KNX Database

GWA9801

GEWISS · Order number GWA9801 · Energy Management › Energy Meter Single Phase

Download .knxprod Energy Meter KNX for direct insertion - Single phase S 1.0 [SECURE] 1.0 · 210 KB

Product

ManufacturerGEWISS
Product nameGWA9801
Order numberGWA9801
Product textEnergy Meter KNX for direct insertion - Single phase
HardwareEnergy Meter KNX for direct insertion - Single phase
MediumTwisted Pair
Bus current (mA)8
Rail mountedYes
Width (mm)36
RegistrationCertified · 2020-12-16
Languagesen-US, de-DE, es-ES, it-IT
Catalog entryM-0019_H-A9801-0_HP-512C-10-16B3_CI-GWA9801-0
Fingerprint16B3
SHA-2560036a82a363a835258deb65251b9a254c85118e2a13ef1b4695f92937e24f780
First seen2026-11-25
Markets59 markets

Application program: Energy Meter KNX for direct insertion - Single phase S 1.0 [SECURE] 1.0

Application number$512C
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters526
Group objects325
Group objects (325)
NoNameFunctionSizeDPTFlags
1Consumed active energy primary counterValue in Wh4 Bytes13.10 active energy (Wh)CRT
1Consumed active energy primary counterValue in kWh4 Bytes13.13 active energy (kWh)CRT
2Overflow consumed active energy primary counterOverflow status1 Bit1.2 booleanCRT
3Reset consumed active energy primary counter1=Reset/0=No action1 Bit1.15 resetCW
4Consumed active energy differential counterValue in Wh4 Bytes13.10 active energy (Wh)CRT
4Consumed active energy differential counterValue in kWh4 Bytes13.13 active energy (kWh)CRT
5Trigger consumed active energy differential counter1=Start counter/0=Stop1 Bit1.10 start/stopCW
6Overflow consumed active energy differential counterOverflow status1 Bit1.2 booleanCRT
7Reset consumed active energy differential counter1=Reset/0=No action1 Bit1.15 resetCW
8Produced active energy primary counterValue in Wh4 Bytes13.10 active energy (Wh)CRT
8Produced active energy primary counterValue in kWh4 Bytes13.13 active energy (kWh)CRT
9Overflow produced active energy primary counterOverflow status1 Bit1.2 booleanCRT
10Reset produced active energy primary counter1=Reset/0=No action1 Bit1.15 resetCW
11Produced active energy differential counterValue in Wh4 Bytes13.10 active energy (Wh)CRT
11Produced active energy differential counterValue in kWh4 Bytes13.13 active energy (kWh)CRT
12Trigger produced active energy differential counter1=Start counter/0=Stop1 Bit1.10 start/stopCW
13Overflow produced active energy differential counterOverflow status1 Bit1.2 booleanCRT
14Reset produced active energy differential counter1=Reset/0=No action1 Bit1.15 resetCW
15Active power measuredValue in W4 Bytes14.56 power (W)CRT
16Reactive power measuredValue in VAR4 BytesDPT.14CRT
17Apparent power measuredValue in VA4 BytesDPT.14CRT
18Power factor measuredValue -1..+14 Bytes14.57 power factor (cos Φ)CRT
19Voltage RMS measuredValue in V2 Bytes9.20 voltage (mV)CRT
20Current RMS measuredValue in A2 Bytes9.21 current (mA)CRT
21Frequency measuredValue in Hertz [Hz]4 Bytes14.33 frequency (Hz)CRT
22Power threshold 1 enableEnable/Disable1 Bit1.2 booleanCW
23Power threshold 1 enable statusActive/Deactive1 Bit1.3 enableCRT
24Power threshold 1 value inputValue in [W]4 Bytes14.56 power (W)CW
24Power threshold 1 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
25Power threshold 1 actual valueValue in [W]4 Bytes14.56 power (W)CRT
26Over power threshold 1Value 1/01 Bit1.2 booleanCRT
27Period counter over power threshold 1 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
27Period counter over power threshold 1 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
27Period counter over power threshold 1 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
28Overflow period counter over power threshold 1Overflow state1 Bit1.2 booleanCRT
29Reset period counter over power threshold 11=Reset 0=No action1 Bit1.15 resetCW
30Number counter over power threshold 1 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
30Number counter over power threshold 1 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
31Overflow number counter power limit threshold 1Overflow state1 Bit1.2 booleanCRT
32Reset number counter over power threshold 11=Reset 0=No action1 Bit1.15 resetCW
33Power threshold 2 enableEnable/Disable1 Bit1.2 booleanCW
34Power threshold 2 enable statusActive/Deactive1 Bit1.3 enableCRT
35Power threshold 2 value inputValue in [W]4 Bytes14.56 power (W)CW
35Power threshold 2 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
36Power threshold 2 actual valueValue in [W]4 Bytes14.56 power (W)CRT
