CO2 multi-sensor CO2..2178

Albrecht Jung · Order number CO2..2178 · Heating, air condition, ventilation › Controller

CO2 sensor 706211

Download .knxprod CO2 sensor 706211 1.1 · 4.6 MB

Product

ManufacturerAlbrecht Jung
Product nameCO2 multi-sensor
Order numberCO2..2178
HardwareCO2 multi-sensor
MediumTwisted Pair
Bus current (mA)25
Rail mountedNo
RegistrationRegistered
Languagesde-DE, en-US, es-ES, fr-FR, nl-NL, it-IT, ru-RU
Catalog entryM-0004_H-4.20.2F.2F.20CO2.2E.2E2178-1-O00F4_HP-7062-11-54E7-O00F4_CI-CO2.2E.2E2178-1
Fingerprint54E7
SHA-2563bb52da6f4e23d53c3e96641229713e4de37ec8c7189cc54befb3b5f6605045b
First seen2026-11-25
Markets59 markets

Application program: CO2 sensor 706211 1.1

Application number$7062
Version1.1
Mask versionMV-0705 (7.5)
KNX Data SecureNo
Minimum ETS version3.0d
Parameters1516
Group objects189
Group objects (189)
NoNameFunctionSizeDPTFlags
0B.Channel 1Switching object 1.11 BitCWT
0B.Channel 1Switching1 BitCWT
0B.Channel 1Short time operation1 BitCT
0B.Channel 1Brightness value2 BytesCT
0B.Channel 1Temperature value2 BytesCT
0B.Channel 1Scene extension1 ByteCT
0B.Channel 1Dimming value1 ByteCT
1B.Channel 2Switching object 2.11 BitCWT
1B.Channel 2Switching1 BitCWT
1B.Channel 2Short time operation1 BitCT
1B.Channel 2Brightness value2 BytesCT
1B.Channel 2Temperature value2 BytesCT
1B.Channel 2Scene extension1 ByteCT
1B.Channel 2Dimming value1 ByteCT
2B.Channel 1Switching object 1.21 BitCWT
2B.Channel 1Dimming4 BitCWT
2B.Channel 1Long-time operation1 BitCWT
3B.Channel 2Switching object 2.21 BitCWT
3B.Channel 2Dimming4 BitCWT
3B.Channel 2Long-time operation1 BitCWT
4B.Disable channel 1Disabling switching object 1.11 BitCW
4B.Disable channel 1Disabling1 BitCW
5B.Disable channel 2Disabling switching object 2.11 BitCW
5B.Disable channel 2Disabling1 BitCW
6B.Disable channel 1Disabling switching object 1.21 BitCW
7B.Disable channel 2Disabling switching object 2.21 BitCW
23R.OutputActual temperature2 BytesCRT
24R.InputReceived temperature2 BytesCW
26R.InputSetpoint active operating mode2 BytesCW
26R.InputBasic setpoint2 BytesCW
28R.InputOperating mode switchover1 ByteCWT
28R.InputComfort mode1 BitCWT
29R.InputStandby mode1 BitCWT
30R.InputNight operation1 BitCWT
31R.InputFrost/heat protection1 BitCWT
32R.InputOperating mode forced-control1 ByteCWT
33R.Input / OutputPresence object1 BitCWT
33R.InputPresence object1 BitCW
34R.InputWindow status1 BitCW
35R.InputHeating/cooling switchover1 BitCWT
35R.OutputHeating/cooling switchover1 BitCT
36R.OutputController status, frost alarm1 BitCT
36R.OutputCont. status, cont. inactive1 BitCT
36R.OutputCont. status, heating/cooling1 BitCT
36R.OutputCont. status, Comfort mode1 BitCT
36R.OutputCont. status, cont. disabled1 BitCT
36R.OutputController status, Night mode1 BitCT
36R.OutputCont. status, frost/heat prot.1 BitCT
36R.OutputController status Standby mode1 BitCT
36R.OutputController status1 ByteCT
36R.OutputKNX status operating mode1 ByteCT
37R.OutputHeating message1 BitCT
38R.OutputCooling message1 BitCT
39R.InputDisable controller operation1 BitCW
40R.InputDisable controller1 BitCW
41R.InputDisable additional level1 BitCW
42R.OutputCmd. value, heat./cool. (PWM)1 BitCT
42R.OutputCmd. value, heating/cooling1 ByteCT
42R.OutputCmd. value, heating/cooling1 BitCT
42R.OutputCmd. value, basic heating(PWM)1 BitCT
42R.OutputCmd. value, basic heating1 ByteCT
42R.OutputCmd. value, basic heating1 BitCT
42R.OutputCmd. value for heating (PWM)1 BitCT
42R.OutputCmd. value for heating1 BitCT
42R.OutputCmd. value for heating1 ByteCT
42R.OutputCmd. value, basic level (PWM)1 BitCT
42R.OutputCmd. value, basic level1 ByteCT
42R.OutputCmd. value, basic level1 BitCT
43R.OutputCmd. value, add. heating (PWM)1 BitCT
