| 0 | Measured temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 0 | Measured temperature | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 0 | Measured temperature | °F value | 2 Bytes | | CRT |
| 0 | Measured temperature | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 0 | Measured temperature | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 0 | Measured temperature | °F value | 2 Bytes | | CR |
| 1 | Relative humidity measured | Value [% RH] | 2 Bytes | DPT.9 | CRT |
| 1 | Relative humidity measured | Value [% RH] | 2 Bytes | DPT.9 | CR |
| 2 | Temperature threshold 1 value input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 2 | Temperature threshold 1 value input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 2 | Temperature threshold 1 value input | °F value | 2 Bytes | | CW |
| 2 | Temperature threshold 1 value regulation | 1 = Increase/0 = Decrease | 1 Bit | | CW |
| 3 | Temperature threshold 1 feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 3 | Temperature threshold 1 feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 3 | Temperature threshold 1 feedback | °F value | 2 Bytes | | CRT |
| 4 | Temperature threshold 2 value input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 4 | Temperature threshold 2 value input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 4 | Temperature threshold 2 value input | °F value | 2 Bytes | | CW |
| 4 | Temperature threshold 2 value regulation | 1 = Increase/0 = Decrease | 1 Bit | | CW |
| 5 | Temperature threshold 2 feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 5 | Temperature threshold 2 feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 5 | Temperature threshold 2 feedback | °F value | 2 Bytes | | CRT |
| 6 | Temperature threshold 3 value input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 6 | Temperature threshold 3 value input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 6 | Temperature threshold 3 value input | °F value | 2 Bytes | | CW |
| 6 | Temperature threshold 3 value regulation | 1 = Increase/0 = Decrease | 1 Bit | | CW |
| 7 | Temperature threshold 3 feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 7 | Temperature threshold 3 feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 7 | Temperature threshold 3 feedback | °F value | 2 Bytes | | CRT |
| 8 | Temperature threshold 4 value input | Value °C | 2 Bytes | 9.1 temperature (°C) | CW |
| 8 | Temperature threshold 4 value input | °K value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 8 | Temperature threshold 4 value input | °F value | 2 Bytes | | CW |
| 8 | Temperature threshold 4 value regulation | 1 = Increase/0 = Decrease | 1 Bit | | CW |
| 9 | Temperature threshold 4 feedback | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 9 | Temperature threshold 4 feedback | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 9 | Temperature threshold 4 feedback | °F value | 2 Bytes | | CRT |
| 10 | Relative humidity threshold 1 value regulation | 1 = Increase/0 = Decrease | 1 Bit | DPT.1 | CW |
| 10 | Relative humidity threshold 1 value input | Value [% RH] | 2 Bytes | DPT.9 | CW |
| 11 | Relative humidity threshold 1 feedback | Value [% RH] | 2 Bytes | DPT.9 | CRT |
| 12 | Relative humidity threshold 2 value regulation | 1 = Increase/0 = Decrease | 1 Bit | DPT.1 | CW |
| 12 | Relative humidity threshold 2 value input | Value [% RH] | 2 Bytes | DPT.9 | CW |
| 13 | Relative humidity threshold 2 feedback | Value [% RH] | 2 Bytes | DPT.9 | CRT |
| 14 | Relative humidity threshold 3 value regulation | 1 = Increase/0 = Decrease | 1 Bit | DPT.1 | CW |
| 14 | Relative humidity threshold 3 value input | Value [% RH] | 2 Bytes | DPT.9 | CW |
| 15 | Relative humidity threshold 3 feedback | Value [% RH] | 2 Bytes | DPT.9 | CRT |
| 16 | Relative humidity threshold 4 value regulation | 1 = Increase/0 = Decrease | 1 Bit | DPT.1 | CW |
| 16 | Relative humidity threshold 4 value input | Value [% RH] | 2 Bytes | DPT.9 | CW |
| 17 | Relative humidity threshold 4 feedback | Value [% RH] | 2 Bytes | DPT.9 | CRT |
| 18 | Output A temperature threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 18 | Output A temperature threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 18 | Output A temperature threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 18 | Output A temperature threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 18 | Temperature threshold 1 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 19 | | | 1 Bit | | |
| 20 | | | 1 Byte | | |
| 21 | Temperature threshold 1 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 21 | Temperature threshold 1 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 21 | Temperature threshold 1 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 21 | Temperature threshold 1 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 21 | Temperature threshold 1 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 21 | Temperature threshold 1 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 21 | Temperature threshold 1 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 21 | Temperature threshold 1 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 21 | Temperature threshold 1 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 21 | Temperature threshold 1 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 21 | Temperature threshold 1 output A | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 22 | Output A temperature threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 22 | Output A temperature threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 22 | Output A temperature threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 22 | Output A temperature threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 22 | Temperature threshold 2 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 23 | | | 1 Bit | | |
| 24 | | | 1 Byte | | |
| 25 | Temperature threshold 2 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 25 | Temperature threshold 2 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 25 | Temperature threshold 2 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 25 | Temperature threshold 2 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 25 | Temperature threshold 2 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 25 | Temperature threshold 2 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 25 | Temperature threshold 2 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 25 | Temperature threshold 2 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 25 | Temperature threshold 2 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 25 | Temperature threshold 2 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 25 | Temperature threshold 2 output A | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 26 | Output A temperature threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 26 | Output A temperature threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 26 | Output A temperature threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 26 | Output A temperature threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 26 | Temperature threshold 3 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 27 | | | 1 Bit | | |
