Heating Actuator 6-fold, KNX Secure, ADK-T6 ADK-T6
Atios AG · Order number ADK-T6 · Actuator › Fan coil
Download .knxprod Heating Actuator 6-fold KNX Secure 1.0 · 236 KB
Product
| Manufacturer | Atios AG |
|---|---|
| Product name | Heating Actuator 6-fold, KNX Secure, ADK-T6 |
| Order number | ADK-T6 |
| Product text | Heating Actuator 6-fold KNX Secure |
| Hardware | Heating Actuator 6-fold KNX Secure |
| Medium | Twisted Pair |
| Bus current (mA) | 13.5 |
| Rail mounted | Yes |
| Width (mm) | 72 |
| Registration | Certified · 2026-10-09 |
| Languages | de-DE, en-US |
| Catalog entry | M-02DC_H-AF22FE-1-O0085_HP-002A-10-75CD-O0085_CI-ADK.2DT6-1 |
| Fingerprint | 75CD |
| SHA-256 | f613d89ede1b0890cca354cc71d9bfc4a5f8da19eaedd39461743a5d9d6d7c05 |
| First seen | 2026-11-25 |
| Markets | 58 markets |
Application program: Heating Actuator 6-fold KNX Secure 1.0
| Application number | $002A |
|---|---|
| Version | 1.0 |
| Mask version | MV-07B0 (System B) |
| KNX Data Secure | Yes |
| Minimum ETS version | 5.0 |
| Parameters | 788 |
| Group objects | 261 |
Group objects (261)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 1 | General | In operation | 1 Bit | 1.1 switch | CRT |
| 2 | General | Summer/Winter mode | 1 Bit | 1.1 switch | CWTU |
| 3 | General | Status of operating voltage failure | 1 Bit | 1.5 alarm | CRT |
| 4 | Output 1-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 4 | Output 1-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 5 | Output 1-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 6 | Output 1-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 7 | Output 1-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 8 | Output 1-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 9 | Output 1-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 10 | Output 1-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 11 | Output 1-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 14 | Output 2-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 14 | Output 2-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 15 | Output 2-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 16 | Output 2-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 17 | Output 2-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 18 | Output 2-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 19 | Output 2-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 20 | Output 2-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 21 | Output 2-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 24 | Output 3-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 24 | Output 3-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 25 | Output 3-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 26 | Output 3-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 27 | Output 3-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 28 | Output 3-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 29 | Output 3-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 30 | Output 3-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 31 | Output 3-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 34 | Output 4-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 34 | Output 4-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 35 | Output 4-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 36 | Output 4-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 37 | Output 4-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 38 | Output 4-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 39 | Output 4-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 40 | Output 4-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 41 | Output 4-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 44 | Output 5-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 44 | Output 5-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 45 | Output 5-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 46 | Output 5-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 47 | Output 5-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 48 | Output 5-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 49 | Output 5-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 50 | Output 5-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 51 | Output 5-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 54 | Output 6-{{0:...}} | Control value | 1 Bit | 1.1 switch | CW |
| 54 | Output 6-{{0:...}} | Control value | 1 Byte | 5.1 percentage (0..100%) | CW |
| 55 | Output 6-{{0:...}} | Trigger valve purge | 1 Bit | 1.3 enable | CW |
| 56 | Output 6-{{0:...}} | Forced operation | 1 Bit | 1.3 enable | CW |
| 57 | Output 6-{{0:...}} | Disable | 1 Bit | 1.3 enable | CW |
| 58 | Output 6-{{0:...}} | Status of valve position | 1 Bit | 1.1 switch | CRT |
| 59 | Output 6-{{0:...}} | Control value fault | 1 Bit | 1.5 alarm | CRT |
| 60 | Output 6-{{0:...}} | Status of valve purge | 1 Bit | 1.3 enable | CRT |
| 61 | Output 6-{{0:...}} | Status of Short-circuit/Overload | 1 Bit | 1.5 alarm | CRT |
