CHTF-4.0/15.3.2x (x=0,1,2...) 1CHTFx20DB
GVS · Order number 1CHTFx20DB · Display operation › Touch panel
KNX Smart Touch V40
Download .knxprod KNX Smart Touch V40/1.6 1.6 · 1.3 MB
Product
| Manufacturer | GVS |
|---|---|
| Product name | CHTF-4.0/15.3.2x (x=0,1,2...) |
| Order number | 1CHTFx20DB |
| Product text | KNX Smart Touch V40 |
| Hardware | CHTF-4.0/15.3.2x (x=0,1,2...) |
| Medium | Twisted Pair |
| Bus current (mA) | 12 |
| Rail mounted | No |
| Registration | Certified · 2020-06-16 |
| Languages | de-DE, en-US |
| Catalog entry | M-0085_H-CH20DB-1_HP-004E-16-ED36_CI-1CHTFx20DB-4 |
| Fingerprint | ED36 |
| SHA-256 | 80a678fb0bb9d7b7c2974a3630e7b17015805917cde5e01addede716791e1e39 |
| First seen | 2026-11-25 |
| Markets | 69 markets |
Application program: KNX Smart Touch V40/1.6 1.6
| Application number | $004E |
|---|---|
| Version | 1.6 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | No |
| Minimum ETS version | 5.0 |
| Parameters | 11261 |
| Group objects | 6783 |
Group objects (6783)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | Page 1-HVAC Input | External temperature sensor | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 1 | Page 1-Icon 1 | Switch | 1 Bit | 1.1 switch | CT |
| 1 | Page 1-Icon 1 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 1 | Page 1-Icon 1 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 1 | Page 1-Icon 1 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 1 | Page 1-Icon 1 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 1 | Page 1-Icon 1 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 1 | Page 1-Icon 1 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 1 | Page 1-Icon 1 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 1 | Page 1-Icon 1 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 1 | Page 1-Icon 1 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 1 | Page 1-Icon 1 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 1 | Page 1-AC | External temperature sensor, In | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 1 | Page 1-BgMusic | Power on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 1 | Page 1-RGB Dimming | Red dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 1 | Page 1-RGB Dimming | RGB dimming value | 3 Bytes | 232.600 RGB value 3x(0..255) | CWT |
| 1 | Page 1-RGB Dimming | RGBW dimming value | 6 Bytes | 251.600 RGBW value 4x(0..100%) | CWT |
| 1 | Page 1-Air Quality | AQI, In | 2 Bytes | 7.1 pulses | CWTU |
| 1 | Page 1-Floor heating | External temperature sensor, In | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 1 | Page 1-Energy Meter 1 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 1 | Page 1-Energy Meter 1 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 1 | Page 1-Energy Meter 1 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 1 | Page 1-Energy Meter 1 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 1 | Page 1-Energy Meter 1 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 1 | Page 1-Energy Meter 1 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 1 | Page 1-Energy Meter 1 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 1 | Page 1-Energy Meter 1 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 1 | Page 1-Energy Meter 1 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 2 | Page 1-Icon 1 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 2 | Page 1-Icon 1 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 2 | Page 1-Icon 1 | Stop | 1 Bit | 1.7 step | CT |
| 2 | Page 1-Icon 1 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 2 | Page 1-Icon 1 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 2 | Page 1-Icon 1 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 2 | Page 1-Icon 1 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 2 | Page 1-Icon 1 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 2 | Page 1-Icon 1 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 2 | Page 1-Icon 1 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 2 | Page 1-HVAC Input | Setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 2 | Page 1-AC | Power on/off, Out | 1 Bit | 1.1 switch | CT |
| 2 | Page 1-AC | IR Split unit command, Out | 1 Byte | 17.1 scene number | CT |
| 2 | Page 1-BgMusic | Play/Pause, In/Out | 1 Bit | 1.10 start/stop | CWTU |
| 2 | Page 1-RGB Dimming | Green dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 2 | Page 1-Air Quality | PM2.5, In | 2 Bytes | 9.30 concentration (µg/m³) | CWTU |
| 2 | Page 1-Floor heating | Power on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 2 | Page 1-Ventilation | Power on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 2 | Page 1-Energy Meter 2 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 2 | Page 1-Energy Meter 2 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 2 | Page 1-Energy Meter 2 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 2 | Page 1-Energy Meter 2 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 2 | Page 1-Energy Meter 2 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 2 | Page 1-Energy Meter 2 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 2 | Page 1-Energy Meter 2 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 2 | Page 1-Energy Meter 2 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 2 | Page 1-Energy Meter 2 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 2 | Page 1-Air Quality | PM2.5, In | 2 Bytes | 7.1 pulses | CWTU |
| 3 | Page 1-HVAC Input | Switch Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CWU |
| 3 | Page 1-Icon 1 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 3 | Page 1-Icon 1 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 3 | Page 1-Icon 1 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 3 | Page 1-AC | Status of Power, In | 1 Bit | 1.1 switch | CWTU |
| 3 | Page 1-BgMusic | Next song/Previous song, Out | 1 Bit | 1.7 step | CT |
| 3 | Page 1-RGB Dimming | Blue dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 3 | Page 1-Air Quality | PM10, In | 2 Bytes | 9.30 concentration (µg/m³) | CWTU |
| 3 | Page 1-Floor heating | Heating on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 3 | Page 1-Floor heating | Heating control value, Out | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 3 | Page 1-Ventilation | En./Dis. Heat Recovery, In | 1 Bit | 1.3 enable | CW |
| 3 | Page 1-Energy Meter 3 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 3 | Page 1-Energy Meter 3 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 3 | Page 1-Energy Meter 3 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 3 | Page 1-Energy Meter 3 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 3 | Page 1-Energy Meter 3 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 3 | Page 1-Energy Meter 3 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 3 | Page 1-Energy Meter 3 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 3 | Page 1-Energy Meter 3 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 3 | Page 1-Energy Meter 3 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 3 | Page 1-Air Quality | PM10, In | 2 Bytes | 7.1 pulses | CWTU |
| 4 | Page 1-HVAC Input | HVAC mode | 1 Byte | 20.102 HVAC mode | CW |
| 4 | Page 1-Icon 1 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 4 | Page 1-Icon 1 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 4 | Page 1-HVAC Input | Comfort mode | 1 Bit | 1.3 enable | CW |
| 4 | Page 1-AC | Heat mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 4 | Page 1-AC | Control mode, Out | 1 Byte | 20.105 HVAC control mode | CT |
| 4 | Page 1-BgMusic | Volume+/Volume-, Out | 1 Bit | 1.7 step | CT |
| 4 | Page 1-RGB Dimming | White dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 4 | Page 1-Air Quality | Temperature, In | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 4 | Page 1-Floor heating | Setpoint, In/Out | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 4 | Page 1-Ventilation | Heat Recovery, In/Out | 1 Bit | 1.1 switch | CWTU |
| 4 | Page 1-Energy Meter 4 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 4 | Page 1-Energy Meter 4 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 4 | Page 1-Energy Meter 4 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 4 | Page 1-Energy Meter 4 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 4 | Page 1-Energy Meter 4 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 4 | Page 1-Energy Meter 4 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 4 | Page 1-Energy Meter 4 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 4 | Page 1-Energy Meter 4 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 4 | Page 1-Energy Meter 4 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 4 | Page 1-RGB Dimming | Brightness setting & status | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 5 | Page 1-HVAC Input | Standby mode | 1 Bit | 1.3 enable | CW |
| 5 | Page 1-Icon 2 | Switch | 1 Bit | 1.1 switch | CT |
| 5 | Page 1-Icon 2 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 5 | Page 1-Icon 2 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 5 | Page 1-Icon 2 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 5 | Page 1-Icon 2 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 5 | Page 1-Icon 2 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 5 | Page 1-Icon 2 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 5 | Page 1-Icon 2 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 5 | Page 1-Icon 2 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 5 | Page 1-Icon 2 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 5 | Page 1-Icon 2 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 5 | Page 1-AC | Cool mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 5 | Page 1-AC | Status of control mode, In | 1 Byte | 20.105 HVAC control mode | CWTU |
| 5 | Page 1-BgMusic | Play mode, Out | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 5 | Page 1-Air Quality | Humidity, In | 2 Bytes | 9.7 humidity (%) | CWTU |
| 5 | Page 1-Floor heating | En./Dis. timer, In | 1 Bit | 1.3 enable | CW |
| 5 | Page 1-Ventilation | Filter timer reset, In | 1 Bit | 1.15 reset | CW |
| 5 | Page 1-Energy Meter 5 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 5 | Page 1-Energy Meter 5 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 5 | Page 1-Energy Meter 5 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 5 | Page 1-Energy Meter 5 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 5 | Page 1-Energy Meter 5 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 5 | Page 1-Energy Meter 5 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 5 | Page 1-Energy Meter 5 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 5 | Page 1-Energy Meter 5 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 5 | Page 1-Energy Meter 5 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 5 | Page 1-RGB Dimming | Color Temperature setting & status | 2 Bytes | 7.600 absolute colour temperature (K) | CWT |
| 6 | Page 1-HVAC Input | Economy mode | 1 Bit | 1.3 enable | CW |
| 6 | Page 1-Icon 2 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 6 | Page 1-Icon 2 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 6 | Page 1-Icon 2 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 6 | Page 1-Icon 2 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 6 | Page 1-Icon 2 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 6 | Page 1-Icon 2 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 6 | Page 1-Icon 2 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 6 | Page 1-Icon 2 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 6 | Page 1-Icon 2 | Stop | 1 Bit | 1.7 step | CT |
| 6 | Page 1-Icon 2 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 6 | Page 1-AC | Dry mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 6 | Page 1-BgMusic | Play mode status, In | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 6 | Page 1-Air Quality | VOC, In | 2 Bytes | 9.30 concentration (µg/m³) | CWTU |
| 6 | Page 1-Floor heating | Scene, In | 1 Byte | 18.1 scene control | CW |
| 6 | Page 1-Ventilation | Filter timer counter, In/Out | 2 Bytes | 7.7 time (h) | CWTU |
| 6 | Page 1-Energy Meter 6 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 6 | Page 1-Energy Meter 6 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 6 | Page 1-Energy Meter 6 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 6 | Page 1-Energy Meter 6 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 6 | Page 1-Energy Meter 6 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 6 | Page 1-Energy Meter 6 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 6 | Page 1-Energy Meter 6 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 6 | Page 1-Energy Meter 6 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 6 | Page 1-Energy Meter 6 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 6 | Page 1-Air Quality | VOC, In | 2 Bytes | 7.1 pulses | CWTU |
| 6 | Page 1-Air Quality | VOC, In | 2 Bytes | 9.8 parts/million (ppm) | CWTU |