43R.OutputCmd. value, additional heating1 ByteCT
43R.OutputCmd. value, additional heating1 BitCT
43R.OutputCmd. value, additional level1 ByteCT
43R.OutputCmd. value, add. level (PWM)1 BitCT
43R.OutputCmd. value, additional level1 BitCT
44R.OutputCmd. value, basic cooling1 ByteCT
44R.OutputCmd. value, basic cooling(PWM)1 BitCT
44R.OutputCmd. value, basic cooling1 BitCT
44R.OutputCmd. value for cooling (PWM)1 BitCT
44R.OutputCmd. value for cooling1 BitCT
44R.OutputCmd. value for cooling1 ByteCT
45R.OutputCmd. value, additional cooling1 BitCT
45R.OutputCmd. value, add. cooling (PWM)1 BitCT
45R.OutputCmd. value, additional cooling1 ByteCT
46R.OutputPWM cmd. value heating/cooling1 ByteCT
46R.OutputPWM cmd. value, basic heating1 ByteCT
46R.OutputPWM cmd. value for heating1 ByteCT
46R.OutputPWM cmd. value, basic level1 ByteCT
47R.OutputPWM cmd. value, add. heating1 ByteCT
47R.OutputPWM cmd. value, add. level1 ByteCT
48R.OutputPWM cmd. value, basic cooling1 ByteCT
48R.OutputPWM cmd. value for cooling1 ByteCT
49R.OutputPWM cmd. value, add. cooling1 ByteCT
50R.OutputSetpoint temperature2 BytesCRT
52R.OutputCurrent setpoint shift1 ByteCRT
53R.InputSetpoint shift specification1 ByteCW
54R.OutputStatus signal addition1 ByteCT
55R.OutputKNX status2 BytesCT
56R.OutputKNX status forced oper. mode1 ByteCT
57R.InputCommand value limit1 BitCW
59R.OutputActual temp. not adjusted2 BytesCRT
80S.TemperatureMeasured value2 BytesCRT
81S.HumidityMeasured value2 BytesCRT
82S.CO2Measured value2 BytesCRT
83S.Dew pointTemperature2 BytesCRT
84S.TemperatureLimiting value 11 BitCRT
85S.HumidityLimiting value 11 BitCRT
86S.CO2Limiting value 11 BitCRT
87S.TemperatureLimiting value 21 BitCRT
88S.HumidityLimiting value 21 BitCRT
89S.CO2Limiting value 21 BitCRT
90S.CO2Limiting value 31 BitCRT
91S.CO2Limiting value 41 BitCRT
92S.Temperature limiting value spec. 1Absolute value2 BytesCW
92S.Temperature limiting value spec. 1Percentage1 ByteCW
92S.Temperature limiting value spec. 1Learning1 BitCW
93S.Humidity limiting value spec. 1Absolute value2 BytesCW
93S.Humidity limiting value spec. 1Percentage1 ByteCW
93S.Humidity limiting value spec. 1Learning1 BitCW
94S.CO2 limiting value spec. 1Absolute value2 BytesCW
94S.CO2 limiting value spec. 1Percentage1 ByteCW
94S.CO2 limiting value spec. 1Learning1 BitCW
95S.Temperature limiting value spec. 2Absolute value2 BytesCW
95S.Temperature limiting value spec. 2Percentage1 ByteCW
95S.Temperature limiting value spec. 2Learning1 BitCW
96S.Humidity limiting value spec. 2Absolute value2 BytesCW
96S.Humidity limiting value spec. 2Percentage1 ByteCW
96S.Humidity limiting value spec. 2Learning1 BitCW
97S.CO2 limiting value spec. 2Absolute value2 BytesCW
97S.CO2 limiting value spec. 2Percentage1 ByteCW
97S.CO2 limiting value spec. 2Learning1 BitCW
98S.CO2 limiting value spec. 3Absolute value2 BytesCW
98S.CO2 limiting value spec. 3Percentage1 ByteCW
98S.CO2 limiting value spec. 3Learning1 BitCW
99S.CO2 limiting value spec. 4Absolute value2 BytesCW
99S.CO2 limiting value spec. 4Percentage1 ByteCW
99S.CO2 limiting value spec. 4Learning1 BitCW
108S.Dew point alarmSwitching1 BitCRT
108S.Dew point alarm 1Switching1 BitCRT
108S.Dew point alarmValue1 ByteCRT
108S.Dew point alarm 1Value1 ByteCRT
109S.Dew point alarm 2Switching1 BitCRT
109S.Dew point alarm 2Value1 ByteCRT
110S.TemperatureSensor fault1 BitCRT
111S.HumiditySensor fault1 BitCRT
112S.CO2Sensor fault1 BitCRT
115L.Logic gate 1Input1 BitCW
115L.Logic gate 1Input 11 BitCW
116L.Logic gate 1Input 21 BitCW
117L.Logic gate 1Input 31 BitCW
118L.Logic gate 1Input 41 BitCW
119L.Logic gate 1Output switching1 BitCT
119L.Logic gate 1Output 1 switching1 BitCT
119L.Logic gate 1Output value1 ByteCT