| 64 | Controller 1-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 65 | Controller 1-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 66 | Controller 1-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 67 | Controller 1-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 67 | Controller 1-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 68 | Controller 1-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 69 | Controller 1-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 70 | Controller 1-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 71 | Controller 1-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 72 | Controller 1-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 73 | Controller 1-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 74 | Controller 1-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 75 | Controller 1-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 76 | Controller 1-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 77 | Controller 1-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 78 | Controller 1-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 79 | Controller 1-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 80 | Controller 1-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 81 | Controller 1-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 82 | Controller 1-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 83 | Controller 1-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 84 | Controller 1-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 85 | Controller 1-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 86 | Controller 1-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 87 | Controller 1-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 88 | Controller 1-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 89 | Controller 1-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 90 | Controller 1-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 91 | Controller 1-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 91 | Controller 1-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 91 | Controller 1-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 91 | Controller 1-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 92 | Controller 1-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 92 | Controller 1-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 98 | Controller 2-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 99 | Controller 2-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 100 | Controller 2-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 101 | Controller 2-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 101 | Controller 2-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 102 | Controller 2-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 103 | Controller 2-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 104 | Controller 2-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 105 | Controller 2-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 106 | Controller 2-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 107 | Controller 2-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 108 | Controller 2-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 109 | Controller 2-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 110 | Controller 2-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 111 | Controller 2-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 112 | Controller 2-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 113 | Controller 2-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 114 | Controller 2-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 115 | Controller 2-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 116 | Controller 2-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 117 | Controller 2-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 118 | Controller 2-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 119 | Controller 2-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 120 | Controller 2-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 121 | Controller 2-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 122 | Controller 2-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 123 | Controller 2-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 124 | Controller 2-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 125 | Controller 2-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 125 | Controller 2-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 125 | Controller 2-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 125 | Controller 2-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 126 | Controller 2-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 126 | Controller 2-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 132 | Controller 3-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 133 | Controller 3-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 134 | Controller 3-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 135 | Controller 3-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 135 | Controller 3-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 136 | Controller 3-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 137 | Controller 3-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 138 | Controller 3-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 139 | Controller 3-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 140 | Controller 3-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 141 | Controller 3-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 142 | Controller 3-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 143 | Controller 3-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 144 | Controller 3-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 145 | Controller 3-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 146 | Controller 3-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 147 | Controller 3-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 148 | Controller 3-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 149 | Controller 3-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 150 | Controller 3-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 151 | Controller 3-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 152 | Controller 3-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 153 | Controller 3-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 154 | Controller 3-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 155 | Controller 3-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 156 | Controller 3-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 157 | Controller 3-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 158 | Controller 3-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 159 | Controller 3-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 159 | Controller 3-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 159 | Controller 3-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 159 | Controller 3-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 160 | Controller 3-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 160 | Controller 3-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 166 | Controller 4-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 167 | Controller 4-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 168 | Controller 4-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 169 | Controller 4-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 169 | Controller 4-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 170 | Controller 4-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 171 | Controller 4-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 172 | Controller 4-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 173 | Controller 4-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 174 | Controller 4-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 175 | Controller 4-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 176 | Controller 4-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 177 | Controller 4-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 178 | Controller 4-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 179 | Controller 4-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 180 | Controller 4-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 181 | Controller 4-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 182 | Controller 4-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 183 | Controller 4-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 184 | Controller 4-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 185 | Controller 4-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 186 | Controller 4-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 187 | Controller 4-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 188 | Controller 4-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 189 | Controller 4-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 190 | Controller 4-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 191 | Controller 4-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 192 | Controller 4-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 193 | Controller 4-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 193 | Controller 4-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 193 | Controller 4-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 193 | Controller 4-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 194 | Controller 4-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 194 | Controller 4-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 200 | Controller 5-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 201 | Controller 5-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 202 | Controller 5-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 203 | Controller 5-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 203 | Controller 5-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 204 | Controller 5-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 205 | Controller 5-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 206 | Controller 5-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 207 | Controller 5-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 208 | Controller 5-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 209 | Controller 5-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 210 | Controller 5-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 211 | Controller 5-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 212 | Controller 5-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 213 | Controller 5-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 214 | Controller 5-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 215 | Controller 5-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 216 | Controller 5-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 217 | Controller 5-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 218 | Controller 5-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 219 | Controller 5-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 220 | Controller 5-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 221 | Controller 5-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 222 | Controller 5-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 223 | Controller 5-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 224 | Controller 5-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 225 | Controller 5-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 226 | Controller 5-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 227 | Controller 5-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 227 | Controller 5-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 227 | Controller 5-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 227 | Controller 5-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 228 | Controller 5-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 228 | Controller 5-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 234 | Controller 6-{{0:...}} | Power on/off | 1 Bit | 1.1 switch | CRW |
