Ekinex S.p.A. EK-BO1-TP-RMA Modbus / KNX interface for RDZ air handling units

Modbus / KNX interface for RDZ air handling units EK-BO1-TP-RMA

Ekinex S.p.A. · Order number EK-BO1-TP-RMA · Inputs

Modbus / KNX interface for RDZ air handling units

Download .knxprod APEKBO1TPRMA 0.2 · 135 KB

Product

ManufacturerEkinex S.p.A.
Product nameModbus / KNX interface for RDZ air handling units
Order numberEK-BO1-TP-RMA
HardwareInterfaccia Modbus / KNX per macchine aria RDZ
MediumTwisted Pair
Bus current (mA)10
Rail mountedYes
Width (mm)144
RegistrationRegistered · 2021-07-23
Languagesen-US, it-IT
Catalog entryM-00B6_H-00B60000003F-1_HP-003F-02-2757_CI-EK.2DBO1.2DTP.2DRMA-1
Fingerprint2757
SHA-256ba8deaf137d63f081530752ac3c66b3ea124f048b1bb54c8efe12365af9b9594
First seen2026-11-25
Markets69 markets

Application program: APEKBO1TPRMA 0.2

Application number$003F
Version0.2
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version5.0
Parameters93
Group objects257
Group objects (257)
NoNameFunctionSizeDPTFlags
1Connected ventilation unit1 Bit1.2 booleanCRT
2OFF ventilation unit1 Bit1.1 switchCRWT
3Machine selection alarm1 Bit1.5 alarmCRT
4Modbus communication alarm1 Bit1.5 alarmCRT
5Unit type2 BytesDPT.7CRT
6Version2 BytesDPT.7CRT
7Release2 BytesDPT.7CRT
8Installation right/left2 BytesDPT.7CRT
9n.u.2 Bytes7.1 pulsesCRT
10Communication timeout2 Bytes7.5 time (s)CRWT
11n.u.2 Bytes7.1 pulsesCRT
12Input water temperature2 Bytes9.1 temperature (°C)CRT
13Overheating temperature2 Bytes9.1 temperature (°C)CRT
14Evaporator temperature2 Bytes9.1 temperature (°C)CRT
15Condensator temperature2 Bytes9.1 temperature (°C)CRT
15Post-heating condensator temperature2 Bytes9.1 temperature (°C)CRT
16Heat sink temperature2 Bytes9.1 temperature (°C)CRT
17External air temperature2 Bytes9.1 temperature (°C)CRT
18Inflow air temperature2 Bytes9.1 temperature (°C)CRT
19Extraction air temperature2 Bytes9.1 temperature (°C)CRT
19Post-heating undercooling temperature2 Bytes9.1 temperature (°C)CRT
20Exhaust air temperature2 Bytes9.1 temperature (°C)CRT
20Heat sink undercooling temperature2 Bytes9.1 temperature (°C)CRT
21n.u.2 Bytes9.1 temperature (°C)CRT
22Supply fan rotation turns2 BytesDPT.7CRT
22RPM Fan12 BytesDPT.7CRT
23Exhaust fan rotation turns2 BytesDPT.7CRT
23RPM Fan22 BytesDPT.7CRT
24Air pressure transducer2 Bytes9.6 pressure (Pa)CRT
24Flowmeter 12 Bytes9.9 air flow (m³/h)CRT
25Integration valve1 Byte5.1 percentage (0..100%)CRT
25Flowmeter 22 Bytes9.9 air flow (m³/h)CRT
26n.u.2 Bytes9.1 temperature (°C)CRT
27n.u.2 Bytes9.1 temperature (°C)CRT
28Pre-treatment valve position1 Byte5.1 percentage (0..100%)CRT
29n.u.2 Bytes9.1 temperature (°C)CRT
30n.u.2 Bytes9.1 temperature (°C)CRT
31n.u.2 Bytes9.1 temperature (°C)CRT
32Filters hours alarm threshold (write)4 Bytes13.100 time lag (s)CWT
33Filters hours limit pre (write)4 Bytes13.100 time lag (s)CWT
34Filters operating hours4 Bytes13.100 time lag (s)CRT
35n.u.1 Bit1.1 switchCRT
36Dehumidification request ID status1 Bit1.1 switchCRT
