur à l'initialisation entrée logique 2 | list | Valeur avant initialisation |
| Valeur à l'initialisation entrée logique 3 | list | Valeur avant initialisation |
| Valeur à l'initialisation entrée logique 4 | list | Valeur avant initialisation |
| Objet autorisation bloc logique | list | Inactif |
| Valeur à l'initialisation | list | Valeur avant initialisation |
| Polarité | list | 0 = Bloqué, 1 = Autorisé |
| Résultat logique après autorisation | list | Emission immédiate si autorisation |
| Emission résultat logique | list | Sur changement du résultat logique |
| Résultat logique agit sur sorties | list | Inactif |
| Sortie 1 | list | Oui |
| Sortie 2 | list | Oui |
| Sortie 3 | list | Oui |
| Sortie 4 | list | Oui |
| Sortie 5 | list | Oui |
| Sortie 6 | list | Oui |
| Action si résultat logique = 0 | list | OFF |
| Scène si résultat logique = 0 | unsignedInt 1…64 | 1 |
| Action si résultat logique = 1 | list | ON |
| Scène si résultat logique = 1 | unsignedInt 1…64 | 2 |
| Dummy_4bit_Logic | list | 0 |
| Dummy_1bit_Logic | list | 0 |
| Dummy_3bit_Diagnosis | list | 0 |
| Contact de sortie | list | Normalement ouvert |
| Mode manuel actif pour sortie 1 | list | Oui |
| Indication d'état ON/OFF | list | Oui |
| Temporisations objet ON/OFF | list | Inactif |
| Minuterie | list | Inactif |
| Scène | list | Inactif |
| Preset | list | Inactif |
| Blocage | list | Inactif |
| Forçage | list | Inactif |
| Comptage heures | list | Inactif |
| Détection de courant | list | Inactif |
| Dummy_6bit_TOR_Def | list | 0 |
| Retard pour objet ON/OFF | list | Inactif |
| Retard à l'enclenchement (h) | unsignedInt 0…23 | 0 |
| Retard à l'enclenchement (min) | unsignedInt 0…59 | 3 |
| Retard à l'enclenchement (s), valeur minimale 1s | unsignedInt 0…59 | 0 |
| Retard au déclenchement (h) | unsignedInt 0…23 | 0 |
| Retard au déclenchement (min) | unsignedInt 0…59 | 3 |
| Retard au déclenchement (s), valeur minimale 1s | unsignedInt 0…59 | 0 |
| Alternance minuterie/télérupteur pour objet ON/OFF | list | Inactif |
| Heures (h) | unsignedInt 0…23 | 1 |
| Minutes (min) | unsignedInt 0…59 | 0 |
| Secondes (s), valeur minimale 1s | unsignedInt 0…59 | 0 |
| Fonction additionnelle télérupteur temporisé | list | Inactif |
| Dummy_5bit_Basics | list | 0 |
| Dummy_4bit_Basics | list | 0 |
| Fonctionnement minuterie | list | ON |
| Durée minuterie (h) | unsignedInt 0…23 | 0 |
| Durée minuterie (min) | unsignedInt 0…59 | 3 |
| Durée minuterie (s), valeur minimale 1s | unsignedInt 0…59 | 0 |
| Durée du clignotement ON (s) | unsignedInt 5…240 | 5 |
| Durée du clignotement OFF (s) | unsignedInt 5…240 | 5 |
| Indication d'état ON/OFF durant clignotement | list | ON |
| Préavis d'extinction | list | Actif |
| Secondes (s) | unsignedInt 0…59 | 30 |
| Interruption de minuterie | list | Oui |
| Relance minuterie | list | Oui |
| Limitation du nombre de relances de la minuterie (10ères secondes) | list | Illimité |
| Durée minuterie modifiable par objet | list | Inactif |
| Dummy_3bit_Timer | list | 0 |
| Dummy_4bit_Timer | list | 0 |
| Nombre de scènes utilisées | list | 8 |
| Apprentissage scènes par appui long | list | Actif |
| Acquittement apprentissage de scènes (Etat de la sortie inversé pendant 3s) | list | Inactif |
| Etat de la sortie pour la scène 1 | list | Inactif |
| Etat de la sortie pour la scène 2 | list | Inactif |
| Etat de la sortie pour la scène 3 | list | Inactif |
| Etat de la sortie pour la scène 4 | list | Inactif |