| 7 | Page 1-HVAC Input | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 7 | Page 1-Icon 2 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 7 | Page 1-Icon 2 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 7 | Page 1-Icon 2 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 7 | Page 1-AC | Fan mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 7 | Page 1-BgMusic | Music source, Out | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 7 | Page 1-Air Quality | CO2, In | 2 Bytes | 9.8 parts/million (ppm) | CWTU |
| 7 | Page 1-Ventilation | Filter alarm, Out | 1 Bit | 1.5 alarm | CT |
| 7 | Page 1-Energy Meter 7 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 7 | Page 1-Energy Meter 7 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 7 | Page 1-Energy Meter 7 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 7 | Page 1-Energy Meter 7 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 7 | Page 1-Energy Meter 7 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 7 | Page 1-Energy Meter 7 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 7 | Page 1-Energy Meter 7 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 7 | Page 1-Energy Meter 7 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 7 | Page 1-Energy Meter 7 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 8 | Page 1-HVAC Input | Fan speed low | 1 Bit | 1.1 switch | CWU |
| 8 | Page 1-Icon 2 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 8 | Page 1-Icon 2 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 8 | Page 1-HVAC Input | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 8 | Page 1-BgMusic | Music source status, In | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 8 | Page 1-Ventilation | Fan Speed No.1 1Bit, In/Out | 1 Bit | 1.1 switch | CWTU |
| 8 | Page 1-Ventilation | Fan speed, Out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 8 | Page 1-Energy Meter 8 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 8 | Page 1-Energy Meter 8 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 8 | Page 1-Energy Meter 8 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 8 | Page 1-Energy Meter 8 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 8 | Page 1-Energy Meter 8 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 8 | Page 1-Energy Meter 8 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 8 | Page 1-Energy Meter 8 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 8 | Page 1-Energy Meter 8 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 8 | Page 1-Energy Meter 8 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 8 | Page 1-AC | Auto mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 8 | Page 1-Air Quality | Brightness, In | 2 Bytes | 9.4 lux (Lux) | CWTU |
| 8 | Page 1-Air Quality | Brightness, In | 2 Bytes | 7.13 brightness (lux) | CWTU |
| 9 | Page 1-HVAC Input | Fan speed medium | 1 Bit | 1.1 switch | CWU |
| 9 | Page 1-Icon 3 | Switch | 1 Bit | 1.1 switch | CT |
| 9 | Page 1-Icon 3 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 9 | Page 1-Icon 3 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 9 | Page 1-Icon 3 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 9 | Page 1-Icon 3 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 9 | Page 1-Icon 3 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 9 | Page 1-Icon 3 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 9 | Page 1-Icon 3 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 9 | Page 1-Icon 3 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 9 | Page 1-Icon 3 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 9 | Page 1-Icon 3 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 9 | Page 1-AC | Fan speed low, In/Out | 1 Bit | 1.1 switch | CWTU |
| 9 | Page 1-AC | Fan speed, Out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 9 | Page 1-Ventilation | Fan Speed No.2 1Bit, In/Out | 1 Bit | 1.1 switch | CWTU |
| 9 | Page 1-Ventilation | Stauts of Fan speed, In | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 9 | Page 1-Air Quality | Windspeed, In | 2 Bytes | 9.5 speed (m/s) | CWTU |
| 10 | Page 1-HVAC Input | Fan speed high | 1 Bit | 1.1 switch | CWU |
| 10 | Page 1-Icon 3 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 10 | Page 1-Icon 3 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 10 | Page 1-Icon 3 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 10 | Page 1-Icon 3 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 10 | Page 1-Icon 3 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 10 | Page 1-Icon 3 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 10 | Page 1-Icon 3 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 10 | Page 1-Icon 3 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 10 | Page 1-Icon 3 | Stop | 1 Bit | 1.7 step | CT |
| 10 | Page 1-Icon 3 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 10 | Page 1-AC | Fan speed medium, In/Out | 1 Bit | 1.1 switch | CWTU |
| 10 | Page 1-AC | Stauts of Fan speed, In | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 10 | Page 1-Ventilation | Fan Speed No.3 1Bit, In/Out | 1 Bit | 1.1 switch | CWTU |
| 11 | Page 1-HVAC Input | Fan speed off | 1 Bit | 1.1 switch | CWU |
| 11 | Page 1-Icon 3 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 11 | Page 1-Icon 3 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 11 | Page 1-Icon 3 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 11 | Page 1-AC | Fan speed high, In/Out | 1 Bit | 1.1 switch | CWTU |
| 11 | Page 1-Ventilation | Automatic function, In/Out | 1 Bit | 1.3 enable | CWTU |
| 12 | Page 1-HVAC Input | Fan Automatic operation | 1 Bit | 1.3 enable | CWU |
| 12 | Page 1-Icon 3 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 12 | Page 1-Icon 3 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 12 | Page 1-AC | Fan speed Auto, In/Out | 1 Bit | 1.1 switch | CWTU |
| 12 | Page 1-Ventilation | CO2,In | 2 Bytes | 7.1 pulses | CWTU |
| 12 | Page 1-Ventilation | CO2,In | 2 Bytes | 9.8 parts/million (ppm) | CWTU |
| 13 | Page 1-Icon 4 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 13 | Page 1-Icon 4 | Switch | 1 Bit | 1.1 switch | CT |
| 13 | Page 1-Icon 4 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 13 | Page 1-Icon 4 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 13 | Page 1-Icon 4 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 13 | Page 1-Icon 4 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 13 | Page 1-Icon 4 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 13 | Page 1-Icon 4 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 13 | Page 1-Icon 4 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 13 | Page 1-Icon 4 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 13 | Page 1-Icon 4 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 13 | Page 1-HVAC Output | Instantaneous setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 13 | Page 1-AC | Wind direction fixed/swing, In/Out | 1 Bit | 1.17 trigger | CWTU |
| 13 | Page 1-Ventilation | PM2.5, In | 2 Bytes | 7.1 pulses | CWTU |
| 13 | Page 1-Ventilation | PM2.5, In | 2 Bytes | 9.30 concentration (µg/m³) | CWTU |
| 14 | Page 1-Icon 4 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 14 | Page 1-Icon 4 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 14 | Page 1-Icon 4 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 14 | Page 1-Icon 4 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 14 | Page 1-Icon 4 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 14 | Page 1-Icon 4 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 14 | Page 1-Icon 4 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 14 | Page 1-Icon 4 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 14 | Page 1-Icon 4 | Stop | 1 Bit | 1.7 step | CT |
| 14 | Page 1-Icon 4 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 14 | Page 1-HVAC Output | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CRT |
| 14 | Page 1-Ventilation | Scene, In | 1 Byte | 18.1 scene control | CW |
| 14 | Page 1-AC | Wind direction position, Out | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 15 | Page 1-Icon 4 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 15 | Page 1-Icon 4 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 15 | Page 1-Icon 4 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 15 | Page 1-HVAC Output | HVAC mode | 1 Byte | 20.102 HVAC mode | CRT |
| 15 | Page 1-HVAC Output | Comfort mode | 1 Bit | 1.3 enable | CT |
| 15 | Page 1-AC | Status of Wind direction position, In | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 16 | Page 1-Icon 4 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 16 | Page 1-Icon 4 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 16 | Page 1-HVAC Output | Standby mode | 1 Bit | 1.3 enable | CT |
| 16 | Page 1-AC | Temperature setpoint, In/Out | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 16 | Page 1-AC | Temperature setpoint, In/Out | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 17 | Page 1-Icon 5 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 17 | Page 1-Icon 5 | Switch | 1 Bit | 1.1 switch | CT |
| 17 | Page 1-Icon 5 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 17 | Page 1-Icon 5 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 17 | Page 1-Icon 5 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 17 | Page 1-Icon 5 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 17 | Page 1-Icon 5 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 17 | Page 1-Icon 5 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 17 | Page 1-Icon 5 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 17 | Page 1-Icon 5 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 17 | Page 1-Icon 5 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 17 | Page 1-HVAC Output | Economy mode | 1 Bit | 1.3 enable | CT |
| 18 | Page 1-Icon 5 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 18 | Page 1-Icon 5 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 18 | Page 1-Icon 5 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 18 | Page 1-Icon 5 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 18 | Page 1-Icon 5 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 18 | Page 1-Icon 5 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 18 | Page 1-Icon 5 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 18 | Page 1-Icon 5 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 18 | Page 1-Icon 5 | Stop | 1 Bit | 1.7 step | CT |
| 18 | Page 1-Icon 5 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 18 | Page 1-HVAC Output | Frost/Heat protection mode | 1 Bit | 1.3 enable | CT |
| 19 | Page 1-Icon 5 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 19 | Page 1-Icon 5 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 19 | Page 1-Icon 5 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 19 | Page 1-HVAC Output | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 19 | Page 1-HVAC Output | Heating control value | 1 Bit | 1.1 switch | CT |
| 19 | Page 1-HVAC Output | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 19 | Page 1-HVAC Output | Heating/cooling control value | 1 Bit | 1.1 switch | CT |
| 20 | Page 1-Icon 5 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 20 | Page 1-Icon 5 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 20 | Page 1-HVAC Output | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 20 | Page 1-HVAC Output | Cooling control value | 1 Bit | 1.1 switch | CT |
| 21 | Page 1-Icon 6 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 21 | Page 1-Icon 6 | Switch | 1 Bit | 1.1 switch | CT |
| 21 | Page 1-Icon 6 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 21 | Page 1-Icon 6 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 21 | Page 1-Icon 6 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 21 | Page 1-Icon 6 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 21 | Page 1-Icon 6 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 21 | Page 1-Icon 6 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 21 | Page 1-Icon 6 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 21 | Page 1-Icon 6 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 21 | Page 1-Icon 6 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 21 | Page 1-HVAC Output | Fan speed low | 1 Bit | 1.1 switch | CT |
| 21 | Page 1-HVAC Output | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CT |
| 22 | Page 1-Icon 6 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 22 | Page 1-Icon 6 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 22 | Page 1-Icon 6 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 22 | Page 1-Icon 6 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 22 | Page 1-Icon 6 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 22 | Page 1-Icon 6 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 22 | Page 1-Icon 6 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 22 | Page 1-Icon 6 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 22 | Page 1-Icon 6 | Stop | 1 Bit | 1.7 step | CT |
| 22 | Page 1-Icon 6 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 22 | Page 1-HVAC Output | Fan speed medium | 1 Bit | 1.1 switch | CT |
