| 0 | Compressor speed | Heat pump | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 0 | Operation mode E-heater | Auxiliary heater | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 0 | Hot water temperature middle/bottom | Hot water | 2 Bytes | 9.1 temperature (°C) | CRT |
| 0 | Consumption heat pump | Energy | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 1 | Heartbeat telegram | General setting | 1 Bit | 1.3 enable | CT |
| 1 | Refrigerant circuit state | Heat pump | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 1 | Operation mode E-heater (off) | Auxiliary heater | 1 Bit | 1.1 switch | CRT |
| 1 | Remote room temperature | Heating circuit {{HeatingNumber}} | 2 Bytes | 9.1 temperature (°C) | CRT |
| 1 | Hot water temperature top (optional) | Hot water | 2 Bytes | 9.1 temperature (°C) | CRT |
| 1 | Consumption auxilary heater | Energy | 4 Bytes | 13.13 active energy (kWh) | CRT |
| 2 | Diagnosis | General setting | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 2 | Refrigerant circuit state (off) | Heat pump | 1 Bit | 1.1 switch | CRT |
| 2 | Operation mode E-heater (heating) | Auxiliary heater | 1 Bit | 1.1 switch | CRT |
| 2 | Set desired room temperature | Heating circuit {{HeatingNumber}} | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 2 | Current hot water level | Hot water | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 2 | Runtime heating system | Energy | 4 Bytes | 13.100 time lag (s) | CRT |
| 3 | Brand name | Heat system | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 3 | Refrigerant circuit state (heating) | Heat pump | 1 Bit | 1.1 switch | CRT |
| 3 | Operation mode E-heater (dhw) | Auxiliary heater | 1 Bit | 1.1 switch | CRT |
| 3 | Heating operation mode | Heating circuit {{HeatingNumber}} | 1 Byte | 20.102 HVAC mode | CRWTU |
| 3 | Current hot water level (off) | Hot water | 1 Bit | 1.1 switch | CRT |
| 4 | Hydraulic unit name | Heat system | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 4 | Refrigerant circuit state (cooling) | Heat pump | 1 Bit | 1.1 switch | CRT |
| 4 | Operation mode E-heater (pool) | Auxiliary heater | 1 Bit | 1.1 switch | CRT |
| 4 | Cooling operation mode | Heating circuit {{HeatingNumber}} | 1 Byte | 20.102 HVAC mode | CRWTU |
| 4 | Current hot water level (low) | Hot water | 1 Bit | 1.1 switch | CRT |
| 5 | Heat pump unit name | Heat system | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 5 | Refrigerant circuit state (dhw) | Heat pump | 1 Bit | 1.1 switch | CRT |
| 5 | Operation mode E-heater (defrost) | Auxiliary heater | 1 Bit | 1.1 switch | CRT |
| 5 | Current hot water level (high) | Hot water | 1 Bit | 1.1 switch | CRT |
| 6 | ODU HW version | Heat system | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 6 | Refrigerant circuit state (pool) | Heat pump | 1 Bit | 1.1 switch | CRT |
| 6 | Operation mode E-heater (pool heat) | Auxiliary heater | 1 Bit | 1.1 switch | CRT |
| 6 | Current hot water level (eco) | Hot water | 1 Bit | 1.1 switch | CRT |
| 7 | System supply flow temperature | Heat system | 2 Bytes | 9.1 temperature (°C) | CRT |
| 7 | Refrigerant circuit state (pool heat) | Heat pump | 1 Bit | 1.1 switch | CRT |
| 7 | Operation mode E-heater (alarm) | Auxiliary heater | 1 Bit | 1.1 switch | CRT |
| 7 | Set hot water operation mode | Hot water | 1 Byte | 20.103 DHW mode | CRWTU |
| 8 | Operation pressure | Heat system | 4 Bytes | 14.58 pressure (Pa) | CRT |
| 8 | Refrigerant circuit state (defrost) | Heat pump | 1 Bit | 1.1 switch | CRT |
| 8 | Set reduced level | Hot water | 1 Bit | 1.1 switch | CRWTU |
| 9 | Outdoor temperature | Heat system | 2 Bytes | 9.1 temperature (°C) | CRT |
| 9 | Refrigerant circuit state (alarm) | Heat pump | 1 Bit | 1.1 switch | CRT |
| 9 | Extra hot water mode | Hot water | 1 Bit | 1.10 start/stop | CRWTU |
| 10 | State "Away" mode | Heat system | 1 Bit | 1.1 switch | CRT |
| 10 | Low-noise operation state | Heat pump | 1 Bit | 1.11 state | CRT |
| 10 | Set extra hot water duration | Hot water | 2 Bytes | 7.6 time (min) | CRWTU |
| 11 | State "Holiday" mode | Heat system | 1 Bit | 1.1 switch | CRT |
| 11 | External input 1 state | Heat pump | 1 Bit | 1.1 switch | CRT |
| 11 | Remaining time extra hot water | Hot water | 2 Bytes | 7.6 time (min) | CRT |
| 12 | Errors state | Heat system | 1 Bit | 1.5 alarm | CRT |
| 12 | External input 2 state | Heat pump | 1 Bit | 1.1 switch | CRT |
| 13 | Active errors | Heat system | 14 Bytes | 16.0 Character String (ASCII) | CRT |
| 13 | External input 3 state | Heat pump | 1 Bit | 1.1 switch | CRT |
| 14 | Summer/winter changeover operation mode | Heat system | 1 Byte | 20.105 HVAC control mode | CRWTU |
| 14 | External input 4 state | Heat pump | 1 Bit | 1.1 switch | CRT |
| 15 | Threshold for season switch to heating | Heat system | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 15 | PV system active mode state | Heat pump | 1 Bit | 1.1 switch | CRT |
| 16 | Threshold for season switch to coolting | Heat system | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 16 | Energy provider block state | Heat pump | 1 Bit | 1.11 state | CRT |
| 17 | Min threshold limit for season switch to heating | Heat system | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 17 | External power limitation state | Heat pump | 1 Bit | 1.1 switch | CRT |
| 18 | Max threshold limit for season switch to heating | Heat system | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 18 | EEBus power limitation state | Heat pump | 1 Bit | 1.1 switch | CRT |
| 19 | Min threshold limit for season switch to cooling | Heat system | 2 Bytes | 9.1 temperature (°C) | CRWTU |
| 20 | Max threshold limit for season switch to cooling | Heat system | 2 Bytes | 9.1 temperature (°C) | CRWTU |