| Etat de la sortie pour la scène 5 | list | Inactif |
| Etat de la sortie pour la scène 6 | list | Inactif |
| Etat de la sortie pour la scène 7 | list | Inactif |
| Etat de la sortie pour la scène 8 | list | Inactif |
| Etat de la sortie pour la scène 9 | list | Inactif |
| Etat de la sortie pour la scène 10 | list | Inactif |
| Etat de la sortie pour la scène 11 | list | Inactif |
| Etat de la sortie pour la scène 12 | list | Inactif |
| Etat de la sortie pour la scène 13 | list | Inactif |
| Etat de la sortie pour la scène 14 | list | Inactif |
| Etat de la sortie pour la scène 15 | list | Inactif |
| Etat de la sortie pour la scène 16 | list | Inactif |
| Etat de la sortie pour la scène 17 | list | Inactif |
| Etat de la sortie pour la scène 18 | list | Inactif |
| Etat de la sortie pour la scène 19 | list | Inactif |
| Etat de la sortie pour la scène 20 | list | Inactif |
| Etat de la sortie pour la scène 21 | list | Inactif |
| Etat de la sortie pour la scène 22 | list | Inactif |
| Etat de la sortie pour la scène 23 | list | Inactif |
| Etat de la sortie pour la scène 24 | list | Inactif |
| Etat de la sortie pour la scène 25 | list | Inactif |
| Etat de la sortie pour la scène 26 | list | Inactif |
| Etat de la sortie pour la scène 27 | list | Inactif |
| Etat de la sortie pour la scène 28 | list | Inactif |
| Etat de la sortie pour la scène 29 | list | Inactif |
| Etat de la sortie pour la scène 30 | list | Inactif |
| Etat de la sortie pour la scène 31 | list | Inactif |
| Etat de la sortie pour la scène 32 | list | Inactif |
| Etat de la sortie pour la scène 33 | list | Inactif |
| Etat de la sortie pour la scène 34 | list | Inactif |
| Etat de la sortie pour la scène 35 | list | Inactif |
| Etat de la sortie pour la scène 36 | list | Inactif |
| Etat de la sortie pour la scène 37 | list | Inactif |
| Etat de la sortie pour la scène 38 | list | Inactif |
| Etat de la sortie pour la scène 39 | list | Inactif |
| Etat de la sortie pour la scène 40 | list | Inactif |
| Etat de la sortie pour la scène 41 | list | Inactif |
| Etat de la sortie pour la scène 42 | list | Inactif |
| Etat de la sortie pour la scène 43 | list | Inactif |
| Etat de la sortie pour la scène 44 | list | Inactif |
| Etat de la sortie pour la scène 45 | list | Inactif |
| Etat de la sortie pour la scène 46 | list | Inactif |
| Etat de la sortie pour la scène 47 | list | Inactif |
| Etat de la sortie pour la scène 48 | list | Inactif |
| Etat de la sortie pour la scène 49 | list | Inactif |
| Etat de la sortie pour la scène 50 | list | Inactif |
| Etat de la sortie pour la scène 51 | list | Inactif |
| Etat de la sortie pour la scène 52 | list | Inactif |
| Etat de la sortie pour la scène 53 | list | Inactif |
| Etat de la sortie pour la scène 54 | list | Inactif |
| Etat de la sortie pour la scène 55 | list | Inactif |
| Etat de la sortie pour la scène 56 | list | Inactif |
| Etat de la sortie pour la scène 57 | list | Inactif |
| Etat de la sortie pour la scène 58 | list | Inactif |
| Etat de la sortie pour la scène 59 | list | Inactif |
| Etat de la sortie pour la scène 60 | list | Inactif |
| Etat de la sortie pour la scène 61 | list | Inactif |
| Etat de la sortie pour la scène 62 | list | Inactif |
| Etat de la sortie pour la scène 63 | list | Inactif |
| Etat de la sortie pour la scène 64 | list | Inactif |
| Dummy_1bit_SceneTOR | list | 0 |
| Dummy_4bit_SceneTOR | list | 0 |
| Objets autorisation preset | list | Inactif |
