KNX Database
Ekinex S.p.A. EK-GD1-TP-4-LV-M KNX dimmer 4 CH 12-48 Vdc Monocrome

KNX dimmer 4 CH 12-48 Vdc Monocrome EK-GD1-TP-4-LV-M

Ekinex S.p.A. · Order number EK-GD1-TP-4-LV-M · Dimmers

KNX dimmer 4 CH 12-48 Vdc Monocrome

Download .knxprod APEKGDXTPXLVM 0.1 · 177 KB

Product

ManufacturerEkinex S.p.A.
Product nameKNX dimmer 4 CH 12-48 Vdc Monocrome
Order numberEK-GD1-TP-4-LV-M
HardwareKNX dimmer 4 CH LV Monochrome
MediumTwisted Pair
Bus current (mA)5
Rail mountedYes
Width (mm)72
RegistrationRegistered · 2025-06-11
Languagesen-US, it-IT
Catalog entryM-00B6_H-00B600000078-1_HP-3744-01-1435_CI-EK.2DGD1.2DTP.2D4.2DLV.2DM-1
Fingerprint1435
SHA-2562a01c807b9cb0e314c0028dc084a2d81d0671281dbed19c01212d31ca6ad8ec7
First seen2026-11-25
Markets69 markets

Application program: APEKGDXTPXLVM 0.1

Application number$3744
Version0.1
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters509
Group objects140
Group objects (140)
NoNameFunctionSizeDPTFlags
1Power alarm status 1 BitDPT.1CRT
2Auxiliary output status 1 BitDPT.1CRT
3Output 1 - ON/OFF command 1 BitDPT.1CW
4Output 1 - Dimming command 4 BitDPT.3CW
5Output 1 - Absolute setpoint control 1 ByteDPT.5CW
6Output 1 - ON/OFF status 1 BitDPT.1CRT
7Output 1 - Actual dimming value 1 ByteDPT.5CRT
8Output 1 - Staircase start/stop command 1 BitDPT.1CW
9Output 1 - Lock command 1 BitDPT.1CW
10Output 1 - Forcing command 2 BitDPT.2CW
11Output 1 - Logic object 1 1 BitDPT.1CRWTU
12Output 1 - Logic object 2 1 BitDPT.1CRWTU
13Output 1 - Logic object 3 1 BitDPT.1CRWTU
14Output 1 - Logic object 4 1 BitDPT.1CRWTU
15Output 1 - Logic object 5 1 BitDPT.1CRWTU
16Output 1 - Logic object 6 1 BitDPT.1CRWTU
17Output 1 - Logic object 7 1 BitDPT.1CRWTU
18Output 1 - Logic object 8 1 BitDPT.1CRWTU
19Output 1 - Scene number 1 ByteDPT.17CW
19Output 1 - Scene number 1 ByteDPT.18CW
20Output 1 - Energy counter (Wh) 4 BytesDPT.13CRT
21Output 1 - Energy counter reset command 1 BitDPT.1CW
22Output 1 - Operating hours counter 2 BytesDPT.7CRT
23Output 1 - Operating seconds counter 4 Bytes13.100 time lag (s)CRT
24Output 1 - Hours counter reset 1 BitDPT.1CW
25Output 1 - Hours counter overflow 1 BitDPT.1CRT
26Output 1 - Night mode command 1 BitDPT.1CW
27Output 1 - Short circuit alarm 1 BitDPT.1CRT
28Output 1 - Open load alarm 1 BitDPT.1CRT
29Output 2 - ON/OFF command 1 BitDPT.1CW
30Output 2 - Dimming command 4 BitDPT.3CW
31Output 2 - Absolute setpoint control 1 ByteDPT.5CW
32Output 2 - ON/OFF status 1 BitDPT.1CRT
33Output 2 - Actual dimming value 1 ByteDPT.5CRT
34Output 2 - Staircase start/stop command 1 BitDPT.1CW
35Output 2 - Lock command 1 BitDPT.1CW
36Output 2 - Forcing command 2 BitDPT.2CW
37Output 2 - Logic object 1 1 BitDPT.1CRWTU
38Output 2 - Logic object 2 1 BitDPT.1CRWTU
39Output 2 - Logic object 3 1 BitDPT.1CRWTU
40Output 2 - Logic object 4 1 BitDPT.1CRWTU
41Output 2 - Logic object 5 1 BitDPT.1CRWTU
42Output 2 - Logic object 6 1 BitDPT.1CRWTU
43Output 2 - Logic object 7 1 BitDPT.1CRWTU
44Output 2 - Logic object 8 1 BitDPT.1CRWTU
45Output 2 - Scene number 1 ByteDPT.17CW
45Output 2 - Scene number 1 ByteDPT.18CW
46Output 2 - Energy counter (Wh) 4 BytesDPT.13CRT
47Output 2 - Energy counter reset command 1 BitDPT.1CW
48Output 2 - Operating hours counter 2 BytesDPT.7CRT
49Output 2 - Operating seconds counter 4 Bytes13.100 time lag (s)CRT
50Output 2 - Hours counter reset 1 BitDPT.1CW
51Output 2 - Hours counter overflow 1 BitDPT.1CRT