| 23 | Page 1-Icon 6 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 23 | Page 1-Icon 6 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 23 | Page 1-Icon 6 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 23 | Page 1-HVAC Output | Fan speed high | 1 Bit | 1.1 switch | CT |
| 24 | Page 1-Icon 6 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 24 | Page 1-Icon 6 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 24 | Page 1-HVAC Output | Fan speed off | 1 Bit | 1.1 switch | CT |
| 25 | Page 1-Icon 7 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 25 | Page 1-Icon 7 | Switch | 1 Bit | 1.1 switch | CT |
| 25 | Page 1-Icon 7 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 25 | Page 1-Icon 7 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 25 | Page 1-Icon 7 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 25 | Page 1-Icon 7 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 25 | Page 1-Icon 7 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 25 | Page 1-Icon 7 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 25 | Page 1-Icon 7 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 25 | Page 1-Icon 7 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 25 | Page 1-Icon 7 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 25 | Page 1-HVAC Output | Fan Automatic operation | 1 Bit | 1.3 enable | CT |
| 26 | Page 1-Icon 7 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 26 | Page 1-Icon 7 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 26 | Page 1-Icon 7 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 26 | Page 1-Icon 7 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 26 | Page 1-Icon 7 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 26 | Page 1-Icon 7 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 26 | Page 1-Icon 7 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 26 | Page 1-Icon 7 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 26 | Page 1-Icon 7 | Stop | 1 Bit | 1.7 step | CT |
| 26 | Page 1-Icon 7 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 26 | Page 1-HVAC Output | HVAC on/off | 1 Bit | 1.1 switch | CWTU |
| 27 | Page 1-Icon 7 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 27 | Page 1-Icon 7 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 27 | Page 1-Icon 7 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 27 | Page 1-HVAC Output | Base setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 28 | Page 1-Icon 7 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 28 | Page 1-Icon 7 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 29 | Page 1-Icon 8 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 29 | Page 1-Icon 8 | Switch | 1 Bit | 1.1 switch | CT |
| 29 | Page 1-Icon 8 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 29 | Page 1-Icon 8 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 29 | Page 1-Icon 8 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 29 | Page 1-Icon 8 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 29 | Page 1-Icon 8 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 29 | Page 1-Icon 8 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 29 | Page 1-Icon 8 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 29 | Page 1-Icon 8 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 29 | Page 1-Icon 8 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 30 | Page 1-Icon 8 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 30 | Page 1-Icon 8 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 30 | Page 1-Icon 8 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 30 | Page 1-Icon 8 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 30 | Page 1-Icon 8 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 30 | Page 1-Icon 8 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 30 | Page 1-Icon 8 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 30 | Page 1-Icon 8 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 30 | Page 1-Icon 8 | Stop | 1 Bit | 1.7 step | CT |
| 30 | Page 1-Icon 8 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 31 | Page 1-Icon 8 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 31 | Page 1-Icon 8 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 31 | Page 1-Icon 8 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 32 | Page 1-Icon 8 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 32 | Page 1-Icon 8 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 33 | Page 2-Icon 1 | Switch | 1 Bit | 1.1 switch | CT |
| 33 | Page 2-Icon 1 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 33 | Page 2-Icon 1 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 33 | Page 2-Icon 1 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 33 | Page 2-Icon 1 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 33 | Page 2-Icon 1 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 33 | Page 2-Icon 1 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 33 | Page 2-Icon 1 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 33 | Page 2-Icon 1 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 33 | Page 2-Icon 1 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 33 | Page 2-Icon 1 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 33 | Page 2-HVAC Input | External temperature sensor | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 33 | Page 2-AC | External temperature sensor, In | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 33 | Page 2-BgMusic | Power on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 33 | Page 2-RGB Dimming | RGB dimming value | 3 Bytes | 232.600 RGB value 3x(0..255) | CWT |
| 33 | Page 2-RGB Dimming | Red dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 33 | Page 2-RGB Dimming | RGBW dimming value | 6 Bytes | 251.600 RGBW value 4x(0..100%) | CWT |
| 33 | Page 2-Air Quality | AQI, In | 2 Bytes | 7.1 pulses | CWTU |
| 33 | Page 2-Floor heating | External temperature sensor, In | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 33 | Page 2-Energy Meter 1 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 33 | Page 2-Energy Meter 1 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 33 | Page 2-Energy Meter 1 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 33 | Page 2-Energy Meter 1 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 33 | Page 2-Energy Meter 1 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 33 | Page 2-Energy Meter 1 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 33 | Page 2-Energy Meter 1 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 33 | Page 2-Energy Meter 1 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 33 | Page 2-Energy Meter 1 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 34 | Page 2-Icon 1 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 34 | Page 2-Icon 1 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 34 | Page 2-Icon 1 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 34 | Page 2-Icon 1 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 34 | Page 2-Icon 1 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 34 | Page 2-Icon 1 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 34 | Page 2-Icon 1 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 34 | Page 2-Icon 1 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 34 | Page 2-Icon 1 | Stop | 1 Bit | 1.7 step | CT |
| 34 | Page 2-Icon 1 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 34 | Page 2-HVAC Input | Setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 34 | Page 2-AC | IR Split unit command, Out | 1 Byte | 17.1 scene number | CT |
| 34 | Page 2-AC | Power on/off, Out | 1 Bit | 1.1 switch | CT |
| 34 | Page 2-BgMusic | Play/Pause, In/Out | 1 Bit | 1.10 start/stop | CWTU |
| 34 | Page 2-RGB Dimming | Green dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 34 | Page 2-Air Quality | PM2.5, In | 2 Bytes | 7.1 pulses | CWTU |
| 34 | Page 2-Air Quality | PM2.5, In | 2 Bytes | 9.30 concentration (µg/m³) | CWTU |
| 34 | Page 2-Floor heating | Power on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 34 | Page 2-Ventilation | Power on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 34 | Page 2-Energy Meter 2 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 34 | Page 2-Energy Meter 2 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 34 | Page 2-Energy Meter 2 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 34 | Page 2-Energy Meter 2 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 34 | Page 2-Energy Meter 2 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 34 | Page 2-Energy Meter 2 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 34 | Page 2-Energy Meter 2 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 34 | Page 2-Energy Meter 2 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 34 | Page 2-Energy Meter 2 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 35 | Page 2-Icon 1 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 35 | Page 2-Icon 1 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 35 | Page 2-Icon 1 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 35 | Page 2-HVAC Input | Switch Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CWU |
| 35 | Page 2-AC | Status of Power, In | 1 Bit | 1.1 switch | CWTU |
| 35 | Page 2-BgMusic | Next song/Previous song, Out | 1 Bit | 1.7 step | CT |
| 35 | Page 2-RGB Dimming | Blue dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 35 | Page 2-Air Quality | PM10, In | 2 Bytes | 7.1 pulses | CWTU |
| 35 | Page 2-Air Quality | PM10, In | 2 Bytes | 9.30 concentration (µg/m³) | CWTU |
| 35 | Page 2-Floor heating | Heating on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 35 | Page 2-Floor heating | Heating control value, Out | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 35 | Page 2-Ventilation | En./Dis. Heat Recovery, In | 1 Bit | 1.3 enable | CW |
| 35 | Page 2-Energy Meter 3 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 35 | Page 2-Energy Meter 3 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 35 | Page 2-Energy Meter 3 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 35 | Page 2-Energy Meter 3 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 35 | Page 2-Energy Meter 3 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 35 | Page 2-Energy Meter 3 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 35 | Page 2-Energy Meter 3 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 35 | Page 2-Energy Meter 3 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 35 | Page 2-Energy Meter 3 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 36 | Page 2-Icon 1 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 36 | Page 2-Icon 1 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 36 | Page 2-HVAC Input | Comfort mode | 1 Bit | 1.3 enable | CW |
| 36 | Page 2-HVAC Input | HVAC mode | 1 Byte | 20.102 HVAC mode | CW |
| 36 | Page 2-AC | Heat mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 36 | Page 2-AC | Control mode, Out | 1 Byte | 20.105 HVAC control mode | CT |
| 36 | Page 2-BgMusic | Volume+/Volume-, Out | 1 Bit | 1.7 step | CT |
| 36 | Page 2-RGB Dimming | White dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 36 | Page 2-Air Quality | Temperature, In | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 36 | Page 2-Floor heating | Setpoint, In/Out | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 36 | Page 2-Ventilation | Heat Recovery, In/Out | 1 Bit | 1.1 switch | CWTU |
| 36 | Page 2-Energy Meter 4 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 36 | Page 2-Energy Meter 4 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 36 | Page 2-Energy Meter 4 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 36 | Page 2-Energy Meter 4 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 36 | Page 2-Energy Meter 4 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 36 | Page 2-Energy Meter 4 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 36 | Page 2-Energy Meter 4 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 36 | Page 2-Energy Meter 4 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 36 | Page 2-Energy Meter 4 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 36 | Page 2-RGB Dimming | Brightness setting & status | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 37 | Page 2-Icon 2 | Switch | 1 Bit | 1.1 switch | CT |
| 37 | Page 2-Icon 2 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 37 | Page 2-Icon 2 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 37 | Page 2-Icon 2 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 37 | Page 2-Icon 2 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 37 | Page 2-Icon 2 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 37 | Page 2-Icon 2 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 37 | Page 2-Icon 2 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 37 | Page 2-Icon 2 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 37 | Page 2-Icon 2 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 37 | Page 2-Icon 2 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 37 | Page 2-HVAC Input | Standby mode | 1 Bit | 1.3 enable | CW |
| 37 | Page 2-AC | Cool mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 37 | Page 2-AC | Status of control mode, In | 1 Byte | 20.105 HVAC control mode | CWTU |