| 28 | | | 1 Byte | | |
| 29 | Temperature threshold 3 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 29 | Temperature threshold 3 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 29 | Temperature threshold 3 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 29 | Temperature threshold 3 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 29 | Temperature threshold 3 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 29 | Temperature threshold 3 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 29 | Temperature threshold 3 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 29 | Temperature threshold 3 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 29 | Temperature threshold 3 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 29 | Temperature threshold 3 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 29 | Temperature threshold 3 output A | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 30 | Output A temperature threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 30 | Output A temperature threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 30 | Output A temperature threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 30 | Output A temperature threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 30 | Temperature threshold 4 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 31 | | | 1 Bit | | |
| 32 | | | 1 Byte | | |
| 33 | Temperature threshold 4 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 33 | Temperature threshold 4 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 33 | Temperature threshold 4 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 33 | Temperature threshold 4 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 33 | Temperature threshold 4 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 33 | Temperature threshold 4 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 33 | Temperature threshold 4 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 33 | Temperature threshold 4 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 33 | Temperature threshold 4 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 33 | Temperature threshold 4 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 33 | Temperature threshold 4 output A | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 34 | Relative humidity threshold 1 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 34 | Output A relative humidity threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 34 | Output A relative humidity threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 34 | Output A relative humidity threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 34 | Output A relative humidity threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 35 | | | 1 Bit | | |
| 36 | | | 1 Byte | | |
| 37 | Relative humidity threshold 5 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 37 | Relative humidity threshold 5 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 37 | Relative humidity threshold 5 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 37 | Relative humidity threshold 5 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 37 | Relative humidity threshold 5 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 37 | Relative humidity threshold 5 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 37 | Relative humidity threshold 5 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 37 | Relative humidity threshold 5 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 37 | Relative humidity threshold 5 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 37 | Relative humidity threshold 5 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 37 | Relative humidity threshold 5 output A | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 38 | Output A relative humidity threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 38 | Output A relative humidity threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 38 | Output A relative humidity threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 38 | Output A relative humidity threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 38 | Relative humidity threshold 2 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 39 | | | 1 Bit | | |
| 40 | | | 1 Byte | | |
| 41 | Relative humidity threshold 2 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 41 | Relative humidity threshold 2 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 41 | Relative humidity threshold 2 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 41 | Relative humidity threshold 2 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 41 | Relative humidity threshold 2 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 41 | Relative humidity threshold 2 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 41 | Relative humidity threshold 2 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 41 | Relative humidity threshold 2 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 41 | Relative humidity threshold 2 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 41 | Relative humidity threshold 2 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 41 | Relative humidity threshold 2 output A | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 42 | Output A relative humidity threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 42 | Output A relative humidity threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 42 | Output A relative humidity threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 42 | Output A relative humidity threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 42 | Relative humidity threshold 3 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 43 | | | 1 Bit | | |
| 44 | | | 1 Byte | | |
| 45 | Relative humidity threshold 3 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 45 | Relative humidity threshold 3 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 45 | Relative humidity threshold 3 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 45 | Relative humidity threshold 3 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 45 | Relative humidity threshold 3 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 45 | Relative humidity threshold 3 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 45 | Relative humidity threshold 3 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 45 | Relative humidity threshold 3 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 45 | Relative humidity threshold 3 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 45 | Relative humidity threshold 3 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 45 | Relative humidity threshold 3 output A | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 46 | Output A relative humidity threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 46 | Output A relative humidity threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 46 | Output A relative humidity threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 46 | Output A relative humidity threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 46 | Relative humidity threshold 4 output A status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 47 | | | 1 Bit | | |