37Over power threshold 2Value 1/01 Bit1.2 booleanCRT
38Period counter over power threshold 2 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
38Period counter over power threshold 2 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
38Period counter over power threshold 2 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
39Overflow period counter over power threshold 2Overflow state1 Bit1.2 booleanCRT
40Reset period counter over power threshold 21=Reset 0=No action1 Bit1.15 resetCW
41Number counter over power threshold 2 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
41Number counter over power threshold 2 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
42Overflow number counter power limit threshold 2Overflow state1 Bit1.2 booleanCRT
43Reset number counter over power threshold 21=Reset 0=No action1 Bit1.15 resetCW
44Power threshold 3 enableEnable/Disable1 Bit1.2 booleanCW
45Power threshold 3 enable statusActive/Deactive1 Bit1.3 enableCRT
46Power threshold 3 value inputValue in [W]4 Bytes14.56 power (W)CW
46Power threshold 3 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
47Power threshold 3 actual valueValue in [W]4 Bytes14.56 power (W)CRT
48Over power threshold 3Value 1/01 Bit1.2 booleanCRT
49Period counter over power threshold 3 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
49Period counter over power threshold 3 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
49Period counter over power threshold 3 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
50Overflow period counter over power threshold 3Overflow state1 Bit1.2 booleanCRT
51Reset period counter over power threshold 31=Reset 0=No action1 Bit1.15 resetCW
52Number counter over power threshold 3 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
52Number counter over power threshold 3 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
53Overflow number counter power limit threshold 3Overflow state1 Bit1.2 booleanCRT
54Reset number counter over power threshold 31=Reset 0=No action1 Bit1.15 resetCW
55Power threshold 4 enableEnable/Disable1 Bit1.2 booleanCW
56Power threshold 4 enable statusActive/Deactive1 Bit1.3 enableCRT
57Power threshold 4 value inputValue in [W]4 Bytes14.56 power (W)CW
57Power threshold 4 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
58Power threshold 4 actual valueValue in [W]4 Bytes14.56 power (W)CRT
59Over power threshold 4Value 1/01 Bit1.2 booleanCRT
60Period counter over power threshold 4 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
60Period counter over power threshold 4 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
60Period counter over power threshold 4 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
61Overflow period counter over power threshold 4Overflow state1 Bit1.2 booleanCRT
62Reset period counter over power threshold 41=Reset 0=No action1 Bit1.15 resetCW
63Number counter over power threshold 4 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
63Number counter over power threshold 4 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
64Overflow number counter power limit threshold 4Overflow state1 Bit1.2 booleanCRT
65Reset number counter over power threshold 41=Reset 0=No action1 Bit1.15 resetCW
66Power threshold 5 enableEnable/Disable1 Bit1.2 booleanCW
67Power threshold 5 enable statusActive/Deactive1 Bit1.3 enableCRT
68Power threshold 5 value inputValue in [W]4 Bytes14.56 power (W)CW
68Power threshold 5 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
69Power threshold 5 actual valueValue in [W]4 Bytes14.56 power (W)CRT
70Over power threshold 5Value 1/01 Bit1.2 booleanCRT
71Period counter over power threshold 5 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
71Period counter over power threshold 5 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
71Period counter over power threshold 5 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
72Overflow period counter over power threshold 5Overflow state1 Bit1.2 booleanCRT
73Reset period counter over power threshold 51=Reset 0=No action1 Bit1.15 resetCW
74Number counter over power threshold 5 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
74Number counter over power threshold 5 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
75Overflow number counter power limit threshold 5Overflow state1 Bit1.2 booleanCRT
76Reset number counter over power threshold 51=Reset 0=No action1 Bit1.15 resetCW