| 37 | Page 2-BgMusic | Play mode, Out | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 37 | Page 2-RGB Dimming | Color Temperature setting & status | 2 Bytes | 7.600 absolute colour temperature (K) | CWT |
| 37 | Page 2-Air Quality | Humidity, In | 2 Bytes | 9.7 humidity (%) | CWTU |
| 37 | Page 2-Floor heating | En./Dis. timer, In | 1 Bit | 1.3 enable | CW |
| 37 | Page 2-Ventilation | Filter timer reset, In | 1 Bit | 1.15 reset | CW |
| 37 | Page 2-Energy Meter 5 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 37 | Page 2-Energy Meter 5 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 37 | Page 2-Energy Meter 5 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 37 | Page 2-Energy Meter 5 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 37 | Page 2-Energy Meter 5 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 37 | Page 2-Energy Meter 5 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 37 | Page 2-Energy Meter 5 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 37 | Page 2-Energy Meter 5 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 37 | Page 2-Energy Meter 5 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 38 | Page 2-Icon 2 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 38 | Page 2-Icon 2 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 38 | Page 2-Icon 2 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 38 | Page 2-Icon 2 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 38 | Page 2-Icon 2 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 38 | Page 2-Icon 2 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 38 | Page 2-Icon 2 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 38 | Page 2-Icon 2 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 38 | Page 2-Icon 2 | Stop | 1 Bit | 1.7 step | CT |
| 38 | Page 2-Icon 2 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 38 | Page 2-HVAC Input | Economy mode | 1 Bit | 1.3 enable | CW |
| 38 | Page 2-AC | Dry mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 38 | Page 2-BgMusic | Play mode status, In | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 38 | Page 2-Air Quality | VOC, In | 2 Bytes | 7.1 pulses | CWTU |
| 38 | Page 2-Air Quality | VOC, In | 2 Bytes | 9.30 concentration (µg/m³) | CWTU |
| 38 | Page 2-Floor heating | Scene, In | 1 Byte | 18.1 scene control | CW |
| 38 | Page 2-Ventilation | Filter timer counter, In/Out | 2 Bytes | 7.7 time (h) | CWTU |
| 38 | Page 2-Energy Meter 6 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 38 | Page 2-Energy Meter 6 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 38 | Page 2-Energy Meter 6 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 38 | Page 2-Energy Meter 6 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 38 | Page 2-Energy Meter 6 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 38 | Page 2-Energy Meter 6 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 38 | Page 2-Energy Meter 6 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 38 | Page 2-Energy Meter 6 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 38 | Page 2-Energy Meter 6 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 38 | Page 2-Air Quality | VOC, In | 2 Bytes | 9.8 parts/million (ppm) | CWTU |
| 39 | Page 2-Icon 2 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 39 | Page 2-Icon 2 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 39 | Page 2-Icon 2 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 39 | Page 2-HVAC Input | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 39 | Page 2-AC | Fan mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 39 | Page 2-BgMusic | Music source, Out | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 39 | Page 2-Air Quality | CO2, In | 2 Bytes | 9.8 parts/million (ppm) | CWTU |
| 39 | Page 2-Ventilation | Filter alarm, Out | 1 Bit | 1.5 alarm | CT |
| 39 | Page 2-Energy Meter 7 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 39 | Page 2-Energy Meter 7 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 39 | Page 2-Energy Meter 7 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 39 | Page 2-Energy Meter 7 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 39 | Page 2-Energy Meter 7 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 39 | Page 2-Energy Meter 7 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 39 | Page 2-Energy Meter 7 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 39 | Page 2-Energy Meter 7 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 39 | Page 2-Energy Meter 7 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 40 | Page 2-Icon 2 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 40 | Page 2-Icon 2 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 40 | Page 2-HVAC Input | Fan speed low | 1 Bit | 1.1 switch | CWU |
| 40 | Page 2-HVAC Input | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 40 | Page 2-AC | Auto mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 40 | Page 2-BgMusic | Music source status, In | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 40 | Page 2-Ventilation | Fan Speed No.1 1Bit, In/Out | 1 Bit | 1.1 switch | CWTU |
| 40 | Page 2-Ventilation | Fan speed, Out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 40 | Page 2-Energy Meter 8 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 40 | Page 2-Energy Meter 8 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 40 | Page 2-Energy Meter 8 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 40 | Page 2-Energy Meter 8 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 40 | Page 2-Energy Meter 8 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 40 | Page 2-Energy Meter 8 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 40 | Page 2-Energy Meter 8 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 40 | Page 2-Energy Meter 8 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 40 | Page 2-Energy Meter 8 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 40 | Page 2-Air Quality | Brightness, In | 2 Bytes | 9.4 lux (Lux) | CWTU |
| 40 | Page 2-Air Quality | Brightness, In | 2 Bytes | 7.13 brightness (lux) | CWTU |
| 41 | Page 2-Icon 3 | Switch | 1 Bit | 1.1 switch | CT |
| 41 | Page 2-Icon 3 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 41 | Page 2-Icon 3 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 41 | Page 2-Icon 3 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 41 | Page 2-Icon 3 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 41 | Page 2-Icon 3 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 41 | Page 2-Icon 3 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 41 | Page 2-Icon 3 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 41 | Page 2-Icon 3 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 41 | Page 2-Icon 3 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 41 | Page 2-Icon 3 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 41 | Page 2-HVAC Input | Fan speed medium | 1 Bit | 1.1 switch | CWU |
| 41 | Page 2-AC | Fan speed low, In/Out | 1 Bit | 1.1 switch | CWTU |
| 41 | Page 2-AC | Fan speed, Out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 41 | Page 2-Ventilation | Fan Speed No.2 1Bit, In/Out | 1 Bit | 1.1 switch | CWTU |
| 41 | Page 2-Ventilation | Stauts of Fan speed, In | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 41 | Page 2-Air Quality | Windspeed, In | 2 Bytes | 9.5 speed (m/s) | CWTU |
| 42 | Page 2-Icon 3 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 42 | Page 2-Icon 3 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 42 | Page 2-Icon 3 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 42 | Page 2-Icon 3 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 42 | Page 2-Icon 3 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 42 | Page 2-Icon 3 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 42 | Page 2-Icon 3 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 42 | Page 2-Icon 3 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 42 | Page 2-Icon 3 | Stop | 1 Bit | 1.7 step | CT |
| 42 | Page 2-Icon 3 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 42 | Page 2-HVAC Input | Fan speed high | 1 Bit | 1.1 switch | CWU |
| 42 | Page 2-AC | Fan speed medium, In/Out | 1 Bit | 1.1 switch | CWTU |
| 42 | Page 2-AC | Stauts of Fan speed, In | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 42 | Page 2-Ventilation | Fan Speed No.3 1Bit, In/Out | 1 Bit | 1.1 switch | CWTU |
| 43 | Page 2-Icon 3 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 43 | Page 2-Icon 3 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 43 | Page 2-Icon 3 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 43 | Page 2-HVAC Input | Fan speed off | 1 Bit | 1.1 switch | CWU |
| 43 | Page 2-AC | Fan speed high, In/Out | 1 Bit | 1.1 switch | CWTU |
| 43 | Page 2-Ventilation | Automatic function, In/Out | 1 Bit | 1.3 enable | CWTU |
| 44 | Page 2-Icon 3 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 44 | Page 2-Icon 3 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 44 | Page 2-HVAC Input | Fan Automatic operation | 1 Bit | 1.3 enable | CWU |
| 44 | Page 2-AC | Fan speed Auto, In/Out | 1 Bit | 1.1 switch | CWTU |
| 44 | Page 2-Ventilation | CO2,In | 2 Bytes | 7.1 pulses | CWTU |
| 44 | Page 2-Ventilation | CO2,In | 2 Bytes | 9.8 parts/million (ppm) | CWTU |
| 45 | Page 2-Icon 4 | Switch | 1 Bit | 1.1 switch | CT |
| 45 | Page 2-Icon 4 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 45 | Page 2-Icon 4 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 45 | Page 2-Icon 4 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 45 | Page 2-Icon 4 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 45 | Page 2-Icon 4 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 45 | Page 2-Icon 4 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 45 | Page 2-Icon 4 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 45 | Page 2-Icon 4 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 45 | Page 2-Icon 4 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 45 | Page 2-Icon 4 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 45 | Page 2-HVAC Output | Instantaneous setpoint | 2 Bytes | 9.1 temperature (°C) | CRT |
| 45 | Page 2-AC | Wind direction fixed/swing, In/Out | 1 Bit | 1.17 trigger | CWTU |
| 45 | Page 2-Ventilation | PM2.5, In | 2 Bytes | 7.1 pulses | CWTU |
| 45 | Page 2-Ventilation | PM2.5, In | 2 Bytes | 9.30 concentration (µg/m³) | CWTU |
| 46 | Page 2-Icon 4 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 46 | Page 2-Icon 4 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 46 | Page 2-Icon 4 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 46 | Page 2-Icon 4 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 46 | Page 2-Icon 4 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 46 | Page 2-Icon 4 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 46 | Page 2-Icon 4 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 46 | Page 2-Icon 4 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 46 | Page 2-Icon 4 | Stop | 1 Bit | 1.7 step | CT |
| 46 | Page 2-Icon 4 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 46 | Page 2-HVAC Output | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CRT |
| 46 | Page 2-AC | Wind direction position, Out | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 46 | Page 2-Ventilation | Scene, In | 1 Byte | 18.1 scene control | CW |
| 47 | Page 2-Icon 4 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 47 | Page 2-Icon 4 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 47 | Page 2-Icon 4 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 47 | Page 2-HVAC Output | Comfort mode | 1 Bit | 1.3 enable | CT |
| 47 | Page 2-HVAC Output | HVAC mode | 1 Byte | 20.102 HVAC mode | CRT |
| 47 | Page 2-AC | Status of Wind direction position, In | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 48 | Page 2-Icon 4 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 48 | Page 2-Icon 4 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 48 | Page 2-HVAC Output | Standby mode | 1 Bit | 1.3 enable | CT |
| 48 | Page 2-AC | Temperature setpoint, In/Out | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 48 | Page 2-AC | Temperature setpoint, In/Out | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 49 | Page 2-Icon 5 | Switch | 1 Bit | 1.1 switch | CT |
| 49 | Page 2-Icon 5 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 49 | Page 2-Icon 5 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 49 | Page 2-Icon 5 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 49 | Page 2-Icon 5 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 49 | Page 2-Icon 5 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 49 | Page 2-Icon 5 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 49 | Page 2-Icon 5 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 49 | Page 2-Icon 5 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 49 | Page 2-Icon 5 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 49 | Page 2-Icon 5 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 49 | Page 2-HVAC Output | Economy mode | 1 Bit | 1.3 enable | CT |