37n.u.1 Bit1.1 switchCRT
38Renewal ID status1 Bit1.1 switchCRT
39n.u.1 Bit1.1 switchCRT
40n.u.1 Bit1.1 switchCRT
41Boost request ID status1 Bit1.1 switchCRT
42n.u.1 Bit1.1 switchCRT
43n.u.1 Bit1.1 switchCRT
44n.u.1 Bit1.1 switchCRT
45n.u.1 Bit1.1 switchCRT
46n.u.1 Bit1.1 switchCRT
47n.u.1 Bit1.1 switchCRT
48n.u.1 Bit1.1 switchCRT
49n.u.1 Bit1.1 switchCRT
50n.u.1 Bit1.1 switchCRT
51Damaged/disconnected air delivery temperature probe1 Bit1.5 alarmCRT
51Error NTC11 Bit1.5 alarmCRT
52Damaged/disconnected summer supply exchanger temperature probe1 Bit1.5 alarmCRT
52Damaged/disconnected air extraction temperature probe1 Bit1.5 alarmCRT
52Damaged/disconnected evaporator temperature probe1 Bit1.5 alarmCRT
52Error NTC41 Bit1.5 alarmCRT
53Damaged/disconnected air exhaust temperature probe1 Bit1.5 alarmCRT
53Damaged/disconnected air extraction temperature probe1 Bit1.5 alarmCRT
53Damaged/disconnected undercooling temperature probe B1 Bit1.5 alarmCRT
53Error NTC21 Bit1.5 alarmCRT
54Damaged/disconnected exhaust temperature probe1 Bit1.5 alarmCRT
54Damaged/disconnected heat sink temperature probe1 Bit1.5 alarmCRT
55Damaged/disconnected undercooling temperature probe A1 Bit1.5 alarmCRT
56Damaged/disconnected water temperature probe1 Bit1.5 alarmCRT
57Damaged/disconnected exhaust condensator probe1 Bit1.5 alarmCRT
58Damaged/disconnected external air temperature probe1 Bit1.5 alarmCRT
58Error NTC31 Bit1.5 alarmCRT
59Damaged/disconnected summer exhaust exchanger temperature probe1 Bit1.5 alarmCRT
59Damaged/disconnected condenser temperature probe1 Bit1.5 alarmCRT
59Damaged/disconnected post-heating condenser temperature probe1 Bit1.5 alarmCRT
59Gas transducer damaged/disconnected1 Bit1.5 alarmCRT
60Air pressure transducer damaged/disconnected1 Bit1.5 alarmCRT
60Air transducer A damaged/disconnected1 Bit1.5 alarmCRT
60Flux11 Bit1.5 alarmCRT
61Air transducer B damaged/disconnected1 Bit1.5 alarmCRT
61Flux21 Bit1.5 alarmCRT
62External air flowmeter1 Bit1.5 alarmCRT
63n.u.1 Bit1.5 alarmCRT
64Damaged/disconnected duct temperature probe1 Bit1.5 alarmCRT
65n.u.1 Bit1.5 alarmCRT
66n.u.1 Bit1.5 alarmCRT
67Gas shortage alarm1 Bit1.5 alarmCRT
67Gas low pressure alarm1 Bit1.5 alarmCRT
68Condensation temperature alarm1 Bit1.5 alarmCRT
68Gas high pressure alarm1 Bit1.5 alarmCRT
69Gas high temperature alarm1 Bit1.5 alarmCRT
69Compressor high temperature alarm1 Bit1.5 alarmCRT
70Communication alarm1 Bit1.5 alarmCRT
71n.u.1 Bit1.5 alarmCRT
72Antifreeze alarm (coil protection)1 Bit1.5 alarmCRT
72Defrosting alarm1 Bit1.5 alarmCRT
72Water high temperature alarm1 Bit1.5 alarmCRT
73Input ventilator alarm1 Bit1.5 alarmCRT
73Error fan11 Bit1.5 alarmCRT
74Extraction ventilator alarm1 Bit1.5 alarmCRT
74Error fan21 Bit1.5 alarmCRT
75Defrosting alarm (evaporation low temp.)1 Bit1.5 alarmCRT
76n.u.1 Bit1.5 alarmCRT
77Dirty supply filter alarm1 Bit1.5 alarmCRT
78Dirty exhaust filter alarm1 Bit1.5 alarmCRT
79No filter change alarm1 Bit1.5 alarmCRT
80n.u.1 Bit1.5 alarmCRT
81n.u.1 Bit1.5 alarmCRT