119L.Logic gate 1Output 1 value1 ByteCT
120L.Logic gate 1Output 2 switching1 BitCT
120L.Logic gate 1Output 2 value1 ByteCT
121L.Logic gate 2Input1 BitCW
121L.Logic gate 2Input 11 BitCW
122L.Logic gate 2Input 21 BitCW
123L.Logic gate 2Input 31 BitCW
124L.Logic gate 2Input 41 BitCW
125L.Logic gate 2Output switching1 BitCT
125L.Logic gate 2Output 1 switching1 BitCT
125L.Logic gate 2Output value1 ByteCT
125L.Logic gate 2Output 1 value1 ByteCT
126L.Logic gate 2Output 2 switching1 BitCT
126L.Logic gate 2Output 2 value1 ByteCT
127L.Logic gate 3Input1 BitCW
127L.Logic gate 3Input 11 BitCW
128L.Logic gate 3Input 21 BitCW
129L.Logic gate 3Input 31 BitCW
130L.Logic gate 3Input 41 BitCW
131L.Logic gate 3Output switching1 BitCT
131L.Logic gate 3Output 1 switching1 BitCT
131L.Logic gate 3Output value1 ByteCT
131L.Logic gate 3Output 1 value1 ByteCT
132L.Logic gate 3Output 2 switching1 BitCT
132L.Logic gate 3Output 2 value1 ByteCT
133L.Logic gate 4Input 11 BitCW
133L.Logic gate 4Input1 BitCW
134L.Logic gate 4Input 21 BitCW
135L.Logic gate 4Input 31 BitCW
136L.Logic gate 4Input 41 BitCW
137L.Logic gate 4Output value1 ByteCT
137L.Logic gate 4Output 1 value1 ByteCT
137L.Logic gate 4Output 1 switching1 BitCT
137L.Logic gate 4Output switching1 BitCT
138L.Logic gate 4Output 2 value1 ByteCT
138L.Logic gate 4Output 2 switching1 BitCT
Parameters (370)
ParameterTypeDefault
Basic node of the plug-in settingsunsignedInt 0…655350
Window widthunsignedInt 0…655351000
Window heightunsignedInt 0…65535700
Ratio of the tree view to the overall width of the windowunsignedInt 0…10029
Ratio of the parameter table area to the overall heightunsignedInt 0…10070
Minimum width of the parameter name columnunsignedInt 0…655350
Minimum width of the parameter value columnunsignedInt 0…655350
Plug-in window size adjustablelisttrue
TreeView size adjustablelisttrue
There are no parameters for this nodetextFür diesen Knoten sind keine Parameter
AvailabletextFür diesen Knoten sind keine Parameter
WarningtextText
This change causestextText
Group assignments invalid.textText
Really delete it?textText
This operation causes alltext
Device parameters to default settingstext
reset. Thus invalidtext
Group assignments aretext
deleted. Really continuetext
operation?text
Reset devicetextText
OKtextText
CanceltextText
StandardtextText
HelptextText
The input value is invalid.text
CTH sensorunsignedInt 0…6553510
SensorunsignedInt 0…6553531
Activating sensor channel 1listActive
Activating sensor channel 2listActive
Activating sensor channel 3listActive
Activating sensor channel 4listActive
Deactivating sensor channel 5listInactive
Deactivating sensor channel 6listInactive
Deactivating sensor channel 7listInactive
Deactivating sensor channel 8listInactive
Deactivating sensor channel 9listInactive
Deactivate check modelistInactive
Room temperature control (RTC)unsignedInt 0…6553511
Room temperature controller functionlistSwitched-on
Push button interfaceunsignedInt 0…6553517
Logic gatesunsignedInt 0…6553536
Control circuitslist1 Control circuit
Operating modelistHeating
Additional level disabling objectlistNo
Transmit heating and cooling command value to shared objectlistNo
Type of basic level, heatinglistContinuous PI control
Type of heating controllistContinuous PI control
Type of controllistContinuous PI control
Type of control, basic levellistContinuous PI control
Type of basic heatinglistHot water heater (5K / 150min)
Type of heatinglistHot water heater (5K / 150min)
Proportional range, basic level [(10..127) * 0.1K]unsignedInt 10…12750
Proportional range, heating [(10..127) * 0.1K]unsignedInt 10…12750
Proportional range, basic level heating [(10..127) * 0.1K]unsignedInt 10…12750