| 48 | | | 1 Byte | | |
| 49 | Relative humidity threshold 4 output A | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 49 | Relative humidity threshold 4 output A | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 49 | Relative humidity threshold 4 output A | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 49 | Relative humidity threshold 4 output A | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 49 | Relative humidity threshold 4 output A | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 49 | Relative humidity threshold 4 output A | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 49 | Relative humidity threshold 4 output A | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 49 | Relative humidity threshold 4 output A | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 49 | Relative humidity threshold 4 output A | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 49 | Relative humidity threshold 4 output A | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 49 | Relative humidity threshold 4 output A | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 50 | Output B temperature threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 50 | Output B temperature threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 50 | Output B temperature threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 50 | Output B temperature threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 50 | Temperature threshold 1 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 51 | | | 1 Bit | | |
| 52 | | | 1 Byte | | |
| 53 | Temperature threshold 1 output B | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 53 | Temperature threshold 1 output B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 53 | Temperature threshold 1 output B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 53 | Temperature threshold 1 output B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 53 | Temperature threshold 1 output B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 53 | Temperature threshold 1 output B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 53 | Temperature threshold 1 output B | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 53 | Temperature threshold 1 output B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 53 | Temperature threshold 1 output B | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 53 | Temperature threshold 1 output B | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 53 | Temperature threshold 1 output B | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 54 | Output C temperature threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 54 | Output C temperature threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 54 | Output C temperature threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 54 | Output C temperature threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 54 | Temperature threshold 1 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 55 | | | 1 Bit | | |
| 56 | | | 1 Byte | | |
| 57 | Temperature threshold 1 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 57 | Temperature threshold 1 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 57 | Temperature threshold 1 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 57 | Temperature threshold 1 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 57 | Temperature threshold 1 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 57 | Temperature threshold 1 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 57 | Temperature threshold 1 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 57 | Temperature threshold 1 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 57 | Temperature threshold 1 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 57 | Temperature threshold 1 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 57 | Temperature threshold 1 output C | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 58 | Output D temperature threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 58 | Output D temperature threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 58 | Output D temperature threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 58 | Output D temperature threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 58 | Temperature threshold 1 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 59 | | | 1 Bit | | |
| 60 | | | 1 Byte | | |
| 61 | Temperature threshold 1 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 61 | Temperature threshold 1 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 61 | Temperature threshold 1 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 61 | Temperature threshold 1 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 61 | Temperature threshold 1 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 61 | Temperature threshold 1 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 61 | Temperature threshold 1 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 61 | Temperature threshold 1 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 61 | Temperature threshold 1 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 61 | Temperature threshold 1 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 61 | Temperature threshold 1 output D | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 62 | Output B temperature threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 62 | Output B temperature threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 62 | Output B temperature threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 62 | Output B temperature threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 62 | Temperature threshold 2 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 63 | | | 1 Bit | | |
| 64 | | | 1 Byte | | |
| 65 | Temperature threshold 2 output B | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 65 | Temperature threshold 2 output B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 65 | Temperature threshold 2 output B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 65 | Temperature threshold 2 output B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 65 | Temperature threshold 2 output B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 65 | Temperature threshold 2 output B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 65 | Temperature threshold 2 output B | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 65 | Temperature threshold 2 output B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 65 | Temperature threshold 2 output B | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 65 | Temperature threshold 2 output B | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 65 | Temperature threshold 2 output B | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 66 | Output C temperature threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 66 | Output C temperature threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 66 | Output C temperature threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 66 | Output C temperature threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 66 | Temperature threshold 2 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 67 | | | 1 Bit | | |
