GWA9303
GEWISS · Order number GWA9303 · Lighting Control/Regulation › Dimmer 2 outputs
Download .knxprod KNX UNIVERSAL DIMMER 2-CH X 400W - DIN RAIL 1.2 · 200 KB
Product
| Manufacturer | GEWISS |
|---|---|
| Product name | GWA9303 |
| Order number | GWA9303 |
| Product text | KNX UNIVERSAL DIMMER 2-CH X 400W - DIN RAIL |
| Hardware | KNX UNIVERSAL DIMMER 2-CH X 400W - DIN RAIL |
| Medium | Twisted Pair |
| Bus current (mA) | 4 |
| Rail mounted | Yes |
| Width (mm) | 70 |
| Registration | Certified · 2020-04-01 |
| Languages | de-DE, en-US, es-ES, it-IT, fr-FR, nl-NL |
| Catalog entry | M-0019_H-4940270-1-O0048_HP-4947-12-F5BA-O0048_CI-GWA9303-1 |
| Fingerprint | F5BA |
| SHA-256 | e9f04abaeb555f8cef6be33e2cf8d9e7d247961309a67e17b736567ea278626c |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: KNX UNIVERSAL DIMMER 2-CH X 400W - DIN RAIL 1.2
| Application number | $4947 |
|---|---|
| Version | 1.2 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Minimum ETS version | 4.0 |
| Parameters | 736 |
| Group objects | 109 |
Group objects (109)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Channel CH1 | Switching ON/OFF | 1 Bit | CRWU | |
| 1 | Channel CH1 | Brighter/darker | 4 Bit | CRWU | |
| 2 | Channel CH1 | Dimming value | 1 Byte | CWU | |
| 3 | Channel CH1 | Soft switching | 1 Bit | CRWU | |
| 4 | Channel CH1 | Lock | 1 Bit | CRWU | |
| 5 | Channel CH1 | Call up/save scenes | 1 Byte | CRWU | |
| 6 | Channel CH1 | Lock scenes = 1 | 1 Bit | CRW | |
| 6 | Channel CH1 | Enable scenes = 1 | 1 Bit | CRW | |
| 7 | Channel CH1 | Force = 1 | 1 Bit | CRWU | |
| 7 | Channel CH1 | Force = 0 | 1 Bit | CRWU | |
| 7 | Channel CH1 | Dimming value with forced op | 1 Byte | CRWU | |
| 7 | Channel CH1 | Forced mode | 2 Bit | CRWU | |
| 8 | Channel CH1 | Dimming value limit | 1 Byte | CRWU | |
| 9 | Channel CH1 | Feedback On/Off | 1 Bit | CRTU | |
| 10 | Channel CH1 | Feedback in % | 1 Byte | CRTU | |
| 11 | Channel CH1 | Time to next service | 2 Bytes | CRWTU | |
| 11 | Channel CH1 | Operating hours feedback | 2 Bytes | CRWT | |
| 12 | Channel CH1 | Service required | 1 Bit | CRTU | |
| 13 | Channel CH1 | Reset service | 1 Bit | CRW | |
| 13 | Channel CH1 | Reset operating hours | 1 Bit | CRW | |
| 14 | Channel CH1 | General error message | 1 Bit | CRTU | |
| 15 | Channel CH1 | Short circuit message | 1 Bit | CRTU | |
| 16 | Channel CH1 | Excess temperature message | 1 Bit | CRTU | |
| 17 | Channel CH1 | Mains power failure | 1 Bit | CRTU | |
| 18 | Channel CH1 | Load type message (RC/L) | 1 Bit | CRTU | |
| 30 | Channel CH2 | Switching ON/OFF | 1 Bit | CRWU | |
| 31 | Channel CH2 | Brighter/darker | 4 Bit | CRWU | |
| 32 | Channel CH2 | Dimming value | 1 Byte | CWU | |
| 33 | Channel CH2 | Soft switching | 1 Bit | CRWU | |
| 34 | Channel CH2 | Lock | 1 Bit | CRWU | |
| 35 | Channel CH2 | Call up/save scenes | 1 Byte | CRWU | |
| 36 | Channel CH2 | Enable scenes = 1 | 1 Bit | CRW | |
| 36 | Channel CH2 | Lock scenes = 1 | 1 Bit | CRW | |
| 37 | Channel CH2 | Force = 0 | 1 Bit | CRWU | |
| 37 | Channel CH2 | Force = 1 | 1 Bit | CRWU | |
| 37 | Channel CH2 | Dimming value with forced op | 1 Byte | CRWU | |
| 37 | Channel CH2 | Forced mode | 2 Bit | CRWU | |
| 38 | Channel CH2 | Dimming value limit | 1 Byte | CRWU | |
| 39 | Channel CH2 | Feedback On/Off | 1 Bit | CRTU | |
| 40 | Channel CH2 | Feedback in % | 1 Byte | CRTU | |
| 41 | Channel CH2 | Time to next service | 2 Bytes | CRWTU | |