| 235 | Controller 6-{{0:...}} | External temperature sensor 1 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 236 | Controller 6-{{0:...}} | External temperature sensor 2 | 2 Bytes | 9.1 temperature (°C) | CWTU |
| 237 | Controller 6-{{0:...}} | Base setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 237 | Controller 6-{{0:...}} | Current setpoint adjustment | 2 Bytes | 9.1 temperature (°C) | CW |
| 238 | Controller 6-{{0:...}} | Setpoint offset | 1 Bit | 1.7 step | CW |
| 239 | Controller 6-{{0:...}} | Float offset value | 2 Bytes | 9.2 temperature difference (K) | CW |
| 240 | Controller 6-{{0:...}} | Setpoint offset reset | 1 Bit | 1.15 reset | CW |
| 241 | Controller 6-{{0:...}} | Heating/Cooling mode | 1 Bit | 1.100 cooling/heating | CW |
| 242 | Controller 6-{{0:...}} | Operation mode | 1 Byte | 20.102 HVAC mode | CW |
| 243 | Controller 6-{{0:...}} | Comfort mode | 1 Bit | 1.3 enable | CW |
| 244 | Controller 6-{{0:...}} | Economy mode | 1 Bit | 1.3 enable | CW |
| 245 | Controller 6-{{0:...}} | Frost/Heat protection mode | 1 Bit | 1.3 enable | CW |
| 246 | Controller 6-{{0:...}} | Standby mode | 1 Bit | 1.3 enable | CW |
| 247 | Controller 6-{{0:...}} | Extended comfort mode | 1 Bit | 1.16 acknowledge | CW |
| 248 | Controller 6-{{0:...}} | Scene | 1 Byte | 18.1 scene control | CW |
| 249 | Controller 6-{{0:...}} | Window contact | 1 Bit | 1.19 window/door | CWTU |
| 250 | Controller 6-{{0:...}} | Presence detector | 1 Bit | 1.18 occupancy | CWTU |
| 251 | Controller 6-{{0:...}} | Actual temperature, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 252 | Controller 6-{{0:...}} | Base temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 253 | Controller 6-{{0:...}} | Setpoint offset, status | 2 Bytes | 9.2 temperature difference (K) | CRT |
| 254 | Controller 6-{{0:...}} | Current temperature setpoint, status | 2 Bytes | 9.1 temperature (°C) | CRT |
| 255 | Controller 6-{{0:...}} | Heating/Cooling mode, status | 1 Bit | 1.100 cooling/heating | CRT |
| 256 | Controller 6-{{0:...}} | Operation mode, status | 1 Byte | 20.102 HVAC mode | CRT |
| 257 | Controller 6-{{0:...}} | Comfort mode, status | 1 Bit | 1.3 enable | CRT |
| 258 | Controller 6-{{0:...}} | Economy mode, status | 1 Bit | 1.3 enable | CRT |
| 259 | Controller 6-{{0:...}} | Frost/Heat protection mode, status | 1 Bit | 1.3 enable | CRT |
| 260 | Controller 6-{{0:...}} | Standby mode, status | 1 Bit | 1.3 enable | CRT |
| 261 | Controller 6-{{0:...}} | Heating control value | 1 Bit | 1.1 switch | CRT |
| 261 | Controller 6-{{0:...}} | Heating/cooling control value | 1 Bit | 1.1 switch | CRT |
| 261 | Controller 6-{{0:...}} | Heating control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 261 | Controller 6-{{0:...}} | Heating/cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
| 262 | Controller 6-{{0:...}} | Cooling control value | 1 Bit | 1.1 switch | CRT |
| 262 | Controller 6-{{0:...}} | Cooling control value | 1 Byte | 5.1 percentage (0..100%) | CRT |
Parameters (117)
| Parameter | Type | Default |
|---|---|---|
| Send delay after voltage recovery [0..15] | unsignedInt 0…15 | 5 |
| Send cycle of "In operation" telegram [1..240,0=inactive] | unsignedInt 0…240 | 0 |
| Thermal driving | list | 230V AC |
| Report operating voltage failure status | unsignedInt 0…1 | 1 |
| Number of valve outputs | list | 6 |
| Number of room temperature controllers | list | 6 |
| Manual operation | unsignedInt 0…1 | 1 |
| Manual to automatic by | list | Both long press and automatic delay time |
| Delay time [10..6000] | unsignedInt 10…6000 | 10 |
| Summer/Winter mode | list | Disable |
| Summer/Winter mode after download | list | Unchange |
| Description (max 30char.) | text | |
| Controller from | list | Local controller 1 |
| Control value for valve output (1bit/1byte) | list | Control value of cooling |
| Control value for valve output (1bit) | list | Control value of cooling |
| Monitoring control value | unsignedInt 0…1 | 0 |
| Monitoring period of control value [10..65535] | unsignedInt 10…65535 | 60 |
| Control value after fault occurs (at summer) [0..100] | unsignedInt 0…100 | 0 |
| Control value after fault occurs [0..100] | unsignedInt 0…100 | 0 |
| Control value after fault occurs (at winter) [0..100] | unsignedInt 0…100 | 0 |
| Reply mode of Obj. "Control value fault" | list | Respond after change |
| Valve control mode | list | Continuous PWM(use PI control) |
| Valve type | list | Normal(de-energised closed) |
| PWM cycle time [1..255] | unsignedInt 1…255 | 15 |
| Valve position after download | list | Close valve |
| If bus recovery, valve position | list | Unchange |
| Reply mode for valve status | list | Respond after change |
| Minimum limitation of control value | unsignedInt 0…50 | 0 |
| Maximum limitation of control value | unsignedInt 51…100 | 100 |
| Control value lower than the minimum limitation | list | 0%=0%,otherwise=Minimum limitation value |
| Valve purge function | unsignedInt 0…1 | 0 |