| 68 | | | 1 Byte | | |
| 69 | Temperature threshold 2 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 69 | Temperature threshold 2 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 69 | Temperature threshold 2 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 69 | Temperature threshold 2 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 69 | Temperature threshold 2 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 69 | Temperature threshold 2 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 69 | Temperature threshold 2 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 69 | Temperature threshold 2 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 69 | Temperature threshold 2 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 69 | Temperature threshold 2 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 69 | Temperature threshold 2 output C | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 70 | Output D temperature threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 70 | Output D temperature threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 70 | Output D temperature threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 70 | Output D temperature threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 70 | Temperature threshold 2 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 71 | | | 1 Bit | | |
| 72 | | | 1 Byte | | |
| 73 | Temperature threshold 2 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 73 | Temperature threshold 2 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 73 | Temperature threshold 2 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 73 | Temperature threshold 2 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 73 | Temperature threshold 2 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 73 | Temperature threshold 2 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 73 | Temperature threshold 2 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 73 | Temperature threshold 2 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 73 | Temperature threshold 2 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 73 | Temperature threshold 2 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 73 | Temperature threshold 2 output D | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 74 | Output B temperature threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 74 | Output B temperature threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 74 | Output B temperature threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 74 | Output B temperature threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 74 | Temperature threshold 3 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 75 | | | 1 Bit | | |
| 76 | | | 1 Byte | | |
| 77 | Temperature threshold 3 output B | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 77 | Temperature threshold 3 output B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 77 | Temperature threshold 3 output B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 77 | Temperature threshold 3 output B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 77 | Temperature threshold 3 output B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 77 | Temperature threshold 3 output B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 77 | Temperature threshold 3 output B | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 77 | Temperature threshold 3 output B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 77 | Temperature threshold 3 output B | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 77 | Temperature threshold 3 output B | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 77 | Temperature threshold 3 output B | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 78 | Output C temperature threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 78 | Output C temperature threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 78 | Output C temperature threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 78 | Output C temperature threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 78 | Temperature threshold 3 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 79 | | | 1 Bit | | |
| 80 | | | 1 Byte | | |
| 81 | Temperature threshold 3 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 81 | Temperature threshold 3 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 81 | Temperature threshold 3 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 81 | Temperature threshold 3 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 81 | Temperature threshold 3 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 81 | Temperature threshold 3 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 81 | Temperature threshold 3 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 81 | Temperature threshold 3 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 81 | Temperature threshold 3 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 81 | Temperature threshold 3 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 81 | Temperature threshold 3 output C | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 82 | Output D temperature threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 82 | Output D temperature threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 82 | Output D temperature threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 82 | Output D temperature threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 82 | Temperature threshold 3 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 83 | | | 1 Bit | | |
| 84 | | | 1 Byte | | |
| 85 | Temperature threshold 3 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 85 | Temperature threshold 3 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 85 | Temperature threshold 3 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 85 | Temperature threshold 3 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 85 | Temperature threshold 3 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 85 | Temperature threshold 3 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 85 | Temperature threshold 3 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 85 | Temperature threshold 3 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 85 | Temperature threshold 3 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Temperature threshold 3 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 85 | Temperature threshold 3 output D | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 86 | Output B temperature threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 86 | Output B temperature threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 86 | Output B temperature threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 86 | Output B temperature threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 86 | Temperature threshold 4 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 87 | | | 1 Bit | | |