Lower hysteresis limit of 2-point cont., basic heating [(-128..-5) * 0.1K]signedInt -128…-5-5
Lower hysteresis limit of 2-point cont., heating [(-128..-5) * 0.1K]signedInt -128…-5-5
Lower hysteresis limit of 2-point cont., basic level [(-128..-5) * 0.1K]signedInt -128…-5-5
Reset time, basic level [(0..255) * 1min; 0 = inactive]unsignedInt 0…25590
Reset time, heating [(0..255) * 1min; 0 = inactive]unsignedInt 0…25590
Reset time, basic level heating [(0..255) * 1min; 0 = inactive]unsignedInt 0…25590
Upper hysteresis limit of the 2-point cont., basic heating [(5..127) * 0.1K]signedInt 5…1275
Upper hysteresis limit of the 2-point controller, heating [(5..127) * 0.1K]signedInt 5…1275
Upper hysteresis limit of the 2-point cont., basic level [(5..127) * 0.1K]signedInt 5…1275
Type of basic coolinglistCooling ceiling (5K / 240min)
Proportional range, basic level cooling [(10..127) * 0.1K]unsignedInt 10…12750
Reset time, basic level cooling [(0..255) * 1min; 0 = inactive]unsignedInt 0…25590
Type of additional level, heatinglistContinuous PI control
Lower hysteresis limit of 2-point cont., basic cooling [(-128..-5) * 0.1K]signedInt -128…-5-5
Upper hysteresis limit of the 2-point cont., basic cooling [(5..127) * 0.1K]signedInt 5…1275
Type of control, additional levellistContinuous PI control
Type of additional heatinglistHot water heater (5K / 150min)
Proportional range add. heating [(10..127) * 0.1K]unsignedInt 10…12750
Proportional range, additional level [(10..127) * 0.1K]unsignedInt 10…12750
Lower hysteresis limit of 2-point cont., add. heating [(-128..-5) * 0.1K]signedInt -128…-5-5
Proportional range add. heating [(0..255) * 1min; 0 = inactive]unsignedInt 0…25590
Reset time, additional level heating [(0..255) * 1min; 0 = inactive]unsignedInt 0…25590
Reset time, additional level [(0..255) * 1min; 0 = inactive]unsignedInt 0…25590
Upper hysteresis limit of the 2-point cont., add. heating [(5..127) * 0.1K]signedInt 5…1275
Type of basic level, coolinglistContinuous PI control
Type of cooling controllistContinuous PI control
Type of coolinglistHot water heater (5K / 150min)
Type of coolinglistCooling ceiling (5K / 240min)
Type of basic coolinglistHot water heater (5K / 150min)
Proportional range, cooling [(10..127) * 0.1K]unsignedInt 10…12750
Lower hysteresis limit of 2-point cont., cooling [(-128..-5) * 0.1K]signedInt -128…-5-5
Reset time, cooling [(0..255) * 1min; 0 = inactive]unsignedInt 0…25590
Upper hysteresis limit of the 2-point controller, cooling [(5..127) * 0.1K]signedInt 5…1275
Type of additional level, coolinglistContinuous PI control
Type of additional coolinglistHot water heater (5K / 150min)
Type of additional coolinglistCooling ceiling (5K / 240min)
Proportional range,add. cooling [(10..127) * 0.1K]unsignedInt 10…12750
Lower hysteresis limit of 2-point cont., add. cooling [(-128..-5) * 0.1K]signedInt -128…-5-5
Reset time, additional level [(0..255) * 1min; 0 = inactive]unsignedInt 0…255240
Reset time, add. level cooling [(0..255) * 1min; 0 = inactive]unsignedInt 0…255240
Upper hysteresis limit of the 2-point cont., add. cooling [(5..127) * 0.1K]signedInt 5…1275
Operating mode switchoverlistVia value (1byte)
Operation mode after resetlistStandby mode
Frost/heat protectionlistVia window status
Automatic frost protection temperature droplistOff
Window status delay [(0..255) * 1min; 0 = inactive]unsignedInt 0…2550
Frost protection period in autom. mode [(1..255) * 1min]unsignedInt 1…25520
Frost protection period in autom. mode [(0..255) * 1min]unsignedInt 0…2550
Command value and status outputunsignedInt 0…6553515
Overwrite setpoints in device after ETS programming operation?listYes
Setpoint presettinglistRelative (setpoint temperatures from basic setp.)