| Valeur à l'initialisation de l'objet autorisation preset 1 | list | Valeur avant initialisation |
| Polarité de l'objet autorisation preset 1 | list | 0 = Bloqué, 1 = Autorisé |
| Dummy_1bit_Preset | list | 0 |
| Etat si objet preset 1 = 0 | list | Maintenir l'état courant |
| Scène si preset 1 = 0 | unsignedInt 1…64 | 1 |
| Etat si objet preset 1 = 1 | list | Maintenir l'état courant |
| Scène si preset 1 = 1 | unsignedInt 1…64 | 2 |
| Valeur à l'initialisation de l'objet autorisation preset 2 | list | Valeur avant initialisation |
| Polarité de l'objet autorisation preset 2 | list | 0 = Bloqué, 1 = Autorisé |
| Etat si objet preset 2 = 0 | list | Maintenir l'état courant |
| Scène si preset 2 = 0 | unsignedInt 1…64 | 1 |
| Etat si objet preset 2 = 1 | list | Maintenir l'état courant |
| Scène si preset 2 = 1 | unsignedInt 1…64 | 2 |
| Dummy_4bit_Preset | list | 0 |
| Type de blocage | list | Blocage sortie |
| Durée du blocage | list | Permanent |
| Minutes (min) | unsignedInt 0…59 | 15 |
| Polarité de l'objet blocage 1 | list | 0 = Blocage inactif, 1 = Blocage actif |
| Dummy_4bit_Lockup | list | 0 |
| Etat si blocage 1 | list | Maintenir l'état courant |
| Etat après blocage 1 | list | Maintenir l'état courant |
| ON/OFF | list | Non |
| Scène | list | Non |
| Minuterie | list | Non |
| Alternance minuterie/télérupteur | list | Non |
| Télérupteur temporisé | list | Non |
| Preset 1 | list | Non |
| Preset 2 | list | Non |
| Objet indication d'état fonction blocage | list | Inactif |
| Polarité | list | 0 = Blocage inactif, 1 = Blocage actif |
| Polarité de l'objet blocage 2 | list | 0 = Blocage inactif, 1 = Blocage actif |
| Priorité entre blocage 1 et blocage 2 | list | Blocage 1 > Blocage 2 |
| Etat si blocage 2 | list | Maintenir l'état courant |
| Etat après blocage 2 | list | Maintenir l'état courant |
| Dummy_1bit_Lockup | list | 0 |
| Dummy_2bit_Lockup | list | 0 |
| Dummy_6bit_Lockup | list | 0 |
| Dummy_1byte_Lockup | list | 0 |
| Objet indication d'état fonction forçage | list | Inactif |
| Polarité | list | 0 = Non forcé, 1 = Forcé |
| Dummy_1bit_Priority | list | 0 |
| Etat après forçage | list | Maintenir l'état courant |
| Comptage sur contact | list | Fermé |
| Sens de comptage | list | Incrémenter |
| Seuil de comptage heures | unsignedInt 1…65535 | 10000 |
| Valeur seuil de comptage modifiable par objet | list | Inactif |
| Emission valeur comptage heures | list | Sur changement d'état |
| Intervalle de valeurs (h) | unsignedInt 1…65535 | 100 |
| Période d'émission cyclique (h) | unsignedInt 0…23 | 1 |
| Période d'émission cyclique (min) | unsignedInt 0…59 | 0 |
| Période d'émission cyclique (s) | unsignedInt 0…59 | 0 |
| Emission objet seuil de comptage atteint | list | Périodiquement |
| Dummy_4bit_OHC | list | 0 |
| Retard mesure de courant après commutation | list | Inactif |
| Secondes (s) | unsignedInt 0…59 | 3 |
| Confirmation de commutations | list | Inactif |
| Seuil de courant pour confirmation commutation (mA) | unsignedInt 20…500 | 20 |
| Surveillance seuil de courant | list | Inactif |
| Seuil de courant 1 (mA) | unsignedInt 20…16000 | 10000 |
| Hystérésis positif seuil de courant 1 (mA) | unsignedInt 10…5000 | 50 |
| Hystérésis négatif seuil de courant 1 (mA) | unsignedInt 10…5000 | 50 |
| Seuil de courant 1 modifiable par objet | list | Inactif |
| Seuil de courant 2 (mA) | unsignedInt 20…16000 | 100 |
| Hystérésis positif seuil de courant 2 (mA) | unsignedInt 10…5000 | 50 |