| 41 | Channel CH2 | Operating hours feedback | 2 Bytes | CRWT | |
| 42 | Channel CH2 | Service required | 1 Bit | CRTU | |
| 43 | Channel CH2 | Reset service | 1 Bit | CRW | |
| 43 | Channel CH2 | Reset operating hours | 1 Bit | CRW | |
| 44 | Channel CH2 | General error message | 1 Bit | CRTU | |
| 45 | Channel CH2 | Short circuit message | 1 Bit | CRTU | |
| 46 | Channel CH2 | Excess temperature message | 1 Bit | CRTU | |
| 47 | Channel CH2 | Mains power failure | 1 Bit | CRTU | |
| 48 | Channel CH2 | Load type message (RC/L) | 1 Bit | CRTU | |
| 78 | CH1 + CH2 | Manual | 1 Bit | CRWTU | |
| 80 | Channel CH3 | Switching ON/OFF | 1 Bit | CRWU | |
| 81 | Channel CH3 | Brighter/darker | 4 Bit | CRWU | |
| 82 | Channel CH3 | Dimming value | 1 Byte | CWU | |
| 83 | Channel CH3 | Soft switching | 1 Bit | CRWU | |
| 84 | Channel CH3 | Lock | 1 Bit | CRWU | |
| 85 | Channel CH3 | Call up/save scenes | 1 Byte | CRWU | |
| 86 | Channel CH3 | Lock scenes = 1 | 1 Bit | CRW | |
| 86 | Channel CH3 | Enable scenes = 1 | 1 Bit | CRW | |
| 87 | Channel CH3 | Force = 1 | 1 Bit | CRWU | |
| 87 | Channel CH3 | Force = 0 | 1 Bit | CRWU | |
| 87 | Channel CH3 | Dimming value with forced op | 1 Byte | CRWU | |
| 87 | Channel CH3 | Forced mode | 2 Bit | CRWU | |
| 88 | Channel CH3 | Dimming value limit | 1 Byte | CRWU | |
| 89 | Channel CH3 | Feedback On/Off | 1 Bit | CRTU | |
| 90 | Channel CH3 | Feedback in % | 1 Byte | CRTU | |
| 91 | Channel CH3 | Time to next service | 2 Bytes | CRWTU | |
| 91 | Channel CH3 | Operating hours feedback | 2 Bytes | CRWT | |
| 92 | Channel CH3 | Service required | 1 Bit | CRTU | |
| 93 | Channel CH3 | Reset service | 1 Bit | CRW | |
| 93 | Channel CH3 | Reset operating hours | 1 Bit | CRW | |
| 94 | Channel CH3 | General error message | 1 Bit | CRTU | |
| 95 | Channel CH3 | Short circuit message | 1 Bit | CRTU | |
| 96 | Channel CH3 | Excess temperature message | 1 Bit | CRTU | |
| 97 | Channel CH3 | Mains power failure | 1 Bit | CRTU | |
| 98 | Channel CH3 | Load type message (RC/L) | 1 Bit | CRTU | |
| 110 | Channel CH4 | Switching ON/OFF | 1 Bit | CRWU | |
| 111 | Channel CH4 | Brighter/darker | 4 Bit | CRWU | |
| 112 | Channel CH4 | Dimming value | 1 Byte | CWU | |
| 113 | Channel CH4 | Soft switching | 1 Bit | CRWU | |
| 114 | Channel CH4 | Lock | 1 Bit | CRWU | |
| 115 | Channel CH4 | Call up/save scenes | 1 Byte | CRWU | |
| 116 | Channel CH4 | Enable scenes = 1 | 1 Bit | CRW | |
| 116 | Channel CH4 | Lock scenes = 1 | 1 Bit | CRW | |
| 117 | Channel CH4 | Force = 0 | 1 Bit | CRWU | |
| 117 | Channel CH4 | Force = 1 | 1 Bit | CRWU | |
| 117 | Channel CH4 | Dimming value with forced op | 1 Byte | CRWU | |
| 117 | Channel CH4 | Forced mode | 2 Bit | CRWU | |
| 118 | Channel CH4 | Dimming value limit | 1 Byte | CRWU | |
| 119 | Channel CH4 | Feedback On/Off | 1 Bit | CRTU | |
| 120 | Channel CH4 | Feedback in % | 1 Byte | CRTU | |
| 121 | Channel CH4 | Time to next service | 2 Bytes | CRWTU | |
| 121 | Channel CH4 | Operating hours feedback | 2 Bytes | CRWT | |
| 122 | Channel CH4 | Service required | 1 Bit | CRTU | |
| 123 | Channel CH4 | Reset service | 1 Bit | CRW | |
| 123 | Channel CH4 | Reset operating hours | 1 Bit | CRW | |
| 124 | Channel CH4 | General error message | 1 Bit | CRTU | |
| 125 | Channel CH4 | Short circuit message | 1 Bit | CRTU | |
| 126 | Channel CH4 | Excess temperature message | 1 Bit | CRTU | |
| 127 | Channel CH4 | Mains power failure | 1 Bit | CRTU | |
