GEWISS · Order number GW10761 · EIB Easy › Termoregolazione
Download .knxprod Timed thermostat E 1.0 1.0 · 87 KB
Product
| Manufacturer | GEWISS |
|---|---|
| Product name | GW10761 |
| Order number | GW10761 |
| Product text | Cronotermostato Easy bianco |
| Hardware | Cronotermostati Easy |
| Medium | Twisted Pair |
| Bus current (mA) | 5 |
| Rail mounted | No |
| Registration | Certified |
| Languages | en-US, it-IT, es-ES, de-DE, fr-FR, nl-NL |
| Catalog entry | M-0019_H-10761-1_HP-E301-10-49AC_CI-GW10761-1 |
| Fingerprint | 49AC |
| SHA-256 | ee2fe158240a8224f481ab9bb48f84285a2fe3c3198fabc2db2b14170f9b93ed |
| First seen | 2026-11-25 |
| Markets | 59 markets |
Application program: Cronotermostato E 1.0 1.0
| Application number | $E301 |
|---|---|
| Version | 1.0 |
| Mask version | MV-0021 (2.1) |
| KNX Data Secure | No |
| Parameters | 73 |
| Group objects | 13 |
Group objects (13)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Notifica stato riscaldamento | Stato on/off | 1 Bit | CWTU | |
| 1 | Commutazione riscaldamento | On/Off | 1 Bit | CRT | |
| 2 | Notifica stato condizionamento | Stato on/off | 1 Bit | CWTU | |
| 3 | Commutazione condizionamento | On/Off | 1 Bit | CRT | |
| 4 | Invio modalità termoregolazione | Eco/Precom/Comf/Off | 1 Byte | CRT | |
| 5 | Invio tipo funzionamento | Riscaldamento/Condizionamento | 1 Bit | CRT | |
| 6 | Ingresso modalità termoregolazione | Auto/Eco/Precom/Comf/Off | 1 Byte | CW | |
| 7 | Stato finestra | 1=aperto / 0=chiuso | 1 Bit | CW | |
| 8 | Scenario | Esegui/Apprendi | 1 Byte | CW | |
| 9 | Ingresso tipo funzionamento | Riscaldamento/Condizionamento | 1 Bit | CW | |
| 10 | Segnalazione modalità termoregolazione | Auto/Eco/Precom/Comf/Off | 1 Byte | CRT | |
| 11 | Segnalazione tipo funzionamento | Riscaldamento/Condizionamento | 1 Bit | CRT | |
| 12 | Temperatura misurata | Valore °C | 2 Bytes | CRT |
Parameters (40)
| Parameter | Type | Default |
|---|---|---|
| Modalità di programmazione | list | Modalità Easy |
| Tipo di controllo per riscaldamento | list | Controllo a due punti (on/off) |
| Tipo di controllo per condizionamento | list | Controllo a due punti (on/off) |
| Formato per Impostazione Modalità | list | Entrambi gli oggetti ad 1 bit ed 1 byte |
| Impostazione Setpoint dal BUS | list | Disabilita |
| Notifiche attuatori comandati | list | abilitate |
| Periodo ripetizione comandi in assenza di feedback | list | 5 minuti |
| Formato dei comandi | list | Comandi da 1 bit |
| Differenziale di regolazione (decimi di °C) | unsignedInt 2…20 | 2 |
| Autoapprendimento gradiente termico | list | disabilitato |
| Valore % min. per invio valore | list | 5% |
| Differenziale di regolazione PWM | list | 1,6 °C |
| Tempo ciclo | list | 20 minuti |
| Differenziale di regolazione (decimi di °C) | unsignedInt 2…20 | 5 |
| Setpoint comfort | unsignedInt 50…400 | 200 |
| Setpoint precomfort | unsignedInt 50…400 | 180 |
| Setpoint economy | unsignedInt 50…400 | 160 |
| Setpoint antigelo | unsignedInt 20…70 | 50 |
| Setpoint comfort | unsignedInt 50…400 | 240 |
| Setpoint precomfort | unsignedInt 50…400 | 260 |
| Setpoint economy | unsignedInt 50…400 | 280 |
| Setpoint protezione alte temperature | unsignedInt 300…400 | 350 |
| Abilitazione sonda esterna | list | Disabilitata |
| Peso della sonda nel calcolo della temperatura | list | 50% |
| Tempo di sorveglianza < minuti > | unsignedInt 2…10 | 2 |
| Temperatura misurata | list | invio periodico |
| Periodo invio temperatura ambiente: | list | Ogni 15 minuti |
| Formato INFO Modalità | list | Entrambi gli oggetti ad 1 bit ed 1 byte |
| Invio della modalità di funzionamento (ECONOMY, COMFORT...) | list | invio solo su variazione |
| Invio messaggio di OFF (a 1 BIT) | list | Invio solo su variazione |
| Tipo di funzionamento (Riscaldamento/Condizionamento) | list | invio solo su variazione |
| Attivare funzione | list | no |
| Numero Scenario 1 | list | Non Assegnato |
| Numero Scenario 2 | list | Non Assegnato |
| Numero Scenario 3 | list | Non Assegnato |
| Numero Scenario 4 | list | Non Assegnato |
| Numero Scenario 5 | list | Non Assegnato |
| Numero Scenario 6 | list | Non Assegnato |
| Numero Scenario 7 | list | Non Assegnato |
| Numero Scenario 8 | list | Non Assegnato |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Timed thermostat E 1.0 1.0 latest | $E301 | 49AC | 2026-11-25 | 87 KB | Download |
About this file
This is the official ETS product database for the GEWISS GW10761 (GW10761), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.