82n.u.1 Bit1.5 alarmCRT
83Season selection via bus1 Bit1.1 switchCWTU
84Dehumidification request1 Bit1.1 switchCWTU
84V4 dehumidification1 Bit1.1 switchCWTU
85Recirculation mode request1 Bit1.1 switchCWTU
86Renewal request1 Bit1.1 switchCWTU
86Renewal request (Speed 2)1 Bit1.1 switchCWTU
86V2 rated1 Bit1.1 switchCWTU
87n.u.1 Bit1.1 switchCWTU
88Free-Cooling forced request1 Bit1.1 switchCWTU
88FC1 Bit1.1 switchCWTU
89Boost request1 Bit1.1 switchCWTU
89Boost request (Speed 3)1 Bit1.1 switchCWTU
89V3 boost1 Bit1.1 switchCWTU
90Thermal integration request1 Bit1.1 switchCWTU
91H2O valve control enabling1 Bit1.1 switchCWTU
92ECONOMY request1 Bit1.1 switchCWTU
92ECONOMY request (Speed 1)1 Bit1.1 switchCWTU
92V1 eco1 Bit1.1 switchCWTU
93Auto FC stop1 Bit1.1 switchCWTU
94n.u.1 Bit1.1 switchCWTU
95n.u.1 Bit1.1 switchCWTU
96n.u.1 Bit1.1 switchCWTU
97n.u.1 Bit1.1 switchCWTU
98n.u.1 Bit1.1 switchCWTU
99Season1 Bit1.1 switchCRT
100Dehumidification active1 Bit1.1 switchCRT
100V4 dehumidification1 Bit1.1 switchCRT
101Recirculation mode active1 Bit1.1 switchCRT
102Renewal active1 Bit1.1 switchCRT
102V2 rated1 Bit1.1 switchCRT
103n.u.1 Bit1.1 switchCRT
104Free-cooling active1 Bit1.1 switchCRT
104FC1 Bit1.1 switchCRT
105Boost active1 Bit1.1 switchCRT
105V3 boost1 Bit1.1 switchCRT
106Thermal integration active1 Bit1.1 switchCRT
107n.u.1 Bit1.1 switchCRT
108Economy call1 Bit1.1 switchCRT
108V1 eco1 Bit1.1 switchCRT
109n.u.1 Bit1.1 switchCRT
110n.u.1 Bit1.1 switchCRT
111n.u.1 Bit1.1 switchCRT
112n.u.1 Bit1.1 switchCRT
113n.u.1 Bit1.1 switchCRT
114n.u.1 Bit1.1 switchCRT
115Antifreeze cycle in progress1 Bit1.1 switchCRT
115Defrost function in progress1 Bit1.1 switchCRT
116Drain-trap cycle in progress1 Bit1.1 switchCRT
117n.u.1 Bit1.1 switchCRT
118n.u.1 Bit1.1 switchCRT
119n.u.1 Bit1.1 switchCRT
120n.u.1 Bit1.1 switchCRT
121n.u.1 Bit1.1 switchCRT
122n.u.1 Bit1.1 switchCRT
123n.u.1 Bit1.1 switchCRT
124n.u.1 Bit1.1 switchCRT
125Supply filter pre-alarm1 Bit1.1 switchCRT
126Exhaust filter pre-alarm1 Bit1.1 switchCRT
127n.u.1 Bit1.1 switchCRT
128n.u.1 Bit1.1 switchCRT
129n.u.1 Bit1.1 switchCRT
130n.u.1 Bit1.1 switchCRT
131Supply air temperature set - summer (write)2 Bytes9.1 temperature (°C)CWTU
131Supply air temperature set (write)2 Bytes9.1 temperature (°C)CWTU
132n.u.2 Bytes9.1 temperature (°C)CWTU
133Renewal flow rate set (write)2 Bytes9.9 air flow (m³/h)CWTU
133Flow rate V2 - rated (write)2 Bytes9.9 air flow (m³/h)CWTU
134Supply flow rate set - winter (write)2 Bytes9.9 air flow (m³/h)CWTU
134Supply flow rate set for dehumidification (write)2 Bytes9.9 air flow (m³/h)CWTU
134Flow rate V4 - dehumid (write)2 Bytes9.9 air flow (m³/h)CWTU
134Recirculation mode flow rate (write)2 Bytes9.9 air flow (m³/h)CWTU
135Boost flow rate set (write)2 Bytes9.9 air flow (m³/h)CWTU
135Flow rate V3 - boost (write)2 Bytes9.9 air flow (m³/h)CWTU
136Free-cooling flow rate set (write)2 Bytes9.9 air flow (m³/h)CWTU
137Economy reduction percentage (write)1 Byte5.1 percentage (0..100%)CWTU