| 128 | Channel CH4 | Load type message (RC/L) | 1 Bit | CRTU | |
| 158 | CH3 + CH4 | Manual | 1 Bit | CRWTU | |
| 240 | Central permanent ON | Receive | 1 Bit | CRWTU | |
| 241 | Central permanent OFF | Receive | 1 Bit | CRWTU | |
| 242 | Central switching | Receive | 1 Bit | CRWTU | |
| 243 | Central recall/save scenes | Receive | 1 Byte | CRWTU | |
| 250 | BCU version | Transmit | 14 Bytes | CRTU | |
| 251 | Version CH1 + CH2 | Transmit | 14 Bytes | CRTU | |
| 252 | Version CH3 + CH4 | Transmit | 14 Bytes | CRTU |
Parameters (113)
| Parameter | Type | Default |
|---|---|---|
| - | list | yes |
| No. Of general parameters | unsignedInt 1…3 | 3 |
| Download 101 | list | yes |
| Object link RMG 4 I invisible | list | DMG 2 T |
| 101 RMG 4 I invisible | list | Defaultwert - Dummy |
| Type of basic module | list | DMG 2 T |
| Type | list | DM 2 |
| Type of second extension module | list | not available/inactive |
| Function of manual push button | list | valid until reset via object |
| Manual operation of channels | list | enabled |
| Object link RMG 4 I invisible | list | 1. DME 2 T |
| Adjust dimming value limits | list | no |
| Adjust soft switching | list | no |
| Adjust lock function | list | no |
| Activate forced mode | list | no |
| Activate scenes | list | no |
| Participation in central objects | list | no |
| Adjust feedback | list | no |
| Activate hour meter | list | no |
| Activate diagnostic messages | list | no |
| Load selection | list | automatic |
| LED Lampen (RC) | list | Defaultwert - Dummy |
| *** 10 % point in 100 µs (Standard=24) | unsignedInt 15…93 | 24 |
| *** 20 % point in 100 µs (Standard=31) | unsignedInt 15…93 | 31 |
| *** 30 % point in 100 µs (Standard=36) | unsignedInt 15…93 | 36 |
| *** 40 % point in 100 µs (Standard=41) | unsignedInt 15…93 | 41 |
| *** 50 % point in 100 µs (Standard=46) | unsignedInt 15…93 | 46 |
| *** 60 % point in 100 µs (Standard=51) | unsignedInt 15…93 | 51 |
| *** 70 % point in 100 µs (Standard=56) | unsignedInt 15…93 | 56 |
| *** 80 % point in 100 µs (Standard=63) | unsignedInt 15…93 | 63 |
| *** 90 % point in 100 µs (Standard=75) | unsignedInt 15…93 | 75 |
| *** Start-up value | list | 50 % |
| ATTENTION: USE ONLY AFTER DISCUSSING WITH HOTLINE! | list | RC mode SET PERMANENTLY! |
| *** Type of load | list | RC |
| *** Start-up time (unit) | list | 20 ms |
| Start-up time | list | 10 s |
| *** Start-up time (factor) | unsignedInt 0…127 | 50 |
| *** 100 % point in 100 µs (Standard=100) | list | 100 % = limited to the 90 % setting |
| Minimum dimming value | list | 10 % |
| Dimming time 1 from 0% to 100% | list | 4 s |
| Dimming time 2 from 0% to 100% | list | 8 s |
| Dimming time 3 from 0% to 100% | list | 12 s |
| When receiving a switching order (1 bit) | list | soft on with dimming time 1 |
| When receiving a dimming order (4 bit) | list | soft on with dimming time 1 |
| When receiving an absolute value (8 bit) | list | soft on with dimming time 1 |
| Switch-on value | list | brightness value before previous switch-OFF |
| Switching ON/OFF with a 4-bit dim telegram | list | yes |
| Perform limitation when writing object | list | no |
| Limit applies to soft switching | list | no |
| Limit applies to switching command (1-bit) | list | no |
| Limit applies to absolute dimming (8-bit) | list | no |
| Limit applies to relative dimming (4-bit) | list | no |
| Time for Soft ON | list | 1 min |