| 50 | Page 2-Icon 5 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 50 | Page 2-Icon 5 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 50 | Page 2-Icon 5 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 50 | Page 2-Icon 5 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 50 | Page 2-Icon 5 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 50 | Page 2-Icon 5 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 50 | Page 2-Icon 5 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 50 | Page 2-Icon 5 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 50 | Page 2-Icon 5 | Stop | 1 Bit | 1.7 step | CT |
| 50 | Page 2-Icon 5 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 50 | Page 2-HVAC Output | Frost/Heat protection mode | 1 Bit | 1.3 enable | CT |
| 51 | Page 2-Icon 5 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 51 | Page 2-Icon 5 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 51 | Page 2-Icon 5 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 51 | Page 2-HVAC Output | Heating control value | 1 Bit | 1.1 switch | CT |
| 51 | Page 2-HVAC Output | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 51 | Page 2-HVAC Output | Heating/cooling control value | 1 Bit | 1.1 switch | CT |
| 51 | Page 2-HVAC Output | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 52 | Page 2-Icon 5 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 52 | Page 2-Icon 5 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 52 | Page 2-HVAC Output | Cooling control value | 1 Bit | 1.1 switch | CT |
| 52 | Page 2-HVAC Output | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 53 | Page 2-Icon 6 | Switch | 1 Bit | 1.1 switch | CT |
| 53 | Page 2-Icon 6 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 53 | Page 2-Icon 6 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 53 | Page 2-Icon 6 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 53 | Page 2-Icon 6 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 53 | Page 2-Icon 6 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 53 | Page 2-Icon 6 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 53 | Page 2-Icon 6 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 53 | Page 2-Icon 6 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 53 | Page 2-Icon 6 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 53 | Page 2-Icon 6 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 53 | Page 2-HVAC Output | Fan speed low | 1 Bit | 1.1 switch | CT |
| 53 | Page 2-HVAC Output | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CT |
| 54 | Page 2-Icon 6 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 54 | Page 2-Icon 6 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 54 | Page 2-Icon 6 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 54 | Page 2-Icon 6 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 54 | Page 2-Icon 6 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 54 | Page 2-Icon 6 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 54 | Page 2-Icon 6 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 54 | Page 2-Icon 6 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 54 | Page 2-Icon 6 | Stop | 1 Bit | 1.7 step | CT |
| 54 | Page 2-Icon 6 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 54 | Page 2-HVAC Output | Fan speed medium | 1 Bit | 1.1 switch | CT |
| 55 | Page 2-Icon 6 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 55 | Page 2-Icon 6 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 55 | Page 2-Icon 6 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 55 | Page 2-HVAC Output | Fan speed high | 1 Bit | 1.1 switch | CT |
| 56 | Page 2-Icon 6 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 56 | Page 2-Icon 6 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 56 | Page 2-HVAC Output | Fan speed off | 1 Bit | 1.1 switch | CT |
| 57 | Page 2-Icon 7 | Switch | 1 Bit | 1.1 switch | CT |
| 57 | Page 2-Icon 7 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 57 | Page 2-Icon 7 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 57 | Page 2-Icon 7 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 57 | Page 2-Icon 7 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 57 | Page 2-Icon 7 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 57 | Page 2-Icon 7 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 57 | Page 2-Icon 7 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 57 | Page 2-Icon 7 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 57 | Page 2-Icon 7 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 57 | Page 2-Icon 7 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 57 | Page 2-HVAC Output | Fan Automatic operation | 1 Bit | 1.3 enable | CT |
| 58 | Page 2-Icon 7 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 58 | Page 2-Icon 7 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 58 | Page 2-Icon 7 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 58 | Page 2-Icon 7 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 58 | Page 2-Icon 7 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 58 | Page 2-Icon 7 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 58 | Page 2-Icon 7 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 58 | Page 2-Icon 7 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 58 | Page 2-Icon 7 | Stop | 1 Bit | 1.7 step | CT |
| 58 | Page 2-Icon 7 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 58 | Page 2-HVAC Output | HVAC on/off | 1 Bit | 1.1 switch | CWTU |
| 59 | Page 2-Icon 7 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 59 | Page 2-Icon 7 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 59 | Page 2-Icon 7 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 59 | Page 2-HVAC Output | Base setpoint temperature | 2 Bytes | 9.1 temperature (°C) | CRT |
| 60 | Page 2-Icon 7 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 60 | Page 2-Icon 7 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 61 | Page 2-Icon 8 | Switch | 1 Bit | 1.1 switch | CT |
| 61 | Page 2-Icon 8 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 61 | Page 2-Icon 8 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 61 | Page 2-Icon 8 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 61 | Page 2-Icon 8 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 61 | Page 2-Icon 8 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 61 | Page 2-Icon 8 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 61 | Page 2-Icon 8 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 61 | Page 2-Icon 8 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 61 | Page 2-Icon 8 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 61 | Page 2-Icon 8 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 62 | Page 2-Icon 8 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 62 | Page 2-Icon 8 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 62 | Page 2-Icon 8 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 62 | Page 2-Icon 8 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 62 | Page 2-Icon 8 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 62 | Page 2-Icon 8 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 62 | Page 2-Icon 8 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 62 | Page 2-Icon 8 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 62 | Page 2-Icon 8 | Stop | 1 Bit | 1.7 step | CT |
| 62 | Page 2-Icon 8 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 63 | Page 2-Icon 8 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 63 | Page 2-Icon 8 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 63 | Page 2-Icon 8 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 64 | Page 2-Icon 8 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 64 | Page 2-Icon 8 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 65 | Page 3-Icon 1 | Switch | 1 Bit | 1.1 switch | CT |
| 65 | Page 3-Icon 1 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 65 | Page 3-Icon 1 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 65 | Page 3-Icon 1 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 65 | Page 3-Icon 1 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 65 | Page 3-Icon 1 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 65 | Page 3-Icon 1 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 65 | Page 3-Icon 1 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 65 | Page 3-Icon 1 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 65 | Page 3-Icon 1 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 65 | Page 3-Icon 1 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 65 | Page 3-HVAC Input | External temperature sensor | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 65 | Page 3-AC | External temperature sensor, In | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 65 | Page 3-BgMusic | Power on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 65 | Page 3-RGB Dimming | RGB dimming value | 3 Bytes | 232.600 RGB value 3x(0..255) | CWT |
| 65 | Page 3-RGB Dimming | Red dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 65 | Page 3-RGB Dimming | RGBW dimming value | 6 Bytes | 251.600 RGBW value 4x(0..100%) | CWT |
| 65 | Page 3-Air Quality | AQI, In | 2 Bytes | 7.1 pulses | CWTU |
| 65 | Page 3-Floor heating | External temperature sensor, In | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 65 | Page 3-Energy Meter 1 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 65 | Page 3-Energy Meter 1 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 65 | Page 3-Energy Meter 1 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 65 | Page 3-Energy Meter 1 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 65 | Page 3-Energy Meter 1 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 65 | Page 3-Energy Meter 1 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 65 | Page 3-Energy Meter 1 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 65 | Page 3-Energy Meter 1 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 65 | Page 3-Energy Meter 1 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 66 | Page 3-Icon 1 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 66 | Page 3-Icon 1 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 66 | Page 3-Icon 1 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 66 | Page 3-Icon 1 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 66 | Page 3-Icon 1 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 66 | Page 3-Icon 1 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 66 | Page 3-Icon 1 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 66 | Page 3-Icon 1 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 66 | Page 3-Icon 1 | Stop | 1 Bit | 1.7 step | CT |
| 66 | Page 3-Icon 1 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 66 | Page 3-HVAC Input | Setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 66 | Page 3-AC | IR Split unit command, Out | 1 Byte | 17.1 scene number | CT |
| 66 | Page 3-AC | Power on/off, Out | 1 Bit | 1.1 switch | CT |
| 66 | Page 3-BgMusic | Play/Pause, In/Out | 1 Bit | 1.10 start/stop | CWTU |
| 66 | Page 3-RGB Dimming | Green dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 66 | Page 3-Air Quality | PM2.5, In | 2 Bytes | 7.1 pulses | CWTU |
| 66 | Page 3-Air Quality | PM2.5, In | 2 Bytes | 9.30 concentration (µg/m³) | CWTU |
| 66 | Page 3-Floor heating | Power on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 66 | Page 3-Ventilation | Power on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 66 | Page 3-Energy Meter 2 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 66 | Page 3-Energy Meter 2 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 66 | Page 3-Energy Meter 2 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 66 | Page 3-Energy Meter 2 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 66 | Page 3-Energy Meter 2 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 66 | Page 3-Energy Meter 2 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 66 | Page 3-Energy Meter 2 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 66 | Page 3-Energy Meter 2 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 66 | Page 3-Energy Meter 2 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 67 | Page 3-Icon 1 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 67 | Page 3-Icon 1 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 67 | Page 3-Icon 1 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 67 | Page 3-HVAC Input | Switch Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CWU |
| 67 | Page 3-AC | Status of Power, In | 1 Bit | 1.1 switch | CWTU |
| 67 | Page 3-BgMusic | Next song/Previous song, Out | 1 Bit | 1.7 step | CT |
| 67 | Page 3-RGB Dimming | Blue dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 67 | Page 3-Air Quality | PM10, In | 2 Bytes | 7.1 pulses | CWTU |
| 67 | Page 3-Air Quality | PM10, In | 2 Bytes | 9.30 concentration (µg/m³) | CWTU |
| 67 | Page 3-Floor heating | Heating on/off, In/Out | 1 Bit | 1.1 switch | CWTU |
| 67 | Page 3-Floor heating | Heating control value, Out | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 67 | Page 3-Ventilation | En./Dis. Heat Recovery, In | 1 Bit | 1.3 enable | CW |