| 88 | | | 1 Byte | | |
| 89 | Temperature threshold 4 output B | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 89 | Temperature threshold 4 output B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 89 | Temperature threshold 4 output B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 89 | Temperature threshold 4 output B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 89 | Temperature threshold 4 output B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 89 | Temperature threshold 4 output B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 89 | Temperature threshold 4 output B | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 89 | Temperature threshold 4 output B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 89 | Temperature threshold 4 output B | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 89 | Temperature threshold 4 output B | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 89 | Temperature threshold 4 output B | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 90 | Output C temperature threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 90 | Output C temperature threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 90 | Output C temperature threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 90 | Output C temperature threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 90 | Temperature threshold 4 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 91 | | | 1 Bit | | |
| 92 | | | 1 Byte | | |
| 93 | Temperature threshold 4 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 93 | Temperature threshold 4 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 93 | Temperature threshold 4 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 93 | Temperature threshold 4 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 93 | Temperature threshold 4 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 93 | Temperature threshold 4 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 93 | Temperature threshold 4 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 93 | Temperature threshold 4 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 93 | Temperature threshold 4 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 93 | Temperature threshold 4 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 93 | Temperature threshold 4 output C | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 94 | Output D temperature threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 94 | Output D temperature threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 94 | Output D temperature threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 94 | Output D temperature threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 94 | Temperature threshold 4 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 95 | | | 1 Bit | | |
| 96 | | | 1 Byte | | |
| 97 | Temperature threshold 4 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 97 | Temperature threshold 4 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 97 | Temperature threshold 4 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 97 | Temperature threshold 4 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 97 | Temperature threshold 4 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 97 | Temperature threshold 4 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 97 | Temperature threshold 4 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 97 | Temperature threshold 4 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 97 | Temperature threshold 4 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 97 | Temperature threshold 4 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 97 | Temperature threshold 4 output D | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 98 | Output B relative humidity threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 98 | Output B relative humidity threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 98 | Output B relative humidity threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 98 | Output B relative humidity threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 98 | Relative humidity threshold 1 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 99 | | | 1 Bit | | |
| 100 | | | 1 Byte | | |
| 101 | Relative humidity threshold 5 output B | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 101 | Relative humidity threshold 5 output B | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 101 | Relative humidity threshold 5 output B | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 101 | Relative humidity threshold 5 output B | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 101 | Relative humidity threshold 5 output B | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 101 | Relative humidity threshold 5 output B | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 101 | Relative humidity threshold 5 output B | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 101 | Relative humidity threshold 5 output B | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 101 | Relative humidity threshold 5 output B | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 101 | Relative humidity threshold 5 output B | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 101 | Relative humidity threshold 5 output B | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 102 | Output C relative humidity threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 102 | Output C relative humidity threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 102 | Output C relative humidity threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 102 | Output C relative humidity threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 102 | Relative humidity threshold 1 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 103 | | | 1 Bit | | |
| 104 | | | 1 Byte | | |
| 105 | Relative humidity threshold 3 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 105 | Relative humidity threshold 3 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 105 | Relative humidity threshold 3 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 105 | Relative humidity threshold 3 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 105 | Relative humidity threshold 3 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 105 | Relative humidity threshold 3 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 105 | Relative humidity threshold 3 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 105 | Relative humidity threshold 3 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 105 | Relative humidity threshold 3 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 105 | Relative humidity threshold 3 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 105 | Relative humidity threshold 3 output D | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 106 | Output D relative humidity threshold 1 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 106 | Output D relative humidity threshold 1 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 106 | Output D relative humidity threshold 1 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 106 | Output D relative humidity threshold 1 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 106 | Relative humidity threshold 1 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 107 | | | 1 Bit | | |