| Dimming value after Soft ON | list | 100 % |
| Time between Soft ON and Soft OFF | list | 5 min |
| Time for Soft OFF | list | 1 min |
| Lock telegram | list | lock with ON telegram |
| Reaction when setting the lock | list | 10 % |
| Reaction when unlocking | list | update |
| Format of forced object | list | 1 bit |
| Activate forced mode with | list | 1 |
| Behaviour at start of forced mode operation | list | no change |
| Reaction on forced ON | list | no change |
| Behaviour at end of forced mode | list | value before forced mode |
| Reaction on forced OFF | list | OFF |
| Lock telegram for scenes | list | lock with ON telegram |
| All scene statuses of channel | list | overwrite when downloading |
| Participation in object Central scene | list | no |
| Channel reacts to | list | scene number 1 |
| Allocated dimming value | list | 10 % |
| Response when receiving scene numbers | list | soft on with dimming time 1 |
| Permit teach-in | list | yes |
| Channel reacts to | list | scene number 2 |
| Allocated dimming value | list | 20 % |
| Channel reacts to | list | scene number 3 |
| Allocated dimming value | list | 30 % |
| Channel reacts to | list | scene number 4 |
| Allocated dimming value | list | 40 % |
| Channel reacts to | list | scene number 5 |
| Allocated dimming value | list | 50 % |
| Channel reacts to | list | scene number 6 |
| Allocated dimming value | list | 60 % |
| Channel reacts to | list | scene number 7 |
| Allocated dimming value | list | 70 % |
| Channel reacts to | list | scene number 8 |
| Allocated dimming value | list | 80 % |
| Format of 1-bit feedback | list | not inverted |
| Send 1-bit feedback cyclically | list | no |
| Send 8-bit feedback | list | only after ending dimming process |
| Send 8-bit feedback cyclically | list | no |
| Time for cyclical transmission of feedback (if available) | list | 60 min |
| Type of hour meter | list | operating hours counter |
| Service interval (0..2000, x 10 h) | unsignedInt 0…2000 | 100 |
| Report time to service when changed (0..100 h, 0 = no report) | unsignedInt 0…100 | 10 |
| Report operating hours at change (0..100 h, 0 = no report) | unsignedInt 0…100 | 10 |
| Transmit operating hours cyclically | list | no |
| Transmit time to service cyclically | list | no |
| Report service cyclically | list | no |
| Time for cyclical transmission | list | 60 min |
| Time for cyclical transmission (time to service) | list | 60 min |
| Status at download and bus failure | list | same as before failure |
| Status at restoration of mains or bus power | list | same as before failure |
| Send general error cyclically | list | no |
| Send short circuit cyclically | list | no |
| Send excess temperature cyclically | list | no |
| Send mains failure cyclically | list | no |
| Send load type cyclically | list | no |
| Send status cyclically (bit set) | list | no |
| Cycle time for all diagnostic messages (if used) | list | 60 min |
| Copy main parameters from channel CH1 | list | no |
| *** 100 % point in 100 µs (Standard=100) | list | 100 (10 ms) |
| *** Type of load | list | L |
| Copy main parameters from channel CH3 | list | no |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| KNX UNIVERSAL DIMMER 2-CH X 400W - DIN RAIL 1.2 latest | $4947 | F5BA | 2026-11-25 | 200 KB | Download |
About this file
This is the official ETS product database for the GEWISS GWA9303 (GWA9303), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.