77Power threshold 6 enableEnable/Disable1 Bit1.2 booleanCW
78Power threshold 6 enable statusActive/Deactive1 Bit1.3 enableCRT
79Power threshold 6 value inputValue in [W]4 Bytes14.56 power (W)CW
79Power threshold 6 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
80Power threshold 6 actual valueValue in [W]4 Bytes14.56 power (W)CRT
81Over power threshold 6Value 1/01 Bit1.2 booleanCRT
82Period counter over power threshold 6 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
82Period counter over power threshold 6 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
82Period counter over power threshold 6 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
83Overflow period counter over power threshold 6Overflow state1 Bit1.2 booleanCRT
84Reset period counter over power threshold 61=Reset 0=No action1 Bit1.15 resetCW
85Number counter over power threshold 6 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
85Number counter over power threshold 6 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
86Overflow number counter power limit threshold 6Overflow state1 Bit1.2 booleanCRT
87Reset number counter over power threshold 61=Reset 0=No action1 Bit1.15 resetCW
88Power threshold 7 enableEnable/Disable1 Bit1.2 booleanCW
89Power threshold 7 enable statusActive/Deactive1 Bit1.3 enableCRT
90Power threshold 7 value inputValue in [W]4 Bytes14.56 power (W)CW
90Power threshold 7 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
91Power threshold 7 actual valueValue in [W]4 Bytes14.56 power (W)CRT
92Over power threshold 7Value 1/01 Bit1.2 booleanCRT
93Period counter over power threshold 7 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
93Period counter over power threshold 7 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
93Period counter over power threshold 7 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
94Overflow period counter over power threshold 7Overflow state1 Bit1.2 booleanCRT
95Reset period counter over power threshold 71=Reset 0=No action1 Bit1.15 resetCW
96Number counter over power threshold 7 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
96Number counter over power threshold 7 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
97Overflow number counter power limit threshold 7Overflow state1 Bit1.2 booleanCRT
98Reset number counter over power threshold 71=Reset 0=No action1 Bit1.15 resetCW
99Power threshold 8 enableEnable/Disable1 Bit1.2 booleanCW
100Power threshold 8 enable statusActive/Deactive1 Bit1.3 enableCRT
101Power threshold 8 value inputValue in [W]4 Bytes14.56 power (W)CW
101Power threshold 8 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
102Power threshold 8 actual valueValue in [W]4 Bytes14.56 power (W)CRT
103Over power threshold 8Value 1/01 Bit1.2 booleanCRT
104Period counter over power threshold 8 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
104Period counter over power threshold 8 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
104Period counter over power threshold 8 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
105Overflow period counter over power threshold 8Overflow state1 Bit1.2 booleanCRT
106Reset period counter over power threshold 81=Reset 0=No action1 Bit1.15 resetCW
107Number counter over power threshold 8 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
107Number counter over power threshold 8 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
108Overflow number counter power limit threshold 8Overflow state1 Bit1.2 booleanCRT
109Reset number counter over power threshold 81=Reset 0=No action1 Bit1.15 resetCW
110Power threshold 9 enableEnable/Disable1 Bit1.2 booleanCW
111Power threshold 9 enable statusActive/Deactive1 Bit1.3 enableCRT
112Power threshold 9 value inputValue in [W]4 Bytes14.56 power (W)CW
112Power threshold 9 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
113Power threshold 9 actual valueValue in [W]4 Bytes14.56 power (W)CRT
114Over power threshold 9Value 1/01 Bit1.2 booleanCRT
115Period counter over power threshold 9 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
115Period counter over power threshold 9 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
115Period counter over power threshold 9 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
116Overflow period counter over power threshold 9Overflow state1 Bit1.2 booleanCRT
117Reset period counter over power threshold 91=Reset 0=No action1 Bit1.15 resetCW
118Number counter over power threshold 9 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
