KNX Database

Auro KNX 180-02

BASALTE · Order number 180-02 · Auro

Download .knxprod Auro KNX app v1.1 1.1 · 98 KB

Product

ManufacturerBASALTE
Product nameAuro KNX
Order number180-02
HardwareAuro 180-02
MediumTwisted Pair
Bus current (mA)10
Rail mountedNo
RegistrationCertified · 2012-03-07
Languagesnl-NL, en-US
Catalog entryM-0081_H-GeneratedNumber.2D22017-0_HP-FE01-11-C7BE_CI-180.2D02-1
FingerprintC7BE
SHA-256eb20614311783b453b14675fba67a6f091909adffc1a4d742c50cfe1149f0de2
First seen2026-11-25
Markets53 markets

Application program: Auro KNX app v1.1 1.1

Application number$FE01
Version1.1
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version3.0f
Parameters466
Group objects22
Group objects (22)
NoNameFunctionSizeDPTFlags
0lighton/off (output)1 Bit1.1 switchCT
1lightdim value (output)1 Byte5.1 percentage (0..100%)CT
2scenescene number (output)1 ByteCT
3all offoff (output)1 Bit1.1 switchCT
4motionon/off (output)1 Bit1.1 switchCT
5day/nighton/off (input)1 Bit1.1 switchCW
6light threshold statuson/off (output)1 Bit1.1 switchCT
7blockingon/off (input)1 Bit1.1 switchCW
8triggeron/off (input)1 Bit1.1 switchCW
9triggeron/off (output)1 Bit1.1 switchCT
10light levellux value (output)2 Bytes9.4 lux (Lux)CRT
11temperatureinternal value (output)2 Bytes9.1 temperature (°C)CRT
12light thresholdlux value (input)2 Bytes9.4 lux (Lux)CW
13light threshold during daylux value (input)2 Bytes9.4 lux (Lux)CW
14light threshold during nightlux value (input)2 Bytes9.4 lux (Lux)CW
15ventilationon/off (output)1 Bit1.1 switchCT
16light statuson/off (input)1 Bit1.1 switchCW
17timeoutseconds (input)2 Bytes7.1 pulsesCW
18timeout during dayseconds (input)2 Bytes7.1 pulsesCW
19timeout during nightseconds (input)2 Bytes7.1 pulsesCW
20led feedbackon/off (input)1 Bit1.1 switchCW
21heat alarmon/off (output)1 Bit1.1 switchCT
Parameters (46)
ParameterTypeDefault
functionlistsingle
seperate day and night functionlistdisable
sending on- and off- telegramliston at first detection and off after time-out
cyclic send time (sec)unsignedInt 1…6010
dependent on light sensorlistdisable
light baselist10 lux
light threshold (x light base)unsignedInt 1…105
light objectlistno light object
light threshold (x light base) at dayunsignedInt 1…105
light threshold (x light base) at nightunsignedInt 1…105
outputlistswitching
time-out to be defined by external group address (integer 2 byte value x 1 sec)listno
time baselistminutes
time (x base) between last detection and offunsignedInt 1…602
min. time between on and off (sec)unsignedInt 1…602
time (x base) between last detection and off at dayunsignedInt 1…602
time (x base) between last detection and off at nightunsignedInt 1…602
dimming value on-telegramunsignedInt 0…255255
dimming value off-telegramunsignedInt 0…2550
dimming value on-telegram during dayunsignedInt 0…255255
dimming value on-telegram during nightunsignedInt 0…255255
dimming value off-telegram during dayunsignedInt 0…2550
dimming value off-telegram during nightunsignedInt 0…2550
scene number on-telegramunsignedInt 1…641
scene number off-telegramunsignedInt 1…642
scene number on-telegram during dayunsignedInt 1…641
scene number on-telegram during nightunsignedInt 1…641
scene number off-telegram during dayunsignedInt 1…642
scene number off-telegram during nightunsignedInt 1…642
blockinglistdisable
action when blockedlistsend no telegram
time after blocking where the detector remains disabled (x 10 sec)unsignedInt 0…2550
ventilationlistdisable
time (x timebase)unsignedInt 1…602
use status feedback from light to determine time-out for ventilationlistdisable
motion objectlistno motion object
led feedbacklistled feedback
sending value (lux) of internal light sensorlistdisable
cyclic time (minutes)unsignedInt 1…601
lux compensation value (x 0.1)unsignedInt 1…10010
sending value (°C) of internal temperature sensorlistdisable
delta temp (x0.5°C)unsignedInt 1…102
compensation valuelist0°C
heat alarmlistdisable
threshold for alarm (°C)unsignedInt 30…7050
time for cyclic sending of alarm (x10 sec)unsignedInt 1…601

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Auro KNX app v1.1 1.1 latest$FE01C7BE2026-11-2598 KBDownload

About this file

This is the official ETS product database for the BASALTE Auro KNX (180-02), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from BASALTE

All BASALTE products