Basic temperature after reset [(7.0..40.0) * 1.0°C]signedInt -32768…327673098
Setpoint temp. comfort mode heating [(7.0..40.0) * 1.0°C]signedInt -32768…327673098
Setpoint temp. comfort mode [(7.0..40.0) * 1.0°C]signedInt -32768…327673098
Setpoint temp. standby mode heating [(7.0..40.0) * 1.0°C]signedInt -32768…327671900
Setpoint temp. standby mode [(7.0..40.0) * 1.0°C]signedInt -32768…327671900
Setpoint temp. night mode heating [(7.0..40.0) * 1.0°C]signedInt -32768…327671700
Setpoint temp. night mode [(7.0..40.0) * 1.0°C]signedInt -32768…327671700
Setpoint temp. comfort mode cooling [(7.0..40.0) * 1.0°C]signedInt -32768…327673098
Setpoint temp. standby mode [(7.0..40.0) * 1.0°C]signedInt -32768…327673198
Setpoint temp. standby mode cooling [(7.0..40.0) * 1,0°C]signedInt -32768…327673198
Setpoint temp. night mode [(7.0..40.0) * 1.0°C]signedInt -32768…327673298
Setpoint temp. night mode cooling [(7.0..40.0) * 1.0°C]signedInt -32768…327673298
Value of the setpoint shift [(0..255) * 0.1K]list0.1K
Value of the setpoint shiftlist0.1K
Permanently apply change to basic setpoint shiftlistNo
Changing the setpoint of the basic temperaturelistApprove via bus
Accept modification of the basic temp. setpoint value permanentlylistNo
Accept modification of the setpoint permanentlylistNo
Standby temperature changelistDeactivated
Night temperature changelistDeactivated
Frost protection setpoint temperature [(7.0..40.0) * 1.0°C]signedInt -32768…32767700
Heat protection setpoint temperature [(7.0..45.0) * 1.0°C]signedInt -32768…327673798
Deadband positionlistAsymmetrical
Deadband between heating and cooling [(0..127) * 0.1K]unsignedInt 0…12720
Dead band shiftlistDeactivated
Level spacing from basic level to additional level [(0..127) * 0.1K]unsignedInt 0…12720
Transmit on setpoint temp. change by [(0..255) * 0.1K]unsignedInt 0…2551
Cyclical transmission of setpoint temp. [(0..255) * 1min; 0 = inactive]unsignedInt 0…2550
Upward adjustment of the basic setpoint temperature [(0..10) * 1K]list+8K
Downward adjustment of the basic setpoint temperature [(-10..0) * 1K]list-8K
Lower the setpoint temp. during standby oper. heat. [(-128..0) * 0.1K]signedInt -128…0-20
Lower the setpoint temp. during standby operation [(-128..0) * 0.1K]signedInt -128…0-20
Lower the setpoint temp. during night oper. heat. [(-128..0) * 0.1K]signedInt -128…0-40
Lower the setpoint temp. during night operation [(-128..0) * 0.1K]signedInt -128…0-40
Raise the setpoint temp. during standby operation [(0..127) * 0.1K]signedInt 0…12720
Raise the setpoint temp. during standby oper. cool. [(0..127) * 0.1K]signedInt 0…12720
Raise the setpoint temp. during nightoperation [(0..127) * 0.1K]signedInt 0…12740
Raise the setpoint temp. during night oper. cool. [(0..127) * 0.1K]signedInt 0…12740
Presence detectionlistPresence button
Length of comfort extension [(0..255) * 1min; 0 = OFF]unsignedInt 0…25530
Change-over between heating and coolinglistVia object (heating/cooling change-over)
Automatic heating/cooling transmission switchoverlistOn changing the operating mode
Cyclical transmission heating/cooling switchover [(0..255)*1min;0=inactive]unsignedInt 0…2550
Heating / cooling mode after a resetlistCooling
Operation of controller inhibitablelistNo
Switch off controller (dew point operation)listNo
Valve protectionlistNo
Setpoint valuesunsignedInt 0…6553512
Number of logic gateslistNo logic gates
Baselist1s
Automatic transmission on change by [(0..100) * 1%; 0 = inactive]unsignedInt 0…1003
Factor (3..127)unsignedInt 3…12717
Baselist0.5ms
Factor [(10..255)unsignedInt 10…25560
Cycle time of the switching cmd. value [(1..255) * 1min]unsignedInt 1…25515
Telegram rate limitlistDisabled
Cycle time for automatic transmission [(0..255) * 1min; 0 = inactive]unsignedInt 0…25510
Telegrams per 17slist30