118Number counter over power threshold 9 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
119Overflow number counter power limit threshold 9Overflow state1 Bit1.2 booleanCRT
120Reset number counter over power threshold 91=Reset 0=No action1 Bit1.15 resetCW
121Power threshold 10 enableEnable/Disable1 Bit1.2 booleanCW
122Power threshold 10 enable statusActive/Deactive1 Bit1.3 enableCRT
123Power threshold 10 value inputValue in [W]4 Bytes14.56 power (W)CW
123Power threshold 10 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
124Power threshold 10 actual valueValue in [W]4 Bytes14.56 power (W)CRT
125Over power threshold 10Value 1/01 Bit1.2 booleanCRT
126Period counter over power threshold 10 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
126Period counter over power threshold 10 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
126Period counter over power threshold 10 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
127Overflow period counter over power threshold 10Overflow state1 Bit1.2 booleanCRT
128Reset period counter over power threshold 101=Reset 0=No action1 Bit1.15 resetCW
129Number counter over power threshold 10 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
129Number counter over power threshold 10 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
130Overflow number counter power limit threshold 10Overflow state1 Bit1.2 booleanCRT
131Reset number counter over power threshold 101=Reset 0=No action1 Bit1.15 resetCW
132Power threshold 11 enableEnable/Disable1 Bit1.2 booleanCW
133Power threshold 11 enable statusActive/Deactive1 Bit1.3 enableCRT
134Power threshold 11 value inputValue in [W]4 Bytes14.56 power (W)CW
134Power threshold 11 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
135Power threshold 11 actual valueValue in [W]4 Bytes14.56 power (W)CRT
136Over power threshold 11Value 1/01 Bit1.2 booleanCRT
137Period counter over power threshold 11 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
137Period counter over power threshold 11 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
137Period counter over power threshold 11 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
138Overflow period counter over power threshold 11Overflow state1 Bit1.2 booleanCRT
139Reset period counter over power threshold 111=Reset 0=No action1 Bit1.15 resetCW
140Number counter over power threshold 11 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
140Number counter over power threshold 11 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
141Overflow number counter power limit threshold 11Overflow state1 Bit1.2 booleanCRT
142Reset number counter over power threshold 111=Reset 0=No action1 Bit1.15 resetCW
143Power threshold 12 enableEnable/Disable1 Bit1.2 booleanCW
144Power threshold 12 enable statusActive/Deactive1 Bit1.3 enableCRT
145Power threshold 12 value inputValue in [W]4 Bytes14.56 power (W)CW
145Power threshold 12 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
146Power threshold 12 actual valueValue in [W]4 Bytes14.56 power (W)CRT
147Over power threshold 12Value 1/01 Bit1.2 booleanCRT
148Period counter over power threshold 12 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
148Period counter over power threshold 12 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
148Period counter over power threshold 12 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
149Overflow period counter over power threshold 12Overflow state1 Bit1.2 booleanCRT
150Reset period counter over power threshold 121=Reset 0=No action1 Bit1.15 resetCW
151Number counter over power threshold 12 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
151Number counter over power threshold 12 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
152Overflow number counter power limit threshold 12Overflow state1 Bit1.2 booleanCRT
153Reset number counter over power threshold 121=Reset 0=No action1 Bit1.15 resetCW
154Power threshold 13 enableEnable/Disable1 Bit1.2 booleanCW
155Power threshold 13 enable statusActive/Deactive1 Bit1.3 enableCRT
156Power threshold 13 value inputValue in [W]4 Bytes14.56 power (W)CW
156Power threshold 13 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
157Power threshold 13 actual valueValue in [W]4 Bytes14.56 power (W)CRT
158Over power threshold 13Value 1/01 Bit1.2 booleanCRT
159Period counter over power threshold 13 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
