KNX Database
Bosch Thermotechnik GmbH 7724002067 KNX 20

KNX 20 7724002067

Bosch Thermotechnik GmbH · Order number 7724002067 · HVAC › Accessories

BOSCH KNX20-KNX

Download .knxprod KNX 20 Gateway 1.0 · 126 KB

Product

ManufacturerBosch Thermotechnik GmbH
Product nameKNX 20
Order number7724002067
HardwareKNX 20
MediumTwisted Pair
Bus current (mA)30
Rail mountedYes
RegistrationCertified · 2026-06-19
Languagesen-US, de-DE
Catalog entryM-0059_H-7724002067-16_HP-7010-10-C902_CI-7724002067-1
FingerprintC902
SHA-2563a133e80b48fa8ef3165cd4e9c2bfba5beef968489a6ea2ee8fb39ae32ba64cf
First seen2026-11-25
MarketsAustria, China, Czech Republic, Estonia, Germany, Italy, Latvia, Lithuania, Poland, Slovakia, Switzerland

Application program: KNX 20 Gateway 1.0

Application number$7010
Version1.0
Mask versionMV-07B0 (System B)
KNX Data SecureYes
Minimum ETS version5.0
Parameters84
Group objects66
Group objects (66)
NoNameFunctionSizeDPTFlags
0Compressor speedHeat pump1 Byte5.1 percentage (0..100%)CRT
0Operation mode E-heaterAuxiliary heater14 Bytes16.0 Character String (ASCII)CRT
0Hot water temperature middle/bottomHot water2 Bytes9.1 temperature (°C)CRT
0Consumption heat pumpEnergy4 Bytes13.13 active energy (kWh)CRT
1Heartbeat telegramGeneral setting1 Bit1.3 enableCT
1Refrigerant circuit stateHeat pump14 Bytes16.0 Character String (ASCII)CRT
1Operation mode E-heater (off)Auxiliary heater1 Bit1.1 switchCRT
1Remote room temperatureHeating circuit {{HeatingNumber}}2 Bytes9.1 temperature (°C)CRT
1Hot water temperature top (optional)Hot water2 Bytes9.1 temperature (°C)CRT
1Consumption auxilary heaterEnergy4 Bytes13.13 active energy (kWh)CRT
2DiagnosisGeneral setting14 Bytes16.0 Character String (ASCII)CRT
2Refrigerant circuit state (off)Heat pump1 Bit1.1 switchCRT
2Operation mode E-heater (heating)Auxiliary heater1 Bit1.1 switchCRT
2Set desired room temperatureHeating circuit {{HeatingNumber}}2 Bytes9.1 temperature (°C)CRWTU
2Current hot water levelHot water14 Bytes16.0 Character String (ASCII)CRT
2Runtime heating systemEnergy4 Bytes13.100 time lag (s)CRT
3Brand nameHeat system14 Bytes16.0 Character String (ASCII)CRT
3Refrigerant circuit state (heating)Heat pump1 Bit1.1 switchCRT
3Operation mode E-heater (dhw)Auxiliary heater1 Bit1.1 switchCRT
3Heating operation modeHeating circuit {{HeatingNumber}}1 Byte20.102 HVAC modeCRWTU
3Current hot water level (off)Hot water1 Bit1.1 switchCRT
4Hydraulic unit nameHeat system14 Bytes16.0 Character String (ASCII)CRT
4Refrigerant circuit state (cooling)Heat pump1 Bit1.1 switchCRT
4Operation mode E-heater (pool)Auxiliary heater1 Bit1.1 switchCRT
4Cooling operation modeHeating circuit {{HeatingNumber}}1 Byte20.102 HVAC modeCRWTU
4Current hot water level (low)Hot water1 Bit1.1 switchCRT
5Heat pump unit nameHeat system14 Bytes16.0 Character String (ASCII)CRT
5Refrigerant circuit state (dhw)Heat pump1 Bit1.1 switchCRT
5Operation mode E-heater (defrost)Auxiliary heater1 Bit1.1 switchCRT
5Current hot water level (high)Hot water1 Bit1.1 switchCRT
6ODU HW versionHeat system14 Bytes16.0 Character String (ASCII)CRT
6Refrigerant circuit state (pool)Heat pump1 Bit1.1 switchCRT
6Operation mode E-heater (pool heat)Auxiliary heater1 Bit1.1 switchCRT
6Current hot water level (eco)Hot water1 Bit1.1 switchCRT
7System supply flow temperatureHeat system2 Bytes9.1 temperature (°C)CRT
7Refrigerant circuit state (pool heat)Heat pump1 Bit1.1 switchCRT
7Operation mode E-heater (alarm)Auxiliary heater1 Bit1.1 switchCRT
7Set hot water operation modeHot water1 Byte20.103 DHW modeCRWTU
8Operation pressureHeat system4 Bytes14.58 pressure (Pa)CRT
8Refrigerant circuit state (defrost)Heat pump1 Bit1.1 switchCRT
8Set reduced levelHot water1 Bit1.1 switchCRWTU
9Outdoor temperatureHeat system2 Bytes9.1 temperature (°C)CRT
9Refrigerant circuit state (alarm)Heat pump1 Bit1.1 switchCRT
9Extra hot water modeHot water1 Bit1.10 start/stopCRWTU
10State "Away" modeHeat system1 Bit1.1 switchCRT
10Low-noise operation stateHeat pump1 Bit1.11 stateCRT
10Set extra hot water durationHot water2 Bytes7.6 time (min)CRWTU