| 108 | | | 1 Byte | | |
| 109 | Relative humidity threshold 1 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 109 | Relative humidity threshold 1 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 109 | Relative humidity threshold 1 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 109 | Relative humidity threshold 1 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 109 | Relative humidity threshold 1 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 109 | Relative humidity threshold 1 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 109 | Relative humidity threshold 1 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 109 | Relative humidity threshold 1 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 109 | Relative humidity threshold 1 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 109 | Relative humidity threshold 1 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 109 | Relative humidity threshold 1 output D | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 110 | Output B relative humidity threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 110 | Output B relative humidity threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 110 | Output B relative humidity threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 110 | Output B relative humidity threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 110 | Relative humidity threshold 2 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 111 | | | 1 Bit | | |
| 112 | | | 1 Byte | | |
| 113 | Relative humidity threshold 1 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 113 | Relative humidity threshold 1 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 113 | Relative humidity threshold 1 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 113 | Relative humidity threshold 1 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 113 | Relative humidity threshold 1 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 113 | Relative humidity threshold 1 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 113 | Relative humidity threshold 1 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 113 | Relative humidity threshold 1 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 113 | Relative humidity threshold 1 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 113 | Relative humidity threshold 1 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 113 | Relative humidity threshold 1 output C | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 114 | Output C relative humidity threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 114 | Output C relative humidity threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 114 | Output C relative humidity threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 114 | Output C relative humidity threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 114 | Relative humidity threshold 2 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 115 | | | 1 Bit | | |
| 116 | | | 1 Byte | | |
| 117 | Relative humidity threshold 4 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 117 | Relative humidity threshold 4 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 117 | Relative humidity threshold 4 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 117 | Relative humidity threshold 4 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 117 | Relative humidity threshold 4 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 117 | Relative humidity threshold 4 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 117 | Relative humidity threshold 4 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 117 | Relative humidity threshold 4 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 117 | Relative humidity threshold 4 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 117 | Relative humidity threshold 4 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 117 | Relative humidity threshold 4 output D | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 118 | Output D relative humidity threshold 2 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 118 | Output D relative humidity threshold 2 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 118 | Output D relative humidity threshold 2 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 118 | Output D relative humidity threshold 2 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 118 | Relative humidity threshold 2 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 119 | | | 1 Bit | | |
| 120 | | | 1 Byte | | |
| 121 | Relative humidity threshold 2 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 121 | Relative humidity threshold 2 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 121 | Relative humidity threshold 2 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 121 | Relative humidity threshold 2 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 121 | Relative humidity threshold 2 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 121 | Relative humidity threshold 2 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 121 | Relative humidity threshold 2 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 121 | Relative humidity threshold 2 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 121 | Relative humidity threshold 2 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 121 | Relative humidity threshold 2 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 121 | Relative humidity threshold 2 output D | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 122 | Output B relative humidity threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 122 | Output B relative humidity threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 122 | Output B relative humidity threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 122 | Output B relative humidity threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 122 | Relative humidity threshold 3 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 123 | | | 1 Bit | | |
| 124 | | | 1 Byte | | |