| 67 | Page 3-Energy Meter 3 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 67 | Page 3-Energy Meter 3 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 67 | Page 3-Energy Meter 3 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 67 | Page 3-Energy Meter 3 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 67 | Page 3-Energy Meter 3 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 67 | Page 3-Energy Meter 3 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 67 | Page 3-Energy Meter 3 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 67 | Page 3-Energy Meter 3 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 67 | Page 3-Energy Meter 3 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 68 | Page 3-Icon 1 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 68 | Page 3-Icon 1 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 68 | Page 3-HVAC Input | Comfort mode | 1 Bit | 1.3 enable | CW |
| 68 | Page 3-HVAC Input | HVAC mode | 1 Byte | 20.102 HVAC mode | CW |
| 68 | Page 3-AC | Heat mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 68 | Page 3-AC | Control mode, Out | 1 Byte | 20.105 HVAC control mode | CT |
| 68 | Page 3-BgMusic | Volume+/Volume-, Out | 1 Bit | 1.7 step | CT |
| 68 | Page 3-RGB Dimming | White dimming value | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 68 | Page 3-Air Quality | Temperature, In | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 68 | Page 3-Floor heating | Setpoint, In/Out | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 68 | Page 3-Ventilation | Heat Recovery, In/Out | 1 Bit | 1.1 switch | CWTU |
| 68 | Page 3-Energy Meter 4 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 68 | Page 3-Energy Meter 4 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 68 | Page 3-Energy Meter 4 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 68 | Page 3-Energy Meter 4 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 68 | Page 3-Energy Meter 4 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 68 | Page 3-Energy Meter 4 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 68 | Page 3-Energy Meter 4 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 68 | Page 3-Energy Meter 4 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 68 | Page 3-Energy Meter 4 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 68 | Page 3-RGB Dimming | Brightness setting & status | 1 Byte | 5.1 percentage (0..100%) | CWT |
| 69 | Page 3-Icon 2 | Switch | 1 Bit | 1.1 switch | CT |
| 69 | Page 3-Icon 2 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 69 | Page 3-Icon 2 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 69 | Page 3-Icon 2 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 69 | Page 3-Icon 2 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 69 | Page 3-Icon 2 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 69 | Page 3-Icon 2 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 69 | Page 3-Icon 2 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 69 | Page 3-Icon 2 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 69 | Page 3-Icon 2 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 69 | Page 3-Icon 2 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 69 | Page 3-HVAC Input | Standby mode | 1 Bit | 1.3 enable | CW |
| 69 | Page 3-AC | Cool mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 69 | Page 3-AC | Status of control mode, In | 1 Byte | 20.105 HVAC control mode | CWTU |
| 69 | Page 3-BgMusic | Play mode, Out | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 69 | Page 3-RGB Dimming | Color Temperature setting & status | 2 Bytes | 7.600 absolute colour temperature (K) | CWT |
| 69 | Page 3-Air Quality | Humidity, In | 2 Bytes | 9.7 humidity (%) | CWTU |
| 69 | Page 3-Floor heating | En./Dis. timer, In | 1 Bit | 1.3 enable | CW |
| 69 | Page 3-Ventilation | Filter timer reset, In | 1 Bit | 1.15 reset | CW |
| 69 | Page 3-Energy Meter 5 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 69 | Page 3-Energy Meter 5 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 69 | Page 3-Energy Meter 5 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 69 | Page 3-Energy Meter 5 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 69 | Page 3-Energy Meter 5 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 69 | Page 3-Energy Meter 5 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 69 | Page 3-Energy Meter 5 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 69 | Page 3-Energy Meter 5 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 69 | Page 3-Energy Meter 5 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 70 | Page 3-Icon 2 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 70 | Page 3-Icon 2 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 70 | Page 3-Icon 2 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 70 | Page 3-Icon 2 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 70 | Page 3-Icon 2 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 70 | Page 3-Icon 2 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 70 | Page 3-Icon 2 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 70 | Page 3-Icon 2 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 70 | Page 3-Icon 2 | Stop | 1 Bit | 1.7 step | CT |
| 70 | Page 3-Icon 2 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 70 | Page 3-HVAC Input | Economy mode | 1 Bit | 1.3 enable | CW |
| 70 | Page 3-AC | Dry mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 70 | Page 3-BgMusic | Play mode status, In | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 70 | Page 3-Air Quality | VOC, In | 2 Bytes | 7.1 pulses | CWTU |
| 70 | Page 3-Air Quality | VOC, In | 2 Bytes | 9.30 concentration (µg/m³) | CWTU |
| 70 | Page 3-Floor heating | Scene, In | 1 Byte | 18.1 scene control | CW |
| 70 | Page 3-Ventilation | Filter timer counter, In/Out | 2 Bytes | 7.7 time (h) | CWTU |
| 70 | Page 3-Energy Meter 6 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 70 | Page 3-Energy Meter 6 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 70 | Page 3-Energy Meter 6 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 70 | Page 3-Energy Meter 6 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 70 | Page 3-Energy Meter 6 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 70 | Page 3-Energy Meter 6 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 70 | Page 3-Energy Meter 6 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 70 | Page 3-Energy Meter 6 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 70 | Page 3-Energy Meter 6 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 70 | Page 3-Air Quality | VOC, In | 2 Bytes | 9.8 parts/million (ppm) | CWTU |
| 71 | Page 3-Icon 2 | Switch status | 1 Bit | 1.1 switch | CWTU |
| 71 | Page 3-Icon 2 | Brightness status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 71 | Page 3-Icon 2 | Blind position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 71 | Page 3-HVAC Input | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 71 | Page 3-AC | Fan mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 71 | Page 3-BgMusic | Music source, Out | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 71 | Page 3-Air Quality | CO2, In | 2 Bytes | 9.8 parts/million (ppm) | CWTU |
| 71 | Page 3-Ventilation | Filter alarm, Out | 1 Bit | 1.5 alarm | CT |
| 71 | Page 3-Energy Meter 7 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 71 | Page 3-Energy Meter 7 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 71 | Page 3-Energy Meter 7 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 71 | Page 3-Energy Meter 7 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 71 | Page 3-Energy Meter 7 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 71 | Page 3-Energy Meter 7 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 71 | Page 3-Energy Meter 7 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 71 | Page 3-Energy Meter 7 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 71 | Page 3-Energy Meter 7 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 72 | Page 3-Icon 2 | Relative dimming | 4 Bit | 3.7 dimming control | CWT |
| 72 | Page 3-Icon 2 | Slat position/status | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 72 | Page 3-HVAC Input | Fan speed low | 1 Bit | 1.1 switch | CWU |
| 72 | Page 3-HVAC Input | Fan speed | 1 Byte | 5.1 percentage (0..100%) | CWU |
| 72 | Page 3-AC | Auto mode, In/Out | 1 Bit | 1.3 enable | CWTU |
| 72 | Page 3-BgMusic | Music source status, In | 1 Byte | 5.10 counter pulses (0..255) | CWTU |
| 72 | Page 3-Ventilation | Fan Speed No.1 1Bit, In/Out | 1 Bit | 1.1 switch | CWTU |
| 72 | Page 3-Ventilation | Fan speed, Out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 72 | Page 3-Energy Meter 8 | Current in mA (DPT 7.012) | 2 Bytes | 7.12 current (mA) | CWTU |
| 72 | Page 3-Energy Meter 8 | Current in mA (DPT 9.021) | 2 Bytes | 9.21 current (mA) | CWTU |
| 72 | Page 3-Energy Meter 8 | Current in A (DPT 14.019) | 4 Bytes | 14.19 electric current (A) | CWTU |
| 72 | Page 3-Energy Meter 8 | Voltage in mV (DPT 9.020) | 2 Bytes | 9.20 voltage (mV) | CWTU |
| 72 | Page 3-Energy Meter 8 | Voltage in V (DPT 14.027) | 4 Bytes | 14.27 electric potential (V) | CWTU |
| 72 | Page 3-Energy Meter 8 | Power in W (DPT 14.056) | 4 Bytes | 14.56 power (W) | CWTU |
| 72 | Page 3-Energy Meter 8 | Power in kW (DPT 9.024) | 2 Bytes | 9.24 power (kW) | CWTU |
| 72 | Page 3-Energy Meter 8 | Active energy in Wh (DPT 13.010) | 4 Bytes | 13.10 active energy (Wh) | CWTU |
| 72 | Page 3-Energy Meter 8 | Active energy in kWh (DPT 13.013) | 4 Bytes | 13.13 active energy (kWh) | CWTU |
| 72 | Page 3-Air Quality | Brightness, In | 2 Bytes | 9.4 lux (Lux) | CWTU |
| 72 | Page 3-Air Quality | Brightness, In | 2 Bytes | 7.13 brightness (lux) | CWTU |
| 73 | Page 3-Icon 3 | Switch | 1 Bit | 1.1 switch | CT |
| 73 | Page 3-Icon 3 | Send 1bit value | 1 Bit | 1.1 switch | CT |
| 73 | Page 3-Icon 3 | Send 2bit value | 2 Bit | 2.1 switch control | CT |
| 73 | Page 3-Icon 3 | Send 4bit value | 4 Bit | 3.7 dimming control | CT |
| 73 | Page 3-Icon 3 | Send 1byte unsigned value | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 73 | Page 3-Icon 3 | Send 1byte percent value | 1 Byte | 5.1 percentage (0..100%) | CT |
| 73 | Page 3-Icon 3 | Send 2byte unsigned value | 2 Bytes | 7.1 pulses | CT |
| 73 | Page 3-Icon 3 | Send 2byte signed value | 2 Bytes | 8.1 pulses difference | CT |
| 73 | Page 3-Icon 3 | Open/Close | 1 Bit | 1.9 open/close | CWT |
| 73 | Page 3-Icon 3 | Up/Down | 1 Bit | 1.8 up/down | CWT |
| 73 | Page 3-Icon 3 | Recall/storage scene No. | 1 Byte | 18.1 scene control | CWT |
| 73 | Page 3-HVAC Input | Fan speed medium | 1 Bit | 1.1 switch | CWU |
| 73 | Page 3-AC | Fan speed low, In/Out | 1 Bit | 1.1 switch | CWTU |
| 73 | Page 3-AC | Fan speed, Out | 1 Byte | 5.1 percentage (0..100%) | CT |
| 73 | Page 3-Ventilation | Fan Speed No.2 1Bit, In/Out | 1 Bit | 1.1 switch | CWTU |
| 73 | Page 3-Ventilation | Stauts of Fan speed, In | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 73 | Page 3-Air Quality | Windspeed, In | 2 Bytes | 9.5 speed (m/s) | CWTU |
| 74 | Page 3-Icon 3 | Brightness dimming | 1 Byte | 5.1 percentage (0..100%) | CT |
| 74 | Page 3-Icon 3 | Send 1bit value, long | 1 Bit | 1.1 switch | CT |
| 74 | Page 3-Icon 3 | Send 2bit value, long | 2 Bit | 2.1 switch control | CT |
| 74 | Page 3-Icon 3 | Send 4bit value, long | 4 Bit | 3.7 dimming control | CT |
| 74 | Page 3-Icon 3 | Send 1byte unsigned value, long | 1 Byte | 5.10 counter pulses (0..255) | CT |
| 74 | Page 3-Icon 3 | Send 1byte percent value, long | 1 Byte | 5.1 percentage (0..100%) | CT |
| 74 | Page 3-Icon 3 | Send 2byte unsigned value, long | 2 Bytes | 7.1 pulses | CT |
| 74 | Page 3-Icon 3 | Send 2byte signed value, long | 2 Bytes | 8.1 pulses difference | CT |
| 74 | Page 3-Icon 3 | Stop | 1 Bit | 1.7 step | CT |
| 74 | Page 3-Icon 3 | Stop/Slat adj. | 1 Bit | 1.7 step | CT |
| 74 | Page 3-HVAC Input | Fan speed high | 1 Bit | 1.1 switch | CWU |
| 74 | Page 3-AC | Fan speed medium, In/Out | 1 Bit | 1.1 switch | CWTU |
First 1000 of 6783 group objects shown. Download the .knxprod for the full list.
Parameters (595)
| Parameter | Type | Default |
|---|---|---|
| Interface Language | list | English |
| Language name | text | Input name |
| Send cycle of "In operation"telegram [1..240,0=inactive] | time | 0 |
| Date and Time can be changed via bus | list | Yes |
| Screen brightness can be changed via bus | list | Yes |
| Screen backgroud setting | list | Default |
| UI style for Multifunction page | list | Windows Tile |
| Status indication | list | Only Icon |
| Temperature display units | list | Celsius(°C) |
| Screen saver | list | Clock |
| Delay time for screen saver[5...255] | time | 10 |
| Delay time for turn off backlight[0...255] | unsignedInt 0…255 | 10 |
| Password function | list | Disable |
| Password 1 (only digit number allow) | text | 1234 |
| Status object read request after restart | list | Enable |
| Delay time from function page back to home page when no operation[0..255, 0=inactive] | time | 5 |