159Period counter over power threshold 13 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
159Period counter over power threshold 13 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
160Overflow period counter over power threshold 13Overflow state1 Bit1.2 booleanCRT
161Reset period counter over power threshold 131=Reset 0=No action1 Bit1.15 resetCW
162Number counter over power threshold 13 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
162Number counter over power threshold 13 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
163Overflow number counter power limit threshold 13Overflow state1 Bit1.2 booleanCRT
164Reset number counter over power threshold 131=Reset 0=No action1 Bit1.15 resetCW
165Power threshold 14 enableEnable/Disable1 Bit1.2 booleanCW
166Power threshold 14 enable statusActive/Deactive1 Bit1.3 enableCRT
167Power threshold 14 value inputValue in [W]4 Bytes14.56 power (W)CW
167Power threshold 14 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
168Power threshold 14 actual valueValue in [W]4 Bytes14.56 power (W)CRT
169Over power threshold 14Value 1/01 Bit1.2 booleanCRT
170Period counter over power threshold 14 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
170Period counter over power threshold 14 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
170Period counter over power threshold 14 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
171Overflow period counter over power threshold 14Overflow state1 Bit1.2 booleanCRT
172Reset period counter over power threshold 141=Reset 0=No action1 Bit1.15 resetCW
173Number counter over power threshold 14 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
173Number counter over power threshold 14 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
174Overflow number counter power limit threshold 14Overflow state1 Bit1.2 booleanCRT
175Reset number counter over power threshold 141=Reset 0=No action1 Bit1.15 resetCW
176Power threshold 15 enableEnable/Disable1 Bit1.2 booleanCW
177Power threshold 15 enable statusActive/Deactive1 Bit1.3 enableCRT
178Power threshold 15 value inputValue in [W]4 Bytes14.56 power (W)CW
178Power threshold 15 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
179Power threshold 15 actual valueValue in [W]4 Bytes14.56 power (W)CRT
180Over power threshold 15Value 1/01 Bit1.2 booleanCRT
181Period counter over power threshold 15 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
181Period counter over power threshold 15 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
181Period counter over power threshold 15 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
182Overflow period counter over power threshold 15Overflow state1 Bit1.2 booleanCRT
183Reset period counter over power threshold 151=Reset 0=No action1 Bit1.15 resetCW
184Number counter over power threshold 15 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
184Number counter over power threshold 15 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
185Overflow number counter power limit threshold 15Overflow state1 Bit1.2 booleanCRT
186Reset number counter over power threshold 151=Reset 0=No action1 Bit1.15 resetCW
187Power threshold 16 enableEnable/Disable1 Bit1.2 booleanCW
188Power threshold 16 enable statusActive/Deactive1 Bit1.3 enableCRT
189Power threshold 16 value inputValue in [W]4 Bytes14.56 power (W)CW
189Power threshold 16 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
190Power threshold 16 actual valueValue in [W]4 Bytes14.56 power (W)CRT
191Over power threshold 16Value 1/01 Bit1.2 booleanCRT
192Period counter over power threshold 16 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
192Period counter over power threshold 16 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
192Period counter over power threshold 16 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
193Overflow period counter over power threshold 16Overflow state1 Bit1.2 booleanCRT
194Reset period counter over power threshold 161=Reset 0=No action1 Bit1.15 resetCW
195Number counter over power threshold 16 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
195Number counter over power threshold 16 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
196Overflow number counter power limit threshold 16Overflow state1 Bit1.2 booleanCRT
197Reset number counter over power threshold 161=Reset 0=No action1 Bit1.15 resetCW
198Power threshold 17 enableEnable/Disable1 Bit1.2 booleanCW
199Power threshold 17 enable statusActive/Deactive1 Bit1.3 enableCRT
