| 1 | Connected ventilation unit | | 1 Bit | 1.2 boolean | CRT |
| 2 | OFF ventilation unit | | 1 Bit | 1.1 switch | CRWT |
| 3 | Machine selection alarm | | 1 Bit | 1.5 alarm | CRT |
| 4 | Modbus communication alarm | | 1 Bit | 1.5 alarm | CRT |
| 5 | Unit type | | 2 Bytes | DPT.7 | CRT |
| 6 | Version | | 2 Bytes | DPT.7 | CRT |
| 7 | Release | | 2 Bytes | DPT.7 | CRT |
| 8 | Installation right/left | | 2 Bytes | DPT.7 | CRT |
| 9 | n.u. | | 2 Bytes | 7.1 pulses | CRT |
| 10 | Communication timeout | | 2 Bytes | 7.5 time (s) | CRWT |
| 11 | n.u. | | 2 Bytes | 7.1 pulses | CRT |
| 12 | Input water temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 13 | Overheating temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 14 | Evaporator temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 15 | Condensator temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 15 | Post-heating condensator temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 16 | Heat sink temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 17 | External air temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 18 | Inflow air temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 19 | Extraction air temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 19 | Post-heating undercooling temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 20 | Exhaust air temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 20 | Heat sink undercooling temperature | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 21 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 22 | Supply fan rotation turns | | 2 Bytes | DPT.7 | CRT |
| 22 | RPM Fan1 | | 2 Bytes | DPT.7 | CRT |
| 23 | Exhaust fan rotation turns | | 2 Bytes | DPT.7 | CRT |
| 23 | RPM Fan2 | | 2 Bytes | DPT.7 | CRT |
| 24 | Air pressure transducer | | 2 Bytes | 9.6 pressure (Pa) | CRT |
| 24 | Flowmeter 1 | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 25 | Integration valve | | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 25 | Flowmeter 2 | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 26 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 27 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 28 | Pre-treatment valve position | | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 29 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 30 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 31 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 32 | Filters hours alarm threshold (write) | | 4 Bytes | 13.100 time lag (s) | CWT |
| 33 | Filters hours limit pre (write) | | 4 Bytes | 13.100 time lag (s) | CWT |
| 34 | Filters operating hours | | 4 Bytes | 13.100 time lag (s) | CRT |
| 35 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 36 | Dehumidification request ID status | | 1 Bit | 1.1 switch | CRT |
| 37 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 38 | Renewal ID status | | 1 Bit | 1.1 switch | CRT |
| 39 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 40 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 41 | Boost request ID status | | 1 Bit | 1.1 switch | CRT |
| 42 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 43 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 44 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 45 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 46 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 47 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 48 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 49 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 50 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 51 | Damaged/disconnected air delivery temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 51 | Error NTC1 | | 1 Bit | 1.5 alarm | CRT |
| 52 | Damaged/disconnected summer supply exchanger temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 52 | Damaged/disconnected air extraction temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 52 | Damaged/disconnected evaporator temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 52 | Error NTC4 | | 1 Bit | 1.5 alarm | CRT |
| 53 | Damaged/disconnected air exhaust temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 53 | Damaged/disconnected air extraction temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 53 | Damaged/disconnected undercooling temperature probe B | | 1 Bit | 1.5 alarm | CRT |
| 53 | Error NTC2 | | 1 Bit | 1.5 alarm | CRT |
| 54 | Damaged/disconnected exhaust temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 54 | Damaged/disconnected heat sink temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 55 | Damaged/disconnected undercooling temperature probe A | | 1 Bit | 1.5 alarm | CRT |
| 56 | Damaged/disconnected water temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 57 | Damaged/disconnected exhaust condensator probe | | 1 Bit | 1.5 alarm | CRT |
| 58 | Damaged/disconnected external air temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 58 | Error NTC3 | | 1 Bit | 1.5 alarm | CRT |
| 59 | Damaged/disconnected summer exhaust exchanger temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 59 | Damaged/disconnected condenser temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 59 | Damaged/disconnected post-heating condenser temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 59 | Gas transducer damaged/disconnected | | 1 Bit | 1.5 alarm | CRT |
| 60 | Air pressure transducer damaged/disconnected | | 1 Bit | 1.5 alarm | CRT |
| 60 | Air transducer A damaged/disconnected | | 1 Bit | 1.5 alarm | CRT |
| 60 | Flux1 | | 1 Bit | 1.5 alarm | CRT |
| 61 | Air transducer B damaged/disconnected | | 1 Bit | 1.5 alarm | CRT |
| 61 | Flux2 | | 1 Bit | 1.5 alarm | CRT |
| 62 | External air flowmeter | | 1 Bit | 1.5 alarm | CRT |
| 63 | n.u. | | 1 Bit | 1.5 alarm | CRT |
| 64 | Damaged/disconnected duct temperature probe | | 1 Bit | 1.5 alarm | CRT |