52Output 2 - Night mode command 1 BitDPT.1CW
53Output 2 - Short circuit alarm 1 BitDPT.1CRT
54Output 2 - Open load alarm 1 BitDPT.1CRT
55Output 3 - ON/OFF command 1 BitDPT.1CW
56Output 3 - Dimming command 4 BitDPT.3CW
57Output 3 - Absolute setpoint control 1 ByteDPT.5CW
58Output 3 - ON/OFF status 1 BitDPT.1CRT
59Output 3 - Actual dimming value 1 ByteDPT.5CRT
60Output 3 - Staircase start/stop command 1 BitDPT.1CW
61Output 3 - Lock command 1 BitDPT.1CW
62Output 3 - Forcing command 2 BitDPT.2CW
63Output 3 - Logic object 1 1 BitDPT.1CRWTU
64Output 3 - Logic object 2 1 BitDPT.1CRWTU
65Output 3 - Logic object 3 1 BitDPT.1CRWTU
66Output 3 - Logic object 4 1 BitDPT.1CRWTU
67Output 3 - Logic object 5 1 BitDPT.1CRWTU
68Output 3 - Logic object 6 1 BitDPT.1CRWTU
69Output 3 - Logic object 7 1 BitDPT.1CRWTU
70Output 3 - Logic object 8 1 BitDPT.1CRWTU
71Output 3 - Scene number 1 ByteDPT.17CW
71Output 3 - Scene number 1 ByteDPT.18CW
72Output 3 - Energy counter (Wh) 4 BytesDPT.13CRT
73Output 3 - Energy counter reset command 1 BitDPT.1CW
74Output 3 - Operating hours counter 2 BytesDPT.7CRT
75Output 3 - Operating seconds counter 4 Bytes13.100 time lag (s)CRT
76Output 3 - Hours counter reset 1 BitDPT.1CW
77Output 3 - Hours counter overflow 1 BitDPT.1CRT
78Output 3 - Night mode command 1 BitDPT.1CW
79Output 3 - Short circuit alarm 1 BitDPT.1CRT
80Output 3 - Open load alarm 1 BitDPT.1CRT
81Output 4 - ON/OFF command 1 BitDPT.1CW
82Output 4 - Dimming command 4 BitDPT.3CW
83Output 4 - Absolute setpoint control 1 ByteDPT.5CW
84Output 4 - ON/OFF status 1 BitDPT.1CRT
85Output 4 - Actual dimming value 1 ByteDPT.5CRT
86Output 4 - Staircase start/stop command 1 BitDPT.1CW
87Output 4 - Lock command 1 BitDPT.1CW
88Output 4 - Forcing command 2 BitDPT.2CW
89Output 4 - Logic object 1 1 BitDPT.1CRWTU
90Output 4 - Logic object 2 1 BitDPT.1CRWTU
91Output 4 - Logic object 3 1 BitDPT.1CRWTU
92Output 4 - Logic object 4 1 BitDPT.1CRWTU
93Output 4 - Logic object 5 1 BitDPT.1CRWTU
94Output 4 - Logic object 6 1 BitDPT.1CRWTU
95Output 4 - Logic object 7 1 BitDPT.1CRWTU
96Output 4 - Logic object 8 1 BitDPT.1CRWTU
97Output 4 - Scene number 1 ByteDPT.17CW
97Output 4 - Scene number 1 ByteDPT.18CW
98Output 4 - Energy counter (Wh) 4 BytesDPT.13CRT
99Output 4 - Energy counter reset command 1 BitDPT.1CRWTU
100Output 4 - Operating hours counter 2 BytesDPT.7CRT
101Output 4 - Operating seconds counter 4 Bytes13.100 time lag (s)CRT
102Output 4 - Hours counter reset 1 BitDPT.1CW
103Output 4 - Hours counter overflow 1 BitDPT.1CRT
104Output 4 - Night mode command 1 BitDPT.1CW
105Output 4 - Short circuit alarm 1 BitDPT.1CRT
106Output 4 - Open load alarm 1 BitDPT.1CRT
108Status 1bit - 1 1 BitDPT.1CRT
109Command 1bit - 1 1 BitDPT.1CW
110Status 1bit - 2 1 BitDPT.1CRT
111Command 1bit - 2 1 BitDPT.1CW
112Status 1bit - 3 1 BitDPT.1CRT
113Command 1bit - 3 1 BitDPT.1CW
114Status 1bit - 4 1 BitDPT.1CRT
115Command 1bit - 4 1 BitDPT.1CW
116Status 1bit - 5 1 BitDPT.1CRT
117Command 1bit - 5 1 BitDPT.1CW
118Status 1byte - 1 1 ByteDPT.6CRT
119Command 1byte - 1 1 ByteDPT.6CW
120Status 1byte - 2 1 ByteDPT.6CRT
121Command 1byte - 2 1 ByteDPT.6CW
122Status 1byte - 3 1 ByteDPT.6CRT
123Command 1byte - 3 1 ByteDPT.6CW
124Status 1byte - 4 1 ByteDPT.6CRT
125Command 1byte - 4 1 ByteDPT.6CW
126Status 1byte - 5 1 ByteDPT.6CRT
127Command 1byte - 5 1 ByteDPT.6CW
128Status 2byte - 1 2 BytesDPT.7CRT
129Command 2byte - 1 2 BytesDPT.7CW