11State "Holiday" modeHeat system1 Bit1.1 switchCRT
11External input 1 stateHeat pump1 Bit1.1 switchCRT
11Remaining time extra hot waterHot water2 Bytes7.6 time (min)CRT
12Errors stateHeat system1 Bit1.5 alarmCRT
12External input 2 stateHeat pump1 Bit1.1 switchCRT
13Active errorsHeat system14 Bytes16.0 Character String (ASCII)CRT
13External input 3 stateHeat pump1 Bit1.1 switchCRT
14Summer/winter changeover operation modeHeat system1 Byte20.105 HVAC control modeCRWTU
14External input 4 stateHeat pump1 Bit1.1 switchCRT
15Threshold for season switch to heatingHeat system2 Bytes9.1 temperature (°C)CRWTU
15PV system active mode stateHeat pump1 Bit1.1 switchCRT
16Threshold for season switch to cooltingHeat system2 Bytes9.1 temperature (°C)CRWTU
16Energy provider block stateHeat pump1 Bit1.11 stateCRT
17Min threshold limit for season switch to heatingHeat system2 Bytes9.1 temperature (°C)CRWTU
17External power limitation stateHeat pump1 Bit1.1 switchCRT
18Max threshold limit for season switch to heatingHeat system2 Bytes9.1 temperature (°C)CRWTU
18EEBus power limitation stateHeat pump1 Bit1.1 switchCRT
19Min threshold limit for season switch to coolingHeat system2 Bytes9.1 temperature (°C)CRWTU
20Max threshold limit for season switch to coolingHeat system2 Bytes9.1 temperature (°C)CRWTU
Parameters (69)
ParameterTypeDefault
Heating circuit 2listDisable
Heating circuit 3listDisable
Heating circuit 4listDisable
Hot waterlistDisable
EnergylistDisable
Heating systemlistDisable
Heat pumplistDisable
Auxiliary heaterlistDisable
Heating circuit 1listDisable
System delay (s)unsignedInt 0…2551
Heartbeat telegramlistDisable
Send interval (s)unsignedInt 1…655352
DiagnosislistDisable
Language of communication textlistEnglish
Product_informationlistDisable
Hydraulic unit namelistDisable
Heat pump unit namelistDisable
Brand namelistDisable
ODU HW versionlistDisable
System supply flow temperaturelistDisable
Operation pressurelistDisable
Outdoor temperaturelistDisable
State "Away" modelistDisable
State "Holiday" modelistDisable
Errors statelistDisable
Active errorslistDisable
Summer/winter changeover operation modelistDisable
Heating cooling modelistAutomatic (only for Einstein)
Threshold for automatic season switch to heatinglistDisable
Threshold heat temperaturelist10 ℃
Threshold for automatic season switch to coolinglistDisable
Threshold cool temperaturelist15 ℃
Send on change oflistDo not send automatically
Sending cyclelistDo not send cyclically
Threshold limit for automatic season switch to heatinglistDisable
Threshold limit for automatic season switch to coolinglistDisable
Compressor speedlistDisable
Refrigerant circuit statelistDisable
Low-noise operation statelistDisable
External input 1 statelistDisable
External input 2 statelistDisable
External input 3 statelistDisable
External input 4 statelistDisable
PV system active mode statelistDisable
Energy provider block statelistDisable
External power limitation statelistDisable
EEBus power limitation statelistDisable
Operation mode E-heaterlistDisable
Remote control installedlistDisable
Set desired room temperaturelistDisable
Heating operation modelistDisable
Operation modelistON
Cooling operation modelistDisable
Temperature setlist0 ℃
Hot water temperature middle/bottomlistDisable
Hot water temperature top (optional)listDisable
Current hot water levellistDisable
Set hot water operation modelistDisable
Extra hot water modelistDisable
Operation modelistStart
Set extra hot water durationlistDisable
Set time (hour)list0 h
Remaining time extra hot waterlistDisable
Operation modelistLow
Set time (minute)list15 min
Consumption heat pumplistDisable
Consumption auxilary heaterlistDisable
Runtime heating systemlistDisable
Total runtime of e-heaterlistDisable

Version history

ApplicationApp noFingerprintFirst seenSizeFile
KNX 20 Gateway 1.0 latest$7010C9022026-11-25126 KBDownload

About this file

This is the official ETS product database for the Bosch Thermotechnik GmbH KNX 20 (7724002067), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.