| 125 | Relative humidity threshold 2 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 125 | Relative humidity threshold 2 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 125 | Relative humidity threshold 2 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 125 | Relative humidity threshold 2 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 125 | Relative humidity threshold 2 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 125 | Relative humidity threshold 2 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 125 | Relative humidity threshold 2 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 125 | Relative humidity threshold 2 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 125 | Relative humidity threshold 2 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 125 | Relative humidity threshold 2 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 125 | Relative humidity threshold 2 output C | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 126 | Output C relative humidity threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 126 | Output C relative humidity threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 126 | Output C relative humidity threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 126 | Output C relative humidity threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 126 | Relative humidity threshold 3 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 127 | | | 1 Bit | | |
| 128 | | | 1 Byte | | |
| 129 | Relative humidity threshold 5 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 129 | Relative humidity threshold 5 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 129 | Relative humidity threshold 5 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 129 | Relative humidity threshold 5 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 129 | Relative humidity threshold 5 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 129 | Relative humidity threshold 5 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 129 | Relative humidity threshold 5 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 129 | Relative humidity threshold 5 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 129 | Relative humidity threshold 5 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 129 | Relative humidity threshold 5 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 129 | Relative humidity threshold 5 output D | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 130 | Output D relative humidity threshold 3 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 130 | Output D relative humidity threshold 3 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 130 | Output D relative humidity threshold 3 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 130 | Output D relative humidity threshold 3 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 130 | Relative humidity threshold 3 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 131 | | | 1 Bit | | |
| 132 | | | 1 Byte | | |
| 133 | Relative humidity threshold 3 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 133 | Relative humidity threshold 3 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 133 | Relative humidity threshold 3 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 133 | Relative humidity threshold 3 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 133 | Relative humidity threshold 3 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 133 | Relative humidity threshold 3 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 133 | Relative humidity threshold 3 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 133 | Relative humidity threshold 3 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 133 | Relative humidity threshold 3 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 133 | Relative humidity threshold 3 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 133 | Relative humidity threshold 3 output D | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 134 | Output B relative humidity threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 134 | Output B relative humidity threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 134 | Output B relative humidity threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 134 | Output B relative humidity threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 134 | Relative humidity threshold 4 output B status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 135 | | | 1 Bit | | |
| 136 | | | 1 Byte | | |
| 137 | Relative humidity threshold 3 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 137 | Relative humidity threshold 3 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 137 | Relative humidity threshold 3 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 137 | Relative humidity threshold 3 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 137 | Relative humidity threshold 3 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 137 | Relative humidity threshold 3 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 137 | Relative humidity threshold 3 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 137 | Relative humidity threshold 3 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 137 | Relative humidity threshold 3 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 137 | Relative humidity threshold 3 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 137 | Relative humidity threshold 3 output C | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 138 | Output C relative humidity threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 138 | Output C relative humidity threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 138 | Output C relative humidity threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 138 | Output C relative humidity threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 138 | Relative humidity threshold 4 output C status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 139 | | | 1 Bit | | |
| 140 | | | 1 Byte | | |
| 141 | Relative humidity threshold 4 output C | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 141 | Relative humidity threshold 4 output C | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 141 | Relative humidity threshold 4 output C | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 141 | Relative humidity threshold 4 output C | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 141 | Relative humidity threshold 4 output C | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 141 | Relative humidity threshold 4 output C | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 141 | Relative humidity threshold 4 output C | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 141 | Relative humidity threshold 4 output C | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 141 | Relative humidity threshold 4 output C | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 141 | Relative humidity threshold 4 output C | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 141 | Relative humidity threshold 4 output C | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 142 | Output D relative humidity threshold 4 reference | HVAC Mode (com/precom/eco/off) | 1 Byte | | CWTU |
| 142 | Output D relative humidity threshold 4 reference | Setpoint [°C] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 142 | Output D relative humidity threshold 4 reference | Setpoint [°K] | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 142 | Output D relative humidity threshold 4 reference | Setpoint [°F] | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 142 | Relative humidity threshold 4 output D status | On/Off status | 1 Bit | 1.1 switch | CWTU |
| 143 | | | 1 Bit | | |
| 144 | | | 1 Byte | | |