130Status 2byte - 2 2 BytesDPT.7CRT
131Command 2byte - 2 2 BytesDPT.7CW
132Status 3byte - 1 6 BytesDPT.251CRT
133Command 3byte - 1 6 BytesDPT.251CW
134Status 3byte - 2 3 BytesDPT.250CRT
135Command 3byte - 2 3 BytesDPT.250CW
136Status 4byte - 1 4 BytesDPT.13CRT
137Command 4byte - 1 4 BytesDPT.13CW
Parameters (90)
ParameterTypeDefault
PID_HARDWARE_TYPE_PARAMETERlist
Product typelistEK-GD2-TP-1-LV-M
Power OFF alarmlistDisabled
Auxiliary output functionlistDisabled
Delay power OFF durationtime10000
Delay power ON durationtime2000
Output 1listDisabled
Output 2listDisabled
Output typelistDirect
Channel to copy fromlistChannel 1
Output 3listDisabled
Output 4listDisabled
Curve typelistLinear
Minimum dimming value (%)unsignedInt 0…500
Maximum dimming value (%)unsignedInt 55…100100
Full range dimming timetime4000
Intensity when switch onlistLast value
Light intensity (%)unsignedInt 0…10050
Switch ON typelistSoft
Ramp time for ONtime2000
Delay start dimming after switch ON (ms)unsignedInt 0…1000250
Switch OFF typelistSoft
Ramp time for OFFtime2000
Switch ON when dimming uplistAlways
Switch OFF when dimming downlistAlways
ON delay timetime0
OFF delay timetime0
Status feedback telegramlistEnabled
Delay after bus recoverytime1000
Transmission cycle timetime0
Behaviour at power ONlistPrevious state
Behaviour at bus OFFlistNo change
Behaviour at bus ONlistPrevious state
Behavior after downloadlistNo change
Lock functionlistDisabled
Lock device signallistNot inverted
After bus recoverylistPrevious state
Behaviour at lockinglistNo change
Behaviour at unlockinglistNo change
Forced functionlistDisabled
Behaviour on forced control startlistLast value
Behaviour on forced control endlistNo change
Behaviour after bus recoverylistPrevious state
Staircase functionlistDisabled
Staircase timetime30000
Manual OFFlistDisabled
RetriggerablelistDisabled
Pre-warninglistDisabled
Pre-warning timetime10000
Interruption time (ms)unsignedInt 250…1000500
Logic functionlistDisabled
Read delay after bus recoveryunsignedInt 250…100001000
Logic operation typelistOR
Logic object 1listDisabled
Logic object 1 negatedlistNo
Logic object 2listDisabled
Logic object 2 negatedlistNo
Logic object 3listDisabled
Logic object 3 negatedlistNo
Logic object 4listDisabled
Logic object 4 negatedlistNo
Logic object 5listDisabled
Logic object 5 negatedlistNo
Logic object 6listDisabled
Logic object 6 negatedlistNo
Logic object 7listDisabled
Logic object 7 negatedlistNo
Logic object 8listDisabled
Logic object 8 negatedlistNo
Scenes functionlistDisabled
Download overwrites learned behaviourlistYes
Scene 1listDisabled
Scene numberunsignedInt 1…641
Activation delaytime0
Learning modelistDisabled
Output behaviourlistOn
Scene 2listDisabled
Scene 3listDisabled
Scene 4listDisabled
Scene 5listDisabled
Scene 6listDisabled
Scene 7listDisabled
Scene 8listDisabled
Night functionlistDisabled
Night mode signallistNot inverted
Maximum light intensity (%)unsignedInt 0…10050
Counter functionlistDisabled
Output load (W)unsignedInt 0…500050
Cyclic sendingtime0
Output PWM frequencylist250 Hz

Version history

ApplicationApp noFingerprintFirst seenSizeFile
APEKGDXTPXLVM 0.1 latest$374414352026-11-25177 KBDownload

About this file

This is the official ETS product database for the Ekinex S.p.A. KNX dimmer 4 CH 12-48 Vdc Monocrome (EK-GD1-TP-4-LV-M), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from Ekinex S.p.A.

All Ekinex S.p.A. products