| 65 | n.u. | | 1 Bit | 1.5 alarm | CRT |
| 66 | n.u. | | 1 Bit | 1.5 alarm | CRT |
| 67 | Gas shortage alarm | | 1 Bit | 1.5 alarm | CRT |
| 67 | Gas low pressure alarm | | 1 Bit | 1.5 alarm | CRT |
| 68 | Condensation temperature alarm | | 1 Bit | 1.5 alarm | CRT |
| 68 | Gas high pressure alarm | | 1 Bit | 1.5 alarm | CRT |
| 69 | Gas high temperature alarm | | 1 Bit | 1.5 alarm | CRT |
| 69 | Compressor high temperature alarm | | 1 Bit | 1.5 alarm | CRT |
| 70 | Communication alarm | | 1 Bit | 1.5 alarm | CRT |
| 71 | n.u. | | 1 Bit | 1.5 alarm | CRT |
| 72 | Antifreeze alarm (coil protection) | | 1 Bit | 1.5 alarm | CRT |
| 72 | Defrosting alarm | | 1 Bit | 1.5 alarm | CRT |
| 72 | Water high temperature alarm | | 1 Bit | 1.5 alarm | CRT |
| 73 | Input ventilator alarm | | 1 Bit | 1.5 alarm | CRT |
| 73 | Error fan1 | | 1 Bit | 1.5 alarm | CRT |
| 74 | Extraction ventilator alarm | | 1 Bit | 1.5 alarm | CRT |
| 74 | Error fan2 | | 1 Bit | 1.5 alarm | CRT |
| 75 | Defrosting alarm (evaporation low temp.) | | 1 Bit | 1.5 alarm | CRT |
| 76 | n.u. | | 1 Bit | 1.5 alarm | CRT |
| 77 | Dirty supply filter alarm | | 1 Bit | 1.5 alarm | CRT |
| 78 | Dirty exhaust filter alarm | | 1 Bit | 1.5 alarm | CRT |
| 79 | No filter change alarm | | 1 Bit | 1.5 alarm | CRT |
| 80 | n.u. | | 1 Bit | 1.5 alarm | CRT |
| 81 | n.u. | | 1 Bit | 1.5 alarm | CRT |
| 82 | n.u. | | 1 Bit | 1.5 alarm | CRT |
| 83 | Season selection via bus | | 1 Bit | 1.1 switch | CWTU |
| 84 | Dehumidification request | | 1 Bit | 1.1 switch | CWTU |
| 84 | V4 dehumidification | | 1 Bit | 1.1 switch | CWTU |
| 85 | Recirculation mode request | | 1 Bit | 1.1 switch | CWTU |
| 86 | Renewal request | | 1 Bit | 1.1 switch | CWTU |
| 86 | Renewal request (Speed 2) | | 1 Bit | 1.1 switch | CWTU |
| 86 | V2 rated | | 1 Bit | 1.1 switch | CWTU |
| 87 | n.u. | | 1 Bit | 1.1 switch | CWTU |
| 88 | Free-Cooling forced request | | 1 Bit | 1.1 switch | CWTU |
| 88 | FC | | 1 Bit | 1.1 switch | CWTU |
| 89 | Boost request | | 1 Bit | 1.1 switch | CWTU |
| 89 | Boost request (Speed 3) | | 1 Bit | 1.1 switch | CWTU |
| 89 | V3 boost | | 1 Bit | 1.1 switch | CWTU |
| 90 | Thermal integration request | | 1 Bit | 1.1 switch | CWTU |
| 91 | H2O valve control enabling | | 1 Bit | 1.1 switch | CWTU |
| 92 | ECONOMY request | | 1 Bit | 1.1 switch | CWTU |
| 92 | ECONOMY request (Speed 1) | | 1 Bit | 1.1 switch | CWTU |
| 92 | V1 eco | | 1 Bit | 1.1 switch | CWTU |
| 93 | Auto FC stop | | 1 Bit | 1.1 switch | CWTU |
| 94 | n.u. | | 1 Bit | 1.1 switch | CWTU |
| 95 | n.u. | | 1 Bit | 1.1 switch | CWTU |
| 96 | n.u. | | 1 Bit | 1.1 switch | CWTU |
| 97 | n.u. | | 1 Bit | 1.1 switch | CWTU |
| 98 | n.u. | | 1 Bit | 1.1 switch | CWTU |
| 99 | Season | | 1 Bit | 1.1 switch | CRT |
| 100 | Dehumidification active | | 1 Bit | 1.1 switch | CRT |
| 100 | V4 dehumidification | | 1 Bit | 1.1 switch | CRT |
| 101 | Recirculation mode active | | 1 Bit | 1.1 switch | CRT |
| 102 | Renewal active | | 1 Bit | 1.1 switch | CRT |
| 102 | V2 rated | | 1 Bit | 1.1 switch | CRT |
| 103 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 104 | Free-cooling active | | 1 Bit | 1.1 switch | CRT |
| 104 | FC | | 1 Bit | 1.1 switch | CRT |
| 105 | Boost active | | 1 Bit | 1.1 switch | CRT |
| 105 | V3 boost | | 1 Bit | 1.1 switch | CRT |
| 106 | Thermal integration active | | 1 Bit | 1.1 switch | CRT |
| 107 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 108 | Economy call | | 1 Bit | 1.1 switch | CRT |
| 108 | V1 eco | | 1 Bit | 1.1 switch | CRT |
| 109 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 110 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 111 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 112 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 113 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 114 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 115 | Antifreeze cycle in progress | | 1 Bit | 1.1 switch | CRT |
| 115 | Defrost function in progress | | 1 Bit | 1.1 switch | CRT |
| 116 | Drain-trap cycle in progress | | 1 Bit | 1.1 switch | CRT |
| 117 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 118 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 119 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 120 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 121 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 122 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 123 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 124 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 125 | Supply filter pre-alarm | | 1 Bit | 1.1 switch | CRT |
| 126 | Exhaust filter pre-alarm | | 1 Bit | 1.1 switch | CRT |
| 127 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 128 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 129 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 130 | n.u. | | 1 Bit | 1.1 switch | CRT |
| 131 | Supply air temperature set - summer (write) | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 131 | Supply air temperature set (write) | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 132 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 133 | Renewal flow rate set (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 133 | Flow rate V2 - rated (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 134 | Supply flow rate set - winter (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 134 | Supply flow rate set for dehumidification (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 134 | Flow rate V4 - dehumid (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 134 | Recirculation mode flow rate (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 135 | Boost flow rate set (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 135 | Flow rate V3 - boost (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 136 | Free-cooling flow rate set (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 137 | Economy reduction percentage (write) | | 1 Byte | 5.1 percentage (0..100%) | CWTU |