Output of the heating command valuelistNormal (under current, this means opened)
Output of the command valuelistNormal (under current, this means opened)
Output of the command values, basic levellistNormal (under current, this means opened)
Output of the heating basic level command valuelistNormal (under current, this means opened)
Output of the cooling basic level command valuelistNormal (under current, this means opened)
Output of the heating additional level command valuelistNormal (under current, this means opened)
Output of the cooling additional level command valuelistNormal (under current, this means opened)
Output of the command values, additional levellistNormal (under current, this means opened)
Output of the cooling command valuelistNormal (under current, this means opened)
Command value limit (not for switching 2-point control)listDeactivated
Command value limit after resetlistDeactivated
Min. cmd. value for heating basic levellist5%
Minimum command value for heatinglist5%
Max. cmd. value for heating basic levellist95%
Maximum command value for heatinglist95%
Min. cmd. value for heating add. levellist5%
Max. cmd. value for heating add. levellist95%
Min. cmd. value for cooling basic levellist5%
Minimum command value for coolinglist5%
Max. cmd. value for cooling basic levellist95%
Maximum command value for coolinglist95%
Min. cmd. value for cooling add. levellist5%
Max. cmd. value for cooling add. levellist95%
Minimum comm. value for heating/coolinglist5%
Min. cmd. value for heating/cooling basic levellist5%
Maximum comm. value for heating/coolinglist95%
Max. cmd. value for heating/cooling basic levellist95%
Min. cmd. value for heating/cooling add. levellist5%
Max. cmd. value for heating/cooling add. levellist95%
Heating messagelistNo
Cooling messagelistNo
Controller statuslistKNX compliant
Single statuslistComfort mode activated
Channel 1unsignedInt 0…6553517
CO2 measurementunsignedInt 0…6553532
Controller generalunsignedInt 0…6553529
Logic gate 1unsignedInt 0…6553536
Behaviour when command value = 100% (Clipping mode)listkeep 100% until setpoint = actual, then 0%
Factor measuring range Parameter block 1listMeasurement range value*1
Factor measuring range Parameter block 2listMeasurement range value*1
Measuring range 0% Parameter block 1signedInt -32768…327670
Format measured valuelistPDT_KNX_FLOAT__2Byte
Measuring range 0% Parameter block 2signedInt -32768…327670
Measuring range 100% Parameter block 1signedInt -32768…327672000
Type of logic operationlistOR
Measuring range 100% Parameter block 2signedInt -32768…327672000
Function input 1listSwitching
Number of inputslist2 Inputs
Height of location above sea level [(0..2000) * 1m]unsignedInt 0…2000500
Transmit on change of the meas. value by [Sending delay: 10s]list3%
Cycl. sending of the measured value [(0..120) * 10s; 0 = inactive]unsignedInt 0…1200
Number and type of output objectslist1 Switching object
Limiting valueslistInactive
Send output atlistEach input event
Transmission behaviour for logic 0listTransmission without delay
Factor (1..100)unsignedInt 1…1001
Transmission behaviour for logic 1listTransmission without delay
Limiting value 1unsignedInt 0…6553535
Limiting values 1+2list1 Limiting value active
Limiting values 3+4listInactive
Limiting value 1 [(0..2000) * 1ppm]unsignedInt 0…20001500
Hysteresis [(0..50) * 1% related to LV range]unsignedInt 0…5020
External limiting value 1listNo
Activation limiting value 1, LV=limiting value, Hyst.=hysteresislistExceed LV=ON, Undershoot LV-hyst.=OFF
Switch-on delay for internal limiting value objectlist3min
Switch-off delay for internal limiting value objectlist10min
Cycl. transmission of output object[(s) [(0..120) * 10s; 0 = inactive]unsignedInt 0…1200
Transmission on change of the limiting value objectlistYes