137Flow rate V1 - eco (write)2 Bytes9.9 air flow (m³/h)CWTU
138Boost deactivation delay (write)2 Bytes7.6 time (min)CWTU
139Free-cooling temperature set (write)2 Bytes9.1 temperature (°C)CWTU
139Temperature FC (write)2 Bytes9.1 temperature (°C)CWTU
140Supply air temperature set - winter (write)2 Bytes9.1 temperature (°C)CWTU
141Supply flow rate set - summer (write)2 Bytes9.9 air flow (m³/h)CWTU
141Delta temperature FC (write)2 Bytes9.2 temperature difference (K)CWTU
142Extraction flow rate set - summer (write)2 Bytes9.9 air flow (m³/h)CWTU
142Antifreeze temperature set - renewal antifreeze protection (write)2 Bytes9.1 temperature (°C)CWTU
143Extraction flow rate set - winter (write)2 Bytes9.9 air flow (m³/h)CWTU
143Exhaust dehumidification flow rate (write)2 Bytes9.9 air flow (m³/h)CWTU
144Supply air temperature set - winter integration (write)2 Bytes9.1 temperature (°C)CWTU
145Supply air temperature set - summer integration (write)2 Bytes9.1 temperature (°C)CWTU
146n.u.2 Bytes9.1 temperature (°C)CWTU
147n.u.2 Bytes9.1 temperature (°C)CWTU
148n.u.2 Bytes9.1 temperature (°C)CWTU
149n.u.2 Bytes9.1 temperature (°C)CWTU
150Start clean air definition test (write)1 Bit1.10 start/stopCWTU
151n.u.2 Bytes9.1 temperature (°C)CWTU
152Filters alarm reset (write)1 Bit1.15 resetCWTU
153Heartbit (write)2 Bytes7.1 pulsesCWTU
154n.u.2 Bytes9.1 temperature (°C)CWTU
155n.u.2 Bytes9.1 temperature (°C)CWTU
156n.u.2 Bytes9.1 temperature (°C)CWTU
157n.u.2 Bytes9.1 temperature (°C)CWTU
158n.u.2 Bytes9.1 temperature (°C)CWTU
159Block hours missed filter change (write)4 Bytes13.100 time lag (s)CWTU
160Filters hours alarm threshold (read)4 Bytes13.100 time lag (s)CRT
161Filters hours limit pre (read)4 Bytes13.100 time lag (s)CRT
162Supply air temperature set - summer (read)2 Bytes9.1 temperature (°C)CRT
162Supply air temperature set (read)2 Bytes9.1 temperature (°C)CRT
163n.u.2 Bytes9.1 temperature (°C)CRT
164Renewal flow rate set (read)2 Bytes9.9 air flow (m³/h)CRT
164Flow rate V2 - rated (read)2 Bytes9.9 air flow (m³/h)CRT
165Supply flow rate set - winter (read)2 Bytes9.9 air flow (m³/h)CRT
165Supply flow rate set for dehumidification (read)2 Bytes9.9 air flow (m³/h)CRT
165Recirculation mode flow rate (read)2 Bytes9.9 air flow (m³/h)CRT
165Flow rate V4 - dehumid (read)2 Bytes9.9 air flow (m³/h)CRT
166Boost flow rate set (read)2 Bytes9.9 air flow (m³/h)CRT
166Flow rate V3 - boost (read)2 Bytes9.9 air flow (m³/h)CRT
167Free-cooling flow rate set (read)2 Bytes9.9 air flow (m³/h)CRT
168Economy reduction percentage (read)1 Byte5.1 percentage (0..100%)CRT
168Flow rate V1 - eco (read)2 Bytes9.9 air flow (m³/h)CRT
169Boost deactivation delay (read)2 Bytes7.6 time (min)CRT
170Free-cooling temperature set (read)2 Bytes9.1 temperature (°C)CRT
170Temperature FC (read)2 Bytes9.1 temperature (°C)CRT
171Supply air temperature set - winter (read)2 Bytes9.1 temperature (°C)CRT
172Supply flow rate set - summer (read)2 Bytes9.9 air flow (m³/h)CRT