| 137 | Flow rate V1 - eco (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 138 | Boost deactivation delay (write) | | 2 Bytes | 7.6 time (min) | CWTU |
| 139 | Free-cooling temperature set (write) | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 139 | Temperature FC (write) | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 140 | Supply air temperature set - winter (write) | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 141 | Supply flow rate set - summer (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 141 | Delta temperature FC (write) | | 2 Bytes | 9.2 temperature difference (K) | CWTU |
| 142 | Extraction flow rate set - summer (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 142 | Antifreeze temperature set - renewal antifreeze protection (write) | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 143 | Extraction flow rate set - winter (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 143 | Exhaust dehumidification flow rate (write) | | 2 Bytes | 9.9 air flow (m³/h) | CWTU |
| 144 | Supply air temperature set - winter integration (write) | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 145 | Supply air temperature set - summer integration (write) | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 146 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 147 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 148 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 149 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 150 | Start clean air definition test (write) | | 1 Bit | 1.10 start/stop | CWTU |
| 151 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 152 | Filters alarm reset (write) | | 1 Bit | 1.15 reset | CWTU |
| 153 | Heartbit (write) | | 2 Bytes | 7.1 pulses | CWTU |
| 154 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 155 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 156 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 157 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 158 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 159 | Block hours missed filter change (write) | | 4 Bytes | 13.100 time lag (s) | CWTU |
| 160 | Filters hours alarm threshold (read) | | 4 Bytes | 13.100 time lag (s) | CRT |
| 161 | Filters hours limit pre (read) | | 4 Bytes | 13.100 time lag (s) | CRT |
| 162 | Supply air temperature set - summer (read) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 162 | Supply air temperature set (read) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 163 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 164 | Renewal flow rate set (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 164 | Flow rate V2 - rated (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 165 | Supply flow rate set - winter (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 165 | Supply flow rate set for dehumidification (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 165 | Recirculation mode flow rate (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 165 | Flow rate V4 - dehumid (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 166 | Boost flow rate set (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 166 | Flow rate V3 - boost (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 167 | Free-cooling flow rate set (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 168 | Economy reduction percentage (read) | | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 168 | Flow rate V1 - eco (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 169 | Boost deactivation delay (read) | | 2 Bytes | 7.6 time (min) | CRT |
| 170 | Free-cooling temperature set (read) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 170 | Temperature FC (read) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 171 | Supply air temperature set - winter (read) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 172 | Supply flow rate set - summer (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 172 | Delta temperature FC (read) | | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 173 | Extraction flow rate set - summer (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 173 | Antifreeze temperature set - renewal antifreeze protection (read) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 174 | Extraction flow rate set - winter (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 174 | Exhaust dehumidification flow rate (read) | | 2 Bytes | 9.9 air flow (m³/h) | CRT |
| 175 | Supply air temperature set - winter integration (read) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 176 | Supply air temperature set - summer integration (read) | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 177 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 178 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 179 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 180 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 181 | Start clean air definition test (read) | | 1 Bit | 1.10 start/stop | CRT |
| 182 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 183 | Filters alarm reset (read) | | 1 Bit | 1.15 reset | CRT |
| 184 | Heartbit (read) | | 2 Bytes | 7.1 pulses | CRT |
| 185 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 186 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 187 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 188 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 189 | n.u. | | 2 Bytes | 9.1 temperature (°C) | CRT |
| 190 | Block hours missed filter change (read) | | 4 Bytes | 13.100 time lag (s) | CRT |
| 191 | Controls for mechanical ventilation system (write) | | 2 Bytes | DPT.7 | CWTU |
| 192 | Controls for mechanical ventilation system (read) | | 2 Bytes | DPT.7 | CRT |