| Duration of valve purge time [1..255] | unsignedInt 1…255 | 10 |
| Automatic valve purge | unsignedInt 0…1 | 0 |
| Purge Cycle in weeks [1..12] | unsignedInt 1…12 | 1 |
| Reply mode for valve purge status | list | Respond after change |
| Valve disable function | list | Disable |
| Forced operation function | list | Disable |
| Control value for forced operation (at summer) [0..100] | unsignedInt 0…100 | 30 |
| Control value for forced operation [0..100] | unsignedInt 0…100 | 30 |
| Control value for forced operation (at winter) [0..100] | unsignedInt 0…100 | 70 |
| Report short-circuit/overload status | unsignedInt 0…1 | 0 |
| Room temperature reference from | list | External sensor 1 |
| Period for request external sensor [0..255] | unsignedInt 0…255 | 10 |
| Combination ratio for external sensor 1 to sensor 2 | list | 50% to 50% |
| Send temperature when the result change by | list | 1.0K |
| Cyclically send temperature [0..255] | unsignedInt 0…255 | 0 |
| Control value after temp. error[0..100] (if 2-point control, set value '0'=0, set value '>0'=1) | unsignedInt 0…100 | 0 |
| Room temperature control mode | list | Heating |
| Heating/Cooling switchover | list | Via object |
| Heating/Cooling status after download | list | Heating |
| Heating/Cooling status after voltage recovery | list | As before voltage failure |
| Room temperature control system | list | 4 pipes system |
| Operation mode | unsignedInt 0…1 | 0 |
| Initial setpoint temperature | list | 20.0 |
| Upper dead zone | list | 2.0 |
| Lower dead zone | list | 2.0 |
| Controller status after download | list | Comfort mode |
| Controller status after voltage recovery | list | As before voltage failure |
| Extended comfort mode [0..255,0=inactive] | unsignedInt 0…255 | 0 |
| 1 bit object function for operation mode | unsignedInt 0…1 | 0 |
| 1 bit object for standby mode | unsignedInt 0…1 | 1 |
| Scene function | unsignedInt 0…1 | 0 |
| Window contact input function | unsignedInt 0…1 | 0 |
| Delay for window contact [0..65535] | unsignedInt 0…65535 | 15 |
| Controller mode for open window | list | Frost/heat protection |
| Bus presence detector function | unsignedInt 0…1 | 0 |
| Setpoint method for operating mode | list | Absolute |
| Base setpoint temperature | list | 20.0 |
| Additional setpoint offset for setpoint adjustment | list | Disable |
| Step of setpoint offset | list | 0.5K |
| Min. setpoint offset [-10..0] | signedInt -10…0 | -5 |
| Max. setpoint offset [0..10] | unsignedInt 0…10 | 5 |
| Reduced heating in standby mode [0..10] | list | 2 |
| Reduced heating in economy mode [0..10] | list | 4 |
| Setpoint temperature in frost protection mode [5..10] | list | 7 |
| Increased cooling in standby mode [0..10] | list | 2 |
| Increased cooling in economy mode [0..10] | list | 4 |
| Setpoint temperature in heat protection mode [30..37] | list | 35 |
| Setpoint temperature in comfort mode [5..37] | list | 21 |
| Setpoint temperature in standby mode [5..37] | list | 19 |
| Setpoint temperature in economy mode [5..37] | list | 17 |
| Setpoint temperature in comfort mode [5..37] | list | 23 |
| Setpoint temperature in standby mode [5..37] | list | 25 |
| Setpoint temperature in economy mode [5..37] | list | 27 |
| Minimum zone between heating and cooling setpoint | list | 2.0 |
| Min. setpoint temperature [5..37] | list | 10 |
| Max. setpoint temperature [5..37] | list | 32 |
| Type of heating control | list | Continuous control(use PI control) |
| Invert control value | list | No |
| Lower Hysteresis [0..200] | unsignedInt 0…200 | 10 |
| Upper Hysteresis [0..200] | unsignedInt 0…200 | 10 |
| Heating speed | list | Hot water heating(5K/150min) |
| Proportional range [10..100] | unsignedInt 0…100 | 40 |
| Reset time [0..255] | unsignedInt 0…255 | 150 |
| Cyclically send control value [0..255] | unsignedInt 0…255 | 10 |
| Type of cooling control | list | Continuous control(use PI control) |
| Cooling speed | list | Cooling ceiling (5K/240min) |
| Proportional range [10..100] | unsignedInt 10…100 | 40 |
| Type of heating/cooling control | list | Continuous control(use PI control) |
| Control value after temp. error (at summer) [0..100] (if 2-point control, set value '0'=0, set value '>0'=1) | unsignedInt 0…100 | 0 |
| Control value after temp. error (at winter) [0..100] (if 2-point control, set value '0'=0, set value '>0'=1) | unsignedInt 0…100 | 0 |
| Limit control mode switchover at summer | unsignedInt 0…1 | 0 |
| Limit control mode switchover at winter | unsignedInt 0…1 | 0 |
| 1->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| Temperature | list | Unchange |
| Operation mode | list | Unchange |
| 2->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 3->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 4->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| 5->Assign scene NO.[1..64,0=inactive] | unsignedInt 0…64 | 0 |
| Controller from | list | External controller |
| Setpoint Temperature error | unsignedInt 0…1 | 0 |
| Send control value on change by [0..100,0=inactive] | unsignedInt 0…100 | 4 |
| Control value for valve output (1byte) | list | Control value of cooling |
| Evaluate valve open/close times for PWM | unsignedInt 0…1 | 0 |
| Fully open time | unsignedInt 0…600 | 120 |
| Fully close time | unsignedInt 0…600 | 120 |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Heating Actuator 6-fold KNX Secure 1.0 latest | $002A | 75CD | 2026-11-25 | 236 KB | Download |
About this file
This is the official ETS product database for the Atios AG Heating Actuator 6-fold, KNX Secure, ADK-T6 (ADK-T6), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.