| Description for Home page function | text | Home page 1 |
| Home page navigation function | list | Enable |
| Page Layout | list | 4 |
| Navigation function 1 | list | Enable |
| Associated function | list | Link to Page 1 |
| Page icon | list | Default |
| Function page 1 | list | Enable |
| Function page 2 | list | Disable |
| Function page 3 | list | Disable |
| Function page 4 | list | Disable |
| Function page 5 | list | Disable |
| Function page 6 | list | Disable |
| Function page 7 | list | Disable |
| Function page 8 | list | Disable |
| Function page 9 | list | Disable |
| Function page 10 | list | Disable |
| Description for page function | text | Page 1 |
| Number of Function icon | list | 4 |
| Icon 1 | list | Enable |
| Function icon | list | Default |
| Description for Icon 1 | text | Icon 1 |
| Function of Icon 1 | list | Switch |
| Datatype of object | list | 1byte[0...255] |
| Output value when press | list | On |
| Output value when press | unsignedInt 0…3 | 1 |
| Output value when press | unsignedInt 0…15 | 0 |
| Output value when press | unsignedInt 0…255 | 127 |
| Output value when press | unsignedInt 0…100 | 100 |
| Output value when press | unsignedInt 0…65535 | 32768 |
| Output value when press | signedInt -32768…32767 | 0 |
| Long operation function | list | Disable |
| Output value when long operation | list | On |
| Output value when long operation | unsignedInt 0…3 | 1 |
| Output value when long operation | unsignedInt 0…15 | 0 |
| Output value when long operation | unsignedInt 0…255 | 127 |
| Output value when long operation | unsignedInt 0…100 | 100 |
| Output value when long operation | unsignedInt 0…65535 | 32768 |
| Output value when long operation | signedInt -32768…32767 | 0 |
| Output scene NO. | list | Scene No.1 |
| Storage scene via long operation | list | Disable |
| Send day/night status | list | No |
| Time for switch to night at: Hours [0..23] | time | 18 |
| Time for switch to night at: Minutes [0..59] | time | 0 |
| Time for switch to day at: Hours [0..23] | time | 6 |
| Time for switch to day at: Minutes [0..59] | time | 0 |
| Latitude | list | North |
| Latitude in degrees [0°..90°] | unsignedInt 0…90 | 39 |
| Latitude in minutes [0'..59'] | unsignedInt 0…59 | 56 |
| Longitude | list | East |
| Longitude in degrees [0°..180°] | unsignedInt 0…180 | 116 |
| Longitude in minutes [0'..59'] | unsignedInt 0…59 | 20 |
| Icon 2 | list | Enable |
| Description for Icon 2 | text | Icon 2 |
| Function of Icon 2 | list | Switch |
| Icon 3 | list | Enable |
| Description for Icon 3 | text | Icon 3 |
| Function of Icon 3 | list | Switch |
| Icon 4 | list | Enable |
| Description for Icon 4 | text | Icon 4 |
| Function of Icon 4 | list | Switch |
| Icon 5 | list | Enable |
| Description for Icon 5 | text | Icon 5 |
| Function of Icon 5 | list | Switch |
| Icon 6 | list | Enable |
| Description for Icon 6 | text | Icon 6 |
| Function of Icon 6 | list | Switch |
| Icon 7 | list | Enable |
| Description for Icon 7 | text | Icon 7 |
| Function of Icon 7 | list | Switch |
| Icon 8 | list | Enable |
| Description for Icon 8 | text | Icon 8 |
| Function of Icon 8 | list | Switch |
| Page function | list | Multifunction (Lighting/Blind/Scene/Value send) |
| Temperature reference from | list | Internal sensor |
| Time period for request external sensor[0...255] | time | 5 |
| Read external sensor after restart | list | Yes |
| Control value after temp. error[0..100%](If 2-point control, set value '0'=0, set value '>0'=1) | unsignedInt 0…100 | 0 |
| Control type of fan speed | list | Disable |
| Output value for Fan speed off | unsignedInt 0…255 | 0 |
| Output value for Fan speed low | unsignedInt 0…255 | 1 |
| Output value for Fan speed medium | unsignedInt 0…255 | 2 |
| Output value for Fan speed high | unsignedInt 0…255 | 3 |
| Output value for Fan speed auto | unsignedInt 0…255 | 4 |
| Status value for Fan speed off | unsignedInt 0…255 | 0 |
| Status value for Fan speed low | unsignedInt 0…255 | 1 |
| Status value for Fan speed medium | unsignedInt 0…255 | 2 |
| Status value for Fan speed high | unsignedInt 0…255 | 3 |
| Status value for Fan speed auto | unsignedInt 0…255 | 4 |
| HVAC control mode | list | Cooling |
| Heating/Cooling status after restart | list | As before power off or reset |
| HVAC control system | list | 4 pipes system |
| HVAC operation mode | list | Disable |
| Operating mode switchover | list | 1Byte |
| Operating mode status | list | 1Byte |
| Controller status after restart | list | Comfort mode |
| Extended comfort mode[0..255,0=inactive] | time | 0 |
| Base setpoint temperature | list | 20.0 |
| Type of Heat control | list | Switching on/off(use 2-point control) |
| Invert control value | list | No |
| PWM cycle time[1..255] | time | 15 |
| Lower Hysteresis[0..200] | unsignedInt 0…200 | 20 |
| Heating speed | list | Hot water heating(5K/150min) |
| Proportional range[10..100] | unsignedInt 10…100 | 40 |
| Reset time[0..255] | time | 150 |
| Send control value on change by [0..100%,0=inactive] | unsignedInt 0…100 | 4 |
| Cyclically send control value[0..255] | time | 0 |
| Type of Cool control | list | Switching on/off(use 2-point control) |
| Cooling speed | list | Cooling ceiling(5K/240min) |
| Type of Heat/Cool control | list | Switching on/off(use 2-point control) |
| Setpoint method for operating mode | list | Absolute |
| Reduced heating in standby mode[0..10] | unsignedInt 0…10 | 2 |
| Reduced heating in economy mode[0..10] | unsignedInt 0…10 | 4 |
| Actual Temp. threshold in frost protection[5..10] | unsignedInt 5…10 | 7 |
| Increased cooling in standby mode[0..10] | unsignedInt 0…10 | 2 |
| Increased cooling in economy mode[0..10] | unsignedInt 0…10 | 4 |
| Actual Temp. threshold in heat protection[30..40] | unsignedInt 30…40 | 35 |
| Setpoint temperature in comfort mode[5..40] | unsignedInt 5…40 | 21 |
| Setpoint temperature in standby mode[5..40] | unsignedInt 5…40 | 19 |
| Setpoint temperature in economy mode[5..40] | unsignedInt 5…40 | 17 |
| Setpoint temperature in frost protection[5..40] | unsignedInt 5…40 | 7 |
| Min. set temperature [5...40] | unsignedInt 5…40 | 5 |
| Max. set temperature [5...40] | unsignedInt 5…40 | 40 |
| Setpoint temperature in comfort mode[5..40] | unsignedInt 5…40 | 23 |
| Setpoint temperature in standby mode[5..40] | unsignedInt 5…40 | 25 |
| Setpoint temperature in economy mode[5..40] | unsignedInt 5…40 | 27 |
| Setpoint temperature in heat protection[5..40] | unsignedInt 5…40 | 35 |
| Control type | list | Gateway Integrate |
| Command No. for Power on [1..64,0=inactive] | unsignedInt 0…64 | 2 |
| Default mode for power on | list | Fan |
| Default setpoint for power on | list | 25°C |
| Default fan speed for power on | list | Auto |
| Command No. for Power off [1..64,0=inactive] | unsignedInt 0…64 | 1 |
| Default setpoint for Heat | list | 22°C |
| Default setpoint for Cool | list | 25°C |
| Command No. for Dry mode [1..64,0=inactive] | unsignedInt 0…64 | 3 |
| Command No. for Fan mode [1..64,0=inactive] | unsignedInt 0…64 | 4 |
| Command No. for Fan speed-auto [1..64,0=inactive] | unsignedInt 0…64 | 6 |
| Command No. for Fan speed-low [1..64,0=inactive] | unsignedInt 0…64 | 7 |
| Command No. for Fan speed-medium [1..64,0=inactive] | unsignedInt 0…64 | 8 |
| Command No. for Fan speed-high [1..64,0=inactive] | unsignedInt 0…64 | 9 |
| Command No. for setpoint 16°C [1..64,0=inactive] | unsignedInt 0…64 | 16 |
| Command No. for setpoint 17°C [1..64,0=inactive] | unsignedInt 0…64 | 17 |
| Command No. for setpoint 18°C [1..64,0=inactive] | unsignedInt 0…64 | 18 |
| Command No. for setpoint 19°C [1..64,0=inactive] | unsignedInt 0…64 | 19 |
| Command No. for setpoint 20°C [1..64,0=inactive] | unsignedInt 0…64 | 20 |
| Command No. for setpoint 21°C [1..64,0=inactive] | unsignedInt 0…64 | 21 |
| Command No. for setpoint 22°C [1..64,0=inactive] | unsignedInt 0…64 | 22 |
| Command No. for setpoint 23°C [1..64,0=inactive] | unsignedInt 0…64 | 23 |
| Command No. for setpoint 24°C [1..64,0=inactive] | unsignedInt 0…64 | 24 |
| Command No. for setpoint 25°C [1..64,0=inactive] | unsignedInt 0…64 | 25 |
| Command No. for setpoint 26°C [1..64,0=inactive] | unsignedInt 0…64 | 26 |
| Command No. for setpoint 27°C [1..64,0=inactive] | unsignedInt 0…64 | 27 |
| Command No. for setpoint 28°C [1..64,0=inactive] | unsignedInt 0…64 | 28 |
| Command No. for setpoint 29°C [1..64,0=inactive] | unsignedInt 0…64 | 29 |
| Command No. for setpoint 30°C [1..64,0=inactive] | unsignedInt 0…64 | 30 |
| Command No. for setpoint 31°C [1..64,0=inactive] | unsignedInt 0…64 | 31 |
| Command No. for setpoint 32°C [1..64,0=inactive] | unsignedInt 0…64 | 32 |
| Command No. for setpoint 16°C [1..64,0=inactive] | unsignedInt 0…64 | 33 |
| Command No. for setpoint 17°C [1..64,0=inactive] | unsignedInt 0…64 | 34 |
| Command No. for setpoint 18°C [1..64,0=inactive] | unsignedInt 0…64 | 35 |
| Command No. for setpoint 19°C [1..64,0=inactive] | unsignedInt 0…64 | 36 |
| Command No. for setpoint 20°C [1..64,0=inactive] | unsignedInt 0…64 | 37 |
| Command No. for setpoint 21°C [1..64,0=inactive] | unsignedInt 0…64 | 38 |
| Command No. for setpoint 22°C [1..64,0=inactive] | unsignedInt 0…64 | 39 |
| Command No. for setpoint 23°C [1..64,0=inactive] | unsignedInt 0…64 | 40 |
| Command No. for setpoint 24°C [1..64,0=inactive] | unsignedInt 0…64 | 41 |
| Command No. for setpoint 25°C [1..64,0=inactive] | unsignedInt 0…64 | 42 |
| Command No. for setpoint 26°C [1..64,0=inactive] | unsignedInt 0…64 | 43 |
| Command No. for setpoint 27°C [1..64,0=inactive] | unsignedInt 0…64 | 44 |
| Command No. for setpoint 28°C [1..64,0=inactive] | unsignedInt 0…64 | 45 |
| Command No. for setpoint 29°C [1..64,0=inactive] | unsignedInt 0…64 | 46 |
| Command No. for setpoint 30°C [1..64,0=inactive] | unsignedInt 0…64 | 47 |
| Command No. for setpoint 31°C [1..64,0=inactive] | unsignedInt 0…64 | 48 |
| Command No. for setpoint 32°C [1..64,0=inactive] | unsignedInt 0…64 | 49 |
| Data type of mode | list | 1byte |
| Output value for Heat | unsignedInt 0…255 | 1 |
| Output value for Cool | unsignedInt 0…255 | 2 |
| Output value for Dry | unsignedInt 0…255 | 3 |
| Output value for Fan | unsignedInt 0…255 | 4 |
| Status value for Heat | unsignedInt 0…255 | 1 |
| Status value for Cool | unsignedInt 0…255 | 2 |
| Status value for Dry | unsignedInt 0…255 | 3 |
| Status value for Fan | unsignedInt 0…255 | 4 |
| Data type of fan speed | list | 1byte |
| Object datatype of setpoint | list | Float value in °C(DPT_9.001) |
| Output value for Heat | list | 1 |
| Output value for Cool | list | 0 |
| Output value for Dry | list | 1 |
| Output value for Fan | list | 1 |
| Min. set temperature [16...32] | unsignedInt 16…32 | 16 |
| Max. set temperature [16...32] | unsignedInt 16…32 | 32 |
| Object value for Wind direction | list | Fixed=0 / Swing=1 |
| Power object telegram define | list | Off=0 / On=1 |
| Play/pause object telegram define | list | Pause=0 / Play=1 |
| Song select object telegram define | list | Previous=0 / Next=1 |
| Volume object telegram define | list | Volume-=0 / Volume+=1 |
| Output value for single cycle | unsignedInt 0…255 | 0 |
| Output value for random play | unsignedInt 0…255 | 1 |
| Output value for playlist cycle | unsignedInt 0…255 | 2 |
| Output value for play in order | unsignedInt 0…255 | 3 |
| Status value for single cycle | unsignedInt 0…255 | 0 |
| Status value for random play | unsignedInt 0…255 | 1 |
| Status value for playlist cycle | unsignedInt 0…255 | 2 |
| Status value for play in order | unsignedInt 0…255 | 3 |
| Output value for USB | unsignedInt 0…255 | 0 |
| Output value for SD | unsignedInt 0…255 | 1 |
| Output value for AUX | unsignedInt 0…255 | 2 |
| Output value for FM | unsignedInt 0…255 | 3 |
| Output value for BT | unsignedInt 0…255 | 4 |
| Status value for USB | unsignedInt 0…255 | 0 |
| Status value for SD | unsignedInt 0…255 | 1 |
| Status value for AUX | unsignedInt 0…255 | 2 |
| Status value for FM | unsignedInt 0…255 | 3 |
| Status value for BT | unsignedInt 0…255 | 4 |
| RGB strip type | list | RGB |
| Object type | list | 1x3byte |
| RGBW object type | list | 4x1byte |
| Items 1 function in List display | list | Temperature |
| Items 2 function in List display | list | Humidity |
| Items 3 function in List display | list | PM2.5 |
| Items 4 function in List display | list | VOC |
| Time period for request external sensor[5..255] | time | 10 |
| Power on/off status after download | list | Off |
| Power on/off status after power on | list | Off |
| Default set temperature[32..64] | unsignedInt 32…64 | 40 |
| Temperature control method | list | Heating on/off (2 point control) |
| Object value of Heating on/off | list | Heat on=1, Heat off=0 |
| Scene function | list | Disable |
| 1->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| Power on/off status | list | On |
| Set temperature[32..64] | unsignedInt 32…64 | 40 |
| 2->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 3->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 4->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 5->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| Heating timer function control via object | list | Disable |