| 145 | Relative humidity threshold 4 output D | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 145 | Relative humidity threshold 4 output D | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 145 | Relative humidity threshold 4 output D | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 145 | Relative humidity threshold 4 output D | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 145 | Relative humidity threshold 4 output D | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 145 | Relative humidity threshold 4 output D | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 145 | Relative humidity threshold 4 output D | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 145 | Relative humidity threshold 4 output D | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 145 | Relative humidity threshold 4 output D | Setpoint value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 145 | Relative humidity threshold 4 output D | Setpoint value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 145 | Relative humidity threshold 4 output D | Setpoint value [°F] | 2 Bytes | DPT.9 | CRT |
| 146 | Temperature threshold 1 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 146 | Temperature threshold 1 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 147 | Temperature threshold 1 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 148 | Temperature threshold 2 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 148 | Temperature threshold 2 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 149 | Temperature threshold 2 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 150 | Temperature threshold 3 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 150 | Temperature threshold 3 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 151 | Temperature threshold 3 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 152 | Temperature threshold 4 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 152 | Temperature threshold 4 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 153 | Temperature threshold 4 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 154 | Relative humidity threshold 1 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 154 | Relative humidity threshold 1 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 155 | Relative humidity threshold 1 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 156 | Relative humidity threshold 2 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 156 | Relative humidity threshold 2 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 157 | Relative humidity threshold 2 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 158 | Relative humidity threshold 3 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 158 | Relative humidity threshold 3 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 159 | Relative humidity threshold 3 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 160 | Relative humidity threshold 4 enabling | 0=Enable/1=Disable | 1 Bit | 1.2 boolean | CW |
| 160 | Relative humidity threshold 4 enabling | 1=Enable/0=Disable | 1 Bit | 1.2 boolean | CW |
| 161 | Relative humidity threshold 4 enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 162 | Dew point temperature alarm enabling | Enable/Disable | 1 Bit | 1.2 boolean | CW |
| 163 | Dew point temperature alarm enabling status | Enabled/Disabled | 1 Bit | 1.3 enable | CRT |
| 164 | Dew point temperature alarm limit regulation | 1 = Increase/0 = Decrease | 1 Bit | DPT.1 | CW |
| 165 | Dew point temperature alarm threshold feedback | Value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 165 | Dew point temperature alarm threshold feedback | Value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 165 | Dew point temperature alarm threshold feedback | Value [°F] | 2 Bytes | DPT.9 | CRT |
| 166 | Dew point temperature alarm output | Value [-128 .. 127] | 1 Byte | 6.10 counter pulses (-128..127) | CRT |
| 166 | Dew point temperature alarm output | On/Off forced positioning | 2 Bit | 2.1 switch control | CRT |
| 166 | Dew point temperature alarm output | 1/0 value | 1 Bit | 1.1 switch | CRT |
| 166 | Dew point temperature alarm output | Value [-32768 .. 32767] | 2 Bytes | 8.1 pulses difference | CRT |
| 166 | Dew point temperature alarm output | Value [0 .. 65535] | 2 Bytes | 7.1 pulses | CRT |
| 166 | Dew point temperature alarm output | Value [0 .. 255] | 1 Byte | 5.10 counter pulses (0..255) | CRT |
| 166 | Dew point temperature alarm output | HVAC Mode (com/precom/eco/off) | 1 Byte | | CRT |
| 166 | Dew point temperature alarm output | Value [0% .. 100%] | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 167 | Dew point temperature | Value [°F] | 2 Bytes | DPT.9 | CRT |
| 167 | Dew point temperature | Value [°K] | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 167 | Dew point temperature | Value [°C] | 2 Bytes | 9.1 temperature (°C) | CRT |
| 167 | Dew point temperature | Value [°C] | 2 Bytes | 9.1 temperature (°C) | CR |
| 167 | Dew point temperature | Value [°K] | 2 Bytes | 9.2 temperature difference (K) | CR |
| 167 | Dew point temperature | Value [°F] | 2 Bytes | DPT.9 | CR |
| 168 | Maximum temperature measured | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 168 | Maximum temperature measured | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 168 | Maximum temperature measured | °F value | 2 Bytes | | CRT |
| 168 | Maximum temperature measured | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 168 | Maximum temperature measured | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 168 | Maximum temperature measured | °F value | 2 Bytes | | CR |
| 169 | Minimum temperature measured | Value °C | 2 Bytes | 9.1 temperature (°C) | CRT |
| 169 | Minimum temperature measured | °K value | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 169 | Minimum temperature measured | °F value | 2 Bytes | | CRT |
| 169 | Minimum temperature measured | Value °C | 2 Bytes | 9.1 temperature (°C) | CR |
| 169 | Minimum temperature measured | °K value | 2 Bytes | 9.2 temperature difference (K) | CR |
| 169 | Minimum temperature measured | °F value | 2 Bytes | | CR |
| 170 | Maximum and minimum temperature values reset | Values reset | 1 Bit | | CW |
| 171 | Maximum relative humidity measured | Value [% RH] | 2 Bytes | DPT.9 | CRT |
| 171 | Maximum relative humidity measured | Value [% RH] | 2 Bytes | DPT.9 | CR |
| 172 | Minimum relative humidity measured | Value [% RH] | 2 Bytes | DPT.9 | CRT |
| 172 | Minimum relative humidity measured | Value [% RH] | 2 Bytes | DPT.9 | CR |
| 173 | Maximum and minimum relative humidity values reset | Values reset | 1 Bit | | CW |
| 174 | Specific humidity | Value [g/kg] | 4 Bytes | 14.5 amplitude | CRT |
| 174 | Specific humidity | Value [g/kg] | 4 Bytes | 14.5 amplitude | CR |
| 175 | Season selection input | 1=Summer / 0=Winter | 1 Bit | 1.2 boolean | CWTU |
| 175 | Season selection input | 1=Winter / 0=Summer | 1 Bit | 1.2 boolean | CWTU |
| 176 | Thermal comfort status feedback | 1=Comfortable/0=Uncomfortable | 1 Bit | 1.2 boolean | CRT |
| 177 | Feedbacks sending trigger | Send feedbacks | 1 Bit | | CW |