| Hystérésis négatif seuil de courant 2 (mA) | unsignedInt 10…5000 | 50 |
| Seuil de courant 2 modifiable par objet | list | Inactif |
| Temps d'acquisition pour notification franchissement seuil (h) | unsignedInt 0…23 | 0 |
| Temps d'acquisition pour notification franchissement seuil (min) | unsignedInt 0…59 | 1 |
| Temps d'acquisition pour notification franchissement seuil (s) | unsignedInt 0…59 | 0 |
| Polarité de l'objet notification courant au-dessus seuil 1 | list | 0 = Inférieur au seuil 1, 1 = Supérieur au seuil 1 |
| Polarité de l'objet notification courant entre seuil 1 et 2 | list | 0 = Pas entre seuil 1&2, 1 = Entre seuil 1&2 |
| Polarité de l'objet notification courant en-dessous seuil 2 | list | 0 = Supérieur au seuil 2, 1 = Inférieur au seuil 2 |
| Emission objet surveillance seuils | list | Sur changement d'état |
| Absence courant | list | Inactif |
| Temps d'acquisition pour notification absence courant (h) | unsignedInt 0…119 | 0 |
| Temps d'acquisition pour notification absence courant (min) | unsignedInt 0…59 | 1 |
| Temps d'acquisition pour notification absence courant (s) | unsignedInt 0…59 | 0 |
| Polarité de l'objet notification absence courant | list | 0 = Présence de courant, 1 = Absence de courant |
| Emission objet notification absence courant | list | Sur changement d'état |
| Heures (h) | unsignedInt 0…23 | 6 |
| Compteur nombre de commutations | list | Inactif |
| Changement d'état pour comptage | list | Ouvert --> Fermé |
| Seuil de comptage | unsignedInt 1…65535 | 10000 |
| Valeur seuil de comptage commut. modifiable par objet | list | Inactif |
| Emission valeur de comptage | list | Sur changement d'état |
| Intervalle de valeurs (commutations) | unsignedInt 1…65535 | 100 |
| Emission objet seuil de comptage atteint | list | Sur changement d'état |
| Emission intensité | list | Inactif |
| Type d'objet valeur de courant | list | 2 octets en mA (DPT 7.012) ex. 2430 mA |
| Intervalle de valeurs (mA) | unsignedInt 1…65535 | 100 |
| Courant dans contact ouvert | list | Inactif |
| Temps d'acquisition pour notification courant dans contact ouvert (h) | unsignedInt 0…23 | 0 |
| Temps d'acquisition pour notification courant dans contact ouvert (min) | unsignedInt 0…59 | 1 |
| Temps d'acquisition pour notification courant dans contact ouvert (s) | unsignedInt 0…59 | 0 |
| Polarité de l'objet notification courant dans contact ouvert | list | 0 = Pas de courant détecté, 1 = Courant détecté |
| Dummy_4bit_Current | list | 0 |
| Mode manuel actif pour sortie 2 | list | Oui |
| Mode manuel actif pour sortie 3 | list | Oui |
| Mode manuel actif pour sortie 4 | list | Oui |
| Mode manuel actif pour sortie 5 | list | Oui |
| Mode manuel actif pour sortie 6 | list | Oui |
| Version du logiciel d'application | text | 0.0.87 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| STYA606E 0.1 latest | $5000 | 420A | 2026-11-25 | 422 KB | Download |
About this file
This is the official ETS product database for the Hager Electro 6-fold switch actuator 16A 230V current monitoring (TYA606E), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from Hager Electro
- 4 sorties 4A TX204A
- 4 sorties 10A TX204B
- 4 sorties 16A TX204C
- 6 sorties 4A TX206A
- 6 sorties 4A - Version a1 TX206A - a1
- 6 sorties 10A TX206B
- 6 sorties 10A - Version a1 TX206B - a1
- 6 sorties 16A TX206C
- 6 sorties 16A - Version a1 TX206C - a1
- 6 sorties 3x6A + 3x16A TX206D
- 6 sorties 3x6A + 3x16A - Version a1 TX206D - a1
- 4-output module 4A Lighting Heating TXA204A