Limiting value 2unsignedInt 0…6553535
Cycl. transm. of the limiting value obj. [(0..120) * 10s; 0 = inactive]unsignedInt 0…1200
Limiting value 3unsignedInt 0…6553535
Limiting value 2 [(0..2000) * 1ppm]unsignedInt 0…20001500
Hysteresis [(0..50) * 1% related to LV range]unsignedInt 0…5010
External limiting value 2listNo
Activation limiting value 2, LV=limiting value, Hyst.=hysteresislistExceed LV=ON, Undershoot LV-hyst.=OFF
Limiting value 3 [(0..2000) * 1ppm]unsignedInt 0…20001800
Limiting value 4unsignedInt 0…6553535
External limiting value 3listNo
Activation limiting value 3; LV=limiting value, Hyst.=hysteresislistExceed LV=ON, Undershoot LV-hyst.=OFF
Limiting value 4 [(0..2000) * 1ppm]unsignedInt 0…20001600
Hysteresis [(0..50) * 1% related to LV range]unsignedInt 0…505
External limiting value 4listNo
Activation limiting value 4, LV=limiting value, Hyst.=hysteresislistExceed LV=ON, Undershoot LV-hyst.=OFF
Channel 2unsignedInt 0…6553517
Controller functionalityunsignedInt 0…655354
Logic gate 2unsignedInt 0…6553536
Function input 2listSwitching
Operating mode heatinglistNo action
Operating mode coolinglistNo action
Temperature measurementunsignedInt 0…6553518
Logic gate 3unsignedInt 0…6553536
Test_GWModul__InReleaseUnsichtbarlistDisabled
Factor base valuelistMeasurement range value*0.1
Base value 0%signedInt -32768…32767-50
Measuring range 100%signedInt -32768…32767450
Internal sensor calibration [(-128..127) * 0.1K]signedInt -128…1270
Limiting value 1 in % [MB: -5°C..45°C --> 1K==2%]unsignedInt 0…10046
Hysteresis 0%..50% [MB: -5°C..45°C --> 1K==2%]unsignedInt 0…504
Limiting value 2 in % [MB: -5°C..45°C --> 1K==2%]unsignedInt 0…10054
Logic gate 4unsignedInt 0…6553536
Temperature measurement CC1 activelistYes
Temperature measurement CC2 inactivelistNo
Temperature detectionlistInternal sensor
Measured value formation, temperature value to be received internallylist50% to 50%
Calibration of received temp. value [(-128..127) * 0.1K]signedInt -128…1270
Request time for received temp. value [(0..255) * 1min; 0 = inactive]unsignedInt 0…2550
Transmission on room temp. change by [(0..255) * 0.1K; 0 = inactive]unsignedInt 0…2553
Cyclical transmission of the room temp. [(0..255) * 1min; 0 = inactive]unsignedInt 0…25515
Cycl. transmission of output object(s) [(0..120) * 10s; 0 = inactive]unsignedInt 0…1200
Humidity measurementunsignedInt 0…6553533
Factor base valuelistMeasurement range value*1
Base value 0%signedInt -32768…327670
Measuring range 100%signedInt -32768…32767100
Limiting value 1 [(20..100) * 1%RH]unsignedInt 20…10060
Hysteresis [(0..50) * 1%RH]unsignedInt 0…503
Limiting value 2 [(20..100) * 1%RH]unsignedInt 20…10060
Activation limiting value 2; LV=limiting value, Hyst.=hysteresislistExceed LV=ON, Undershoot LV-hyst.=OFF
Dew pointunsignedInt 0…6553534
Transmit on dew point change by [Sending delay: 10s]list3%
Cycl. transm. of the dew point temp. [(0..120) * 10s; 0 = inactive]unsignedInt 0…1200
Lead dew point alarm [(0..5) * 1K]unsignedInt 0…52
Switch-off hysteresis [(0..5) * 1K]unsignedInt 0…51
Number and type of alarm objectslist1 Switching object
Switching command for dew point alarmlistON
Value for dew point alarm active [(0..100) * 1%]unsignedInt 0…255255
Value for dew point alarm inactive [(0..100) * 1%]unsignedInt 0…2550
InputunsignedInt 0…6553537
ConnectionlistExternal input object
BehaviourlistNormal
InputsunsignedInt 0…6553537
Command on rising edge Switching object 1.1listOn
Command on rising edge Switching object 2.1listOn
Command on falling edge Switching object 1.1listOff
Command on falling edge Switching object 2.1listOff
Command on rising edge Switching object 1.2listNo reaction
Command on rising edge Switching object 2.2listNo reaction
Command on falling edge Switching object 1.2listNo reaction