172Delta temperature FC (read)2 Bytes9.2 temperature difference (K)CRT
173Extraction flow rate set - summer (read)2 Bytes9.9 air flow (m³/h)CRT
173Antifreeze temperature set - renewal antifreeze protection (read)2 Bytes9.1 temperature (°C)CRT
174Extraction flow rate set - winter (read)2 Bytes9.9 air flow (m³/h)CRT
174Exhaust dehumidification flow rate (read)2 Bytes9.9 air flow (m³/h)CRT
175Supply air temperature set - winter integration (read)2 Bytes9.1 temperature (°C)CRT
176Supply air temperature set - summer integration (read)2 Bytes9.1 temperature (°C)CRT
177n.u.2 Bytes9.1 temperature (°C)CRT
178n.u.2 Bytes9.1 temperature (°C)CRT
179n.u.2 Bytes9.1 temperature (°C)CRT
180n.u.2 Bytes9.1 temperature (°C)CRT
181Start clean air definition test (read)1 Bit1.10 start/stopCRT
182n.u.2 Bytes9.1 temperature (°C)CRT
183Filters alarm reset (read)1 Bit1.15 resetCRT
184Heartbit (read)2 Bytes7.1 pulsesCRT
185n.u.2 Bytes9.1 temperature (°C)CRT
186n.u.2 Bytes9.1 temperature (°C)CRT
187n.u.2 Bytes9.1 temperature (°C)CRT
188n.u.2 Bytes9.1 temperature (°C)CRT
189n.u.2 Bytes9.1 temperature (°C)CRT
190Block hours missed filter change (read)4 Bytes13.100 time lag (s)CRT
191Controls for mechanical ventilation system (write)2 BytesDPT.7CWTU
192Controls for mechanical ventilation system (read)2 BytesDPT.7CRT
Parameters (38)
ParameterTypeDefault
Inflow temperature (summer)float 0…990
Machine typelistUAP...PDC
Update user configuration on downloadlistno
Inflow temperaturefloat 0…990
Renewal flow ratefloat 0…990
Input flow rate (winter)float 0…990
Dehumidification flow ratefloat 0…990
Recirculation mode flow ratefloat 0…990
Boost flow ratefloat 0…990
Free-cooling flow ratefloat 0…990
Economy reduction percentagefloat 0…990
Boost deactivation delayfloat 0…990
Free-cooling temperaturefloat 0…990
Inflow temperature (winter)float 0…990
Input flow rate (summer)float 0…990
Extraction flow rate (summer)float 0…990
Extraction flow rate (winter)float 0…990
Antifreeze temperaturefloat 0…990
Exhaust dehumidification flow ratefloat 0…990
Enable installer objects parameterslistno
Update technician configuration on downloadlistno
Winter integration temperaturefloat 0…990
Delay to power ONtime10
Cyclical sendingtime600
Min. sending intervallistdisabled
Min. change to be transmittedlistdisabled
Delay to status sending at power ONtime10
Status cyclical sendingtime600
Delay to alarm threshold sending at power ONtime10
Alarm threshold cyclical sendingtime600
Summer integration temperaturefloat 0…990
Flow rate V1 (ECO)float 0…990
FC temperaturefloat 0…990
Flow rate V2 (RATED)float 0…990
Flow rate V4 (DEHUMID)float 0…990
Flow rate V3 (BOOST)float 0…990
Delta temperature FCfloat 0…990
AlwaysNolistno

Version history

ApplicationApp noFingerprintFirst seenSizeFile
APEKBO1TPRMA 0.2 latest$003F27572026-11-25135 KBDownload

About this file

This is the official ETS product database for the Ekinex S.p.A. Modbus / KNX interface for RDZ air handling units (EK-BO1-TP-RMA), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.