200Power threshold 17 value inputValue in [W]4 Bytes14.56 power (W)CW
200Power threshold 17 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
201Power threshold 17 actual valueValue in [W]4 Bytes14.56 power (W)CRT
202Over power threshold 17Value 1/01 Bit1.2 booleanCRT
203Period counter over power threshold 17 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
203Period counter over power threshold 17 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
203Period counter over power threshold 17 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
204Overflow period counter over power threshold 17Overflow state1 Bit1.2 booleanCRT
205Reset period counter over power threshold 171=Reset 0=No action1 Bit1.15 resetCW
206Number counter over power threshold 17 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
206Number counter over power threshold 17 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
207Overflow number counter power limit threshold 17Overflow state1 Bit1.2 booleanCRT
208Reset number counter over power threshold 171=Reset 0=No action1 Bit1.15 resetCW
209Power threshold 18 enableEnable/Disable1 Bit1.2 booleanCW
210Power threshold 18 enable statusActive/Deactive1 Bit1.3 enableCRT
211Power threshold 18 value inputValue in [W]4 Bytes14.56 power (W)CW
211Power threshold 18 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
212Power threshold 18 actual valueValue in [W]4 Bytes14.56 power (W)CRT
213Over power threshold 18Value 1/01 Bit1.2 booleanCRT
214Period counter over power threshold 18 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
214Period counter over power threshold 18 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
214Period counter over power threshold 18 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
215Overflow period counter over power threshold 18Overflow state1 Bit1.2 booleanCRT
216Reset period counter over power threshold 181=Reset 0=No action1 Bit1.15 resetCW
217Number counter over power threshold 18 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
217Number counter over power threshold 18 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
218Overflow number counter power limit threshold 18Overflow state1 Bit1.2 booleanCRT
219Reset number counter over power threshold 181=Reset 0=No action1 Bit1.15 resetCW
220Power threshold 19 enableEnable/Disable1 Bit1.2 booleanCW
221Power threshold 19 enable statusActive/Deactive1 Bit1.3 enableCRT
222Power threshold 19 value inputValue in [W]4 Bytes14.56 power (W)CW
222Power threshold 19 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
223Power threshold 19 actual valueValue in [W]4 Bytes14.56 power (W)CRT
224Over power threshold 19Value 1/01 Bit1.2 booleanCRT
225Period counter over power threshold 19 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
225Period counter over power threshold 19 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
225Period counter over power threshold 19 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
226Overflow period counter over power threshold 19Overflow state1 Bit1.2 booleanCRT
227Reset period counter over power threshold 191=Reset 0=No action1 Bit1.15 resetCW
228Number counter over power threshold 19 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
228Number counter over power threshold 19 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
229Overflow number counter power limit threshold 19Overflow state1 Bit1.2 booleanCRT
230Reset number counter over power threshold 191=Reset 0=No action1 Bit1.15 resetCW
231Power threshold 20 enableEnable/Disable1 Bit1.2 booleanCW
232Power threshold 20 enable statusActive/Deactive1 Bit1.3 enableCRT
233Power threshold 20 value inputValue in [W]4 Bytes14.56 power (W)CW
233Power threshold 20 regulation1=Increment/0=Decrement1 Bit1.7 stepCW
234Power threshold 20 actual valueValue in [W]4 Bytes14.56 power (W)CRT
235Over power threshold 20Value 1/01 Bit1.2 booleanCRT
236Period counter over power threshold 20 (s)Value 0.. 2147483647[s]4 Bytes13.100 time lag (s)CRT
236Period counter over power threshold 20 (min)Value 0 .. 65535[min]2 Bytes7.6 time (min)CRT
236Period counter over power threshold 20 (h)Value 0 .. 65535[h]2 Bytes7.7 time (h)CRT
237Overflow period counter over power threshold 20Overflow state1 Bit1.2 booleanCRT
238Reset period counter over power threshold 201=Reset 0=No action1 Bit1.15 resetCW
239Number counter over power threshold 20 (4 byte)Value 0 .. 42949672954 Bytes12.1 counter pulses (unsigned)CRT