Command on falling edge Switching object 2.2listNo reaction
Cyclical transmission ?listNo cyclical transmission
Time base for cyclical transmission of switching object 2.1list1s
Time base for cyclical transmission of switching object 1.1list1s
Time base for cyclical transmission of switching object 2.2listNo cycl. transm. via switching object X.2
Time base for cyclical transmission of switching object 1.2listNo cycl. transm. via switching object X.2
Time factor for cycl. transm. of switching object 2.1 and 2.2 (3..127)unsignedInt 3…12760
Time factor for cycl. transm. of switching object 1.1 and 1.2 (3..127)unsignedInt 3…12760
Response to bus voltage returnlistNo reaction
DisablingunsignedInt 0…6553513
Disabling function switching object 2.1listDisabled
Disabling function switching object 1.1listDisabled
Polarity of the disabling objectlistDisable = 1 (Enable = 0)
Behav. at beginning of disabl. funct. Switching object 1.1listNo reaction
Behav. at beginning of disabl. funct. Switching object 2.1listNo reaction
Behav. at end of disabl. funct. Switching object 1.1listNo reaction
Behav. at end of disabl. funct. Switching object 2.1listNo reaction
Disabling function switching object 2.2listDisabled
Disabling function switching object 1.2listDisabled
Behav. at beginning of disabl. funct. Switching object 1.2listNo reaction
Behav. at beginning of disabl. funct. Switching object 2.2listNo reaction
Behav. at end of disabl. funct. Switching object 1.2listNo reaction
Behav. at end of disabl. funct. Switching object 2.2listNo reaction
OperationlistTwo button operation: brighter (ON)
Increase brightness bylist100%
Reduce brightness bylist100%
Time between switching and dimming, Baselist130ms
Time between switching and dimming, Factor (4..127)unsignedInt 4…1274
Send stop telegram ?listYes
Telegram repetition?listNo
Time between two telegrams, Baselist130ms
Time between two telegrams, Factor (3..127)unsignedInt 3…12710
Disabling functionlistDisabled
Behaviour at the beginning of the disabling functionlistNo reaction
Behaviour at the end of the disabling functionlistNo reaction
Command on rising edgelistUp
Operation conceptlistshort - long - short
Time between short and long time operation, Baselist130ms
Time between short and long time operation, Factor (4..127)unsignedInt 4…1274
Slat adjust time, Baselist130ms
Slat adjust time, Factor (3..127)unsignedInt 3…12720
Function aslistDimming value transmitter
Transmit value onlistRising edge (pushbutton as NO contact)
Value on rising edge [(0..255)unsignedInt 0…255100
Value on falling edge [(0..255)unsignedInt 0…255100
Adjustment via long actuationlistYes
Adjustment via long actuationlistNo
Time between two telegrams, Baselist520ms
Step width (1..10)unsignedInt 0…1510
Transmit light scene number onlistRising edge (pushbutton as NO contact)
Light scene on rising edge (1..64)unsignedInt 1…641
Light scene on falling edge (1..64)unsignedInt 1…641
Only memory function?listNo
Time for long actuation for storage, Baselist130ms
Time for long actuation for storage, Factor (9..127)unsignedInt 9…12710
Value on rising edgelist20°C
Value on falling edgelist18°C
Time between two telegrams, Factor (3..127)unsignedInt 3…1273
Step widthlist1K
Value on rising edgelist200lux
Value on falling edgelist0lux
Step widthlist50lux
OutputunsignedInt 0…6553538
Switching command for logic 0listOFF
Switching command for logic 1listON
Value for logic 0unsignedInt 0…2550
Value for logic 1unsignedInt 0…255255
OutputsunsignedInt 0…6553538

Version history

ApplicationApp noFingerprintFirst seenSizeFile
CO2 sensor 706211 1.1 latest$706254E72026-11-254.6 MBDownload

About this file

This is the official ETS product database for the Albrecht Jung CO2 multi-sensor (CO2..2178), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.