| Timer 1 | list | Disable |
| Timer 2 | list | Disable |
| Timer 3 | list | Enable |
| Timer 4 | list | Disable |
| Timer 5 | list | Enable |
| Timer 6 | list | Disable |
| Timer 7 | list | Enable |
| Timer 8 | list | Enable |
| Execute in weekday | list | Monday-Friday |
| Execute at hours | time | 0 |
| Execute at minutes | time | 0 |
| Wind direction adjustment | list | Disable |
| Default fan speed after power on | list | Medium |
| Object value of fan speed off | list | No.1=0, No.2=0, No.3=0 |
| Object value of fan speed low | list | No.1=1, No.2=0, No.3=0 |
| Object value of fan speed medium | list | No.1=0, No.2=1, No.3=0 |
| Object value of fan speed high | list | No.1=0, No.2=0, No.3=1 |
| Delay between fan speed switch[0..100] | unsignedInt 0…100 | 10 |
| Fan level | list | Off |
| Heat Recovery | list | Off |
| Fan level | list | Low |
| Heat Recovery | list | On |
| Fan level | list | Medium |
| Fan level | list | High |
| Heat Recovery function | list | Disable=0/Enable=1 |
| Filter timer counter | list | Disable |
| Evaluation time[100.10000] | time | 1000 |
| Auto. operation function | list | Disable |
| Auto.operation on object value | list | 1=Auto/0=Cancel |
| Control value reference from | list | CO2 |
| Object datatype of PM2.5 | list | Value in ug/m3(DPT_7.001) |
| Object datatype of CO2 | list | Float value in ppm(DPT_9.008) |
| Period for request control value[0..255] | time | 2 |
| The speed status after control value error | list | Off |
| Threshold value OFF<->speed low[1..4000] | unsignedInt 1…4000 | 450 |
| Threshold value speed low<->medium[1..4000] | unsignedInt 1…4000 | 1000 |
| Threshold value speed medium<->high[1..4000] | unsignedInt 1…4000 | 2000 |
| Hysteresis value is threshold value in +/-[100..400] | unsignedInt 100…400 | 200 |
| Minimum time in fan speed[0..65535] | time | 10 |
| Threshold value OFF<->speed low[1..999] | unsignedInt 1…999 | 35 |
| Threshold value speed low<->medium[1..999] | unsignedInt 1…999 | 75 |
| Threshold value speed medium<->high[1..999] | unsignedInt 1…999 | 115 |
| Hysteresis value is threshold value in +/-[10..30] | unsignedInt 10…30 | 10 |
| Time function 1 | list | Enable |
| Time function 2 | list | Disable |
| Time function 3 | list | Disable |
| Time function 4 | list | Disable |
| Time function 5 | list | Disable |
| Time function 6 | list | Disable |
| Time function 7 | list | Disable |
| Time function 8 | list | Disable |
| Time function 9 | list | Disable |
| Time function 10 | list | Disable |
| Time function 11 | list | Disable |
| Time function 12 | list | Disable |
| Time function 13 | list | Disable |
| Time function 14 | list | Disable |
| Time function 15 | list | Disable |
| Time function 16 | list | Disable |
| DataType of time function | list | 1bit[On/Off] |
| Output value[On/Off] | list | Off |
| Output value[0..255] | unsignedInt 0…255 | 127 |
| Output scene No.[1..64] | list | Scene No.1 |
| Output value[0..65535] | unsignedInt 0…65535 | 32767 |
| Description for time function | text | Time 1 |
| Time disable function | list | Disable |
| Monday is | list | Disable |
| Tuesday is | list | Disable |
| Wednesday is | list | Disable |
| Thursday is | list | Disable |
| Friday is | list | Disable |
| Saturday is | list | Disable |
| Sunday is | list | Disable |
| Hours at | time | 0 |
| Minutes at | time | 0 |
| Event Group 1 Function | list | Enable |
| Event Group 2 Function | list | Disable |
| Event Group 3 Function | list | Disable |
| Event Group 4 Function | list | Disable |
| Event Group 5 Function | list | Disable |
| Event Group 6 Function | list | Disable |
| Event Group 7 Function | list | Disable |
| Event Group 8 Function | list | Disable |
| Object type of Output 1 | list | 1bit |
| 1->Trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| Object value of Output 1[0..1] | list | 0 |
| Object value of Output 1[0..255] | unsignedInt 0…255 | 127 |
| Object value of Output 1[0..65535] | unsignedInt 0…65535 | 32767 |
| Delay time for sending[0..255] | unsignedInt 0…255 | 0 |
| 2->Trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 3->Trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 4->Trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 5->Trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 6->Trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 7->Trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 8->Trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| Object type of Output 2 | list | 1bit |
| Object value of Output 2[0..1] | list | 0 |
| Object value of Output 2[0..255] | unsignedInt 0…255 | 127 |
| Object value of Output 2[0..65535] | unsignedInt 0…65535 | 32767 |
| Object type of Output 3 | list | 1bit |
| Object value of Output 3[0..1] | list | 0 |
| Object value of Output 3[0..255] | unsignedInt 0…255 | 127 |
| Object value of Output 3[0..65535] | unsignedInt 0…65535 | 32767 |
| Object type of Output 4 | list | 1bit |
| Object value of Output 4[0..1] | list | 0 |
| Object value of Output 4[0..255] | unsignedInt 0…255 | 127 |
| Object value of Output 4[0..65535] | unsignedInt 0…65535 | 32767 |
| Object type of Output 5 | list | 1bit |
| Object value of Output 5[0..1] | list | 0 |
| Object value of Output 5[0..255] | unsignedInt 0…255 | 127 |
| Object value of Output 5[0..65535] | unsignedInt 0…65535 | 32767 |
| Object type of Output 6 | list | 1bit |
| Object value of Output 6[0..1] | list | 0 |
| Object value of Output 6[0..255] | unsignedInt 0…255 | 127 |
| Object value of Output 6[0..65535] | unsignedInt 0…65535 | 32767 |
| Object type of Output 7 | list | 1bit |
| Object value of Output 7[0..1] | list | 0 |
| Object value of Output 7[0..255] | unsignedInt 0…255 | 127 |
| Object value of Output 7[0..65535] | unsignedInt 0…65535 | 32767 |
| Object type of Output 8 | list | 1bit |
| Object value of Output 8[0..1] | list | 0 |
| Object value of Output 8[0..255] | unsignedInt 0…255 | 127 |
| Object value of Output 8[0..65535] | unsignedInt 0…65535 | 32767 |
| 1st logic function | list | Disable |
| 2nd logic function | list | Disable |
| 3rd logic function | list | Disable |
| 4th logic function | list | Disable |
| 5th logic function | list | Disable |
| 6th logic function | list | Disable |
| 7th logic function | list | Disable |
| 8th logic function | list | Disable |
| Function of channel | list | AND |
| Input a | list | Disconnected |
| Default value | list | 0 |
| Input b | list | Disconnected |
| Input c | list | Disconnected |
| Input d | list | Disconnected |
| Input e | list | Disconnected |
| Input f | list | Disconnected |
| Input g | list | Disconnected |
| Input h | list | Disconnected |
| Result is inverted | list | No |
| Read input object value after power on | list | No |
| Threshold value data type | list | 1byte |
| Threshold value 0..15 | unsignedInt 0…15 | 8 |
| Threshold value 0..255 | unsignedInt 0…255 | 127 |
| Threshold value 0..65535 | unsignedInt 0…65535 | 32768 |
| Threshold value 0..4294967295 | unsignedInt 0…4294967295 | 65536 |
| If Object value<Threshold value | list | Do not send telegram |
| If Object value=Threshold value | list | Do not send telegram |
| If Object value!=Threshold value | list | Do not send telegram |
| If Object value>Threshold value | list | Do not send telegram |
| If Object value<=Threshold value | list | Do not send telegram |
| If Object value>=Threshold value | list | Do not send telegram |
| Output send when | list | Receiving a new telegram |
| Send delay time: Base | list | None |
| Factor: 1..255 | unsignedInt 1…255 | 1 |
| Format convert type | list | 1x1Byte-->8x1Bit |
| Object type of Input/Output | list | 1bit |
| Scene NO.of Gate after startup[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 1->Gate trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| Input A send on | list | Output A |
| Input B send on | list | Output B |
| Input C send on | list | Output C |
| Input D send on | list | Output D |
| 2->Gate trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 3->Gate trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 4->Gate trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 5->Gate trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 6->Gate trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 7->Gate trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 8->Gate trigger scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| Number of Energy metering | list | 4 |
| Description | text | Energy Meter 1 |
| Data type of display value | list | Value in mA (DPT 7.012) |
| Description | text | Energy Meter 2 |
| Description | text | Energy Meter 3 |
| Description | text | Energy Meter 4 |
| Description | text | Energy Meter 5 |
| Description | text | Energy Meter 6 |
| Description | text | Energy Meter 7 |
| Description | text | Energy Meter 8 |
| Time period for request meter value[5..255] | time | 10 |
| Function page 11 | list | Disable |
| Function page 12 | list | Disable |
| Function page 13 | list | Disable |
| Function page 14 | list | Disable |
| Function page 15 | list | Disable |
| Switching time move to night [-128..127] | signedInt -128…127 | 0 |
| Latitude longitude location setting | text | Beijing, China |
| Fan speed auto | list | Disable |
| Colorful strip function | list | Disable |
| Brightness level at day | list | Level 3 |
| Object datatype of PM10 | list | Value in ug/m3(DPT_7.001) |
| Object datatype of VOC | list | Value in ug/m3(DPT_7.001) |
| Description for time function | text | Time 2 |
| Description for time function | text | Time 3 |
| Description for time function | text | Time 4 |
| Description for time function | text | Time 5 |
| Description for time function | text | Time 6 |
| Description for time function | text | Time 7 |
| Description for time function | text | Time 8 |
| Description for time function | text | Time 9 |
| Description for time function | text | Time 10 |
| Description for time function | text | Time 11 |
| Description for time function | text | Time 12 |
| Description for time function | text | Time 13 |
| Description for time function | text | Time 14 |
| Description for time function | text | Time 15 |
| Description for time function | text | Time 16 |
| Upper Hysteresis[0..200] | unsignedInt 0…200 | 20 |
| Switching time move to day [-128..127] | signedInt -128…127 | 0 |
| Command value for position 1 | unsignedInt 0…255 | 1 |
| Command value for position 2 | unsignedInt 0…255 | 2 |
| Command value for position 3 | unsignedInt 0…255 | 3 |
| Command value for position 4 | unsignedInt 0…255 | 4 |
| Command value for position 5 | unsignedInt 0…255 | 5 |
| Status value for position 1 | unsignedInt 0…255 | 1 |
| Status value for position 2 | unsignedInt 0…255 | 2 |
| Status value for position 3 | unsignedInt 0…255 | 3 |
| Status value for position 4 | unsignedInt 0…255 | 4 |
| Status value for position 5 | unsignedInt 0…255 | 5 |
| Command No. for Auto mode [1..64,0=inactive] | unsignedInt 0…64 | 5 |
| Output value for Auto | unsignedInt 0…255 | 5 |
| Status value for Auto | unsignedInt 0…255 | 5 |
| Output value for Auto | list | 1 |
| Description for page function | text | Page 2 |
| Timer 1 | list | Enable |
| Description for page function | text | Page 3 |
| Description for page function | text | Page 4 |
| Description for page function | text | Page 5 |
| Description for page function | text | Page 6 |
| Description for page function | text | Page 7 |
| Description for page function | text | Page 8 |
| Description for page function | text | Page 9 |
| Description for page function | text | Page 10 |
| Description for page function | text | Page 11 |
| Description for page function | text | Page 12 |
| Description for page function | text | Page 13 |
| Description for page function | text | Page 14 |
| Description for page function | text | Page 15 |
| Internal sensor calibration | list | 0°C |
| Send actual Temp. when change by[1...20] | unsignedInt 1…20 | 2 |
| Cyclically send actual room Temp.[0..255] | time | 10 |
| Reply error of sensor measurement | list | Respond after change |
| Object value of error | list | 0=no error/1=error |
| Temperature display by | list | Internal sensor |
First 500 of 595 parameters shown. Download the .knxprod for the full list.
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| KNX Smart Touch V40/1.6 1.6 latest | $004E | ED36 | 2026-11-25 | 1.3 MB | Download |
About this file
This is the official ETS product database for the GVS CHTF-4.0/15.3.2x (x=0,1,2...) (1CHTFx20DB), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from GVS
- CHTF-5.0/15.3.2x (x=0,1,2...) 1CHTFx19DA
- CHTF-5.0/15.4.2x (x=0,1,2...) 1CHTFx20DA
- iKnx Smart Touch Z10 A-IS03, A-IS05, A-IS08
- KNX Smart Touch with voice control,3-gang CHTBV-3.0/6.2.xy
- KNX Smart Touch S3 CHTF-3.3/3.1.0x
- KNX Smart Touch S3 CHTF-3.3/3.2.xy
- KNX Smart Touch V40 Lite CHTF-4.0/15.4.2x (x=0,1,2...)
- KNX Smart Touch S4 CHTF-4.0/80.1.2x, CHTF-4.0/80.2.2x
- KNX Smart Touch V40s CHTF-4.0/9.5.2x
- KNX Smart Touch V50s CHTF-5.0/15.5.2x
- KNX Smart Touch with push button&Secure,3-gang CHTFB-3.0/6.S.xy
- KNX Smart Touch with push button,3-gang CHTFB-3.0/6.x.yz