239Number counter over power threshold 20 (2 byte)Value 0 .. 655352 Bytes7.1 pulsesCRT
240Overflow number counter power limit threshold 20Overflow state1 Bit1.2 booleanCRT
241Reset number counter over power threshold 201=Reset 0=No action1 Bit1.15 resetCW
Parameters (65)
ParameterTypeDefault
PID_HARDWARE_TYPE_PARAMETERlist
PARAM_DO_MASTER_RESETlistAPP_FIRST_BOOT
Delay time from power on and first transmissionlist11..21 seconds (depends on physical address)
Electric measures sending at bus restoringlistenable
Reset consumed and produced energy primary counters from local menulistenable
Consumed active energy counterlistdisabled
Consumed energy counter formatlistWh
Consumed energy primary counter init valueunsignedInt 0…21474836470
Consumed energy primary counter sending conditionlistsending on variation
Consumed energy primary counter variation for sendinglist50 Wh
Consumed energy primary counter variation for sendinglist1000 Wh (1 kWh)
Consumed energy primary counter sending period (minutes)unsignedInt 1…25515
Consumed energy differential counter overflow valueunsignedInt 0…21474836472147483647
Consumed energy differential counter sending conditionlistsending on variation
Consumed energy differential counter variation for sendinglist50 Wh
Consumed energy differential counter variation for sendinglist1000 Wh (1 kWh)
Consumed energy differential counter sending period (minutes)unsignedInt 1…25515
Start/stop consumed energy differential counter from buslistdisable
Reinitialize consumed energy counterslistno
Produced active energy counterlistdisabled
Produced energy counter formatlistWh
Produced energy primary counter init valueunsignedInt 0…21474836470
Produced energy primary counter sending conditionlistsending on variation
Produced primary counter energy variation for sendinglist50 Wh
Produced primary counter energy variation for sendinglist1000 Wh (1 kWh)
Produced energy primary counter sending period (minutes)unsignedInt 1…25515
Produced energy differential counter overflow valueunsignedInt 0…21474836472147483647
Produced energy differential counter sending conditionlistsending on variation
Produced energy differential counter variation for sendinglist50 Wh
Produced energy differential counter variation for sendinglist1000 Wh (1 kWh)
Produced energy differential counter sending period (minutes)unsignedInt 1…25515
Start/stop produced energy differential counter from buslistdisable
Reinitialize produced energy counterslistno
Power value sendinglistsending on variation
Power variation for sendinglist50 (W/VA/VAR)
Power factor value sendinglistsending on variation
Power factor variation for sendinglist0,2
Voltage RMS value sendinglistsending on variation
Voltage RMS variation for sendinglist5 Volt
Current RMS value sendinglistsending on variation
Current RMS variation for sendinglist0,5 Ampere
Frequency value sendinglistsending on variation
Frequency variation for sendinglist5 Hertz
Power thresholds number to activatelistnone
Threshold activation valuelistvalue "1"
Power threshold initial value (W)signedInt -8000…8000800
Power threshold hysteresis (W)unsignedInt 1…8000100
Changing threshold settinglistabsolute value
Regulation step of threshold by busunsignedInt 1…250100
Signalling of the overcoming power thresholdlistsending on variation
- At overcoming power thresholdlistsend "1"
- At coming back under power thresholdlistsend "0"
- Period of signalling sending (minutes)unsignedInt 1…25515
Over power threshold period counter formatlist4 byte(seconds)
Overflow valueunsignedInt 0…21474836472147483647
Overflow valueunsignedInt 0…6553565535
Period counter sending conditionlistsending on variation
Period counter variation for sendingunsignedInt 1…10010
Counter sending period (minutes)unsignedInt 1…25515
Over power threshold number counter formatlist4 byte unsigned
Overflow valueunsignedInt 0…42949672954294967295
Number counter sending conditionlistsending on variation
Number counter variation for sendingunsignedInt 1…10010
Power threshold function at downloadlistactive
Power threshold function at bus restoringlistas before voltage dropping

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Energy Meter KNX for direct insertion - Single phase S 1.0 [SECURE] 1.0 latest$512C16B32026-11-25210 KBDownload

About this file

This is the official ETS product database for the GEWISS GWA9801 (GWA9801), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from GEWISS

All GEWISS products