AIRZONE – ALTRA AIDOO-AZAI6KNXxxx KNX-HVAC AIRZONE GATEWAY

KNX-HVAC AIRZONE GATEWAY AIDOO-AZAI6KNXxxx

AIRZONE – ALTRA · Order number AIDOO-AZAI6KNXxxx · INTERFACE

Download .knxprod kmachine 1.2 · 83 KB

Product

ManufacturerAIRZONE – ALTRA
Product nameKNX-HVAC AIRZONE GATEWAY
Order numberAIDOO-AZAI6KNXxxx
HardwareHVAC-KNX AIRZONE GATEWAY
MediumTwisted Pair
Rail mountedNo
RegistrationCertified · 2019-07-15
Catalog entryM-00B0_H-AZAI6KNXxxx-257_HP-0004-12-9AB9_CI-AIDOO.2DAZAI6KNXxxx-1
Fingerprint9AB9
SHA-2565b230ef9e6f3ca6894c037fd6f3d0d7a11b195b7955315da67608c4b3bb7bdae
First seen2026-11-25
Markets29 markets

Application program: kmachine 1.2

Application number$0004
Version1.2
Mask versionMV-07B0 (System B)
KNX Data SecureNo
Minimum ETS version4.0
Parameters179
Group objects127
Group objects (127)
NoNameFunctionSizeDPTFlags
1Control On/Off [DPT_1.001]0-Off, 1-On1 BitDPT.1CW
2Control Mode [DPT_20.105]0-Auto, 1-Heat, 3-Cool, 9-Fan, 14-Dry1 ByteDPT.20CW
3Control Mode Cool/Heat [DPT_1.100]0-Cool, 1-Heat1 BitDPT.1CW
4Control Mode Cool & On [DPT 5.001]0% Off, 1%-100% On + Cool1 ByteDPT.5CW
5Control Mode Heat & On [DPT 5.001]0% Off, 1%-100% On + Heat1 ByteDPT.5CW
6Control Mode Auto [DPT_1.002]1-Auto1 BitDPT.1CW
7Control Mode Heat [DPT_1.002]1-Heat1 BitDPT.1CW
8Control Mode Cool [DPT_1.002]1-Cool1 BitDPT.1CW
9Control Mode Fan [DPT_1.002]1-Fan1 BitDPT.1CW
10Control Mode Dry [DPT_1.002]1-Dry1 BitDPT.1CW
11Control Mode +/- [DPT_1.007]0-Decrease, 1-Increase1 BitDPT.1CW
11Control Mode +/- [DPT_1.008]0-Up, 1-Down1 BitDPT.1CW
12Control Fan Speed/3 Speeds [DPT 5.001]0%-49% Speed1, 50%-82% Speed2, 83%-100% Speed31 ByteDPT.5CW
12Control Fan Speed/3 Speeds [DPT 5.010]1 Speed1, 2 Speed2, 3 Speed31 ByteDPT.5CW
13Control Fan Speed Man/Auto [DPT 1.002]1-Auto1 BitDPT.1CW
14Control Fan Speed 1 [DPT 1.002]1-Set Fan Speed 11 BitDPT.1CW
15Control Fan Speed 2 [DPT 1.002]1-Set Fan Speed 21 BitDPT.1CW
16Control Fan Speed 3 [DPT 1.002]1-Set Fan Speed 31 BitDPT.1CW
17Control Fan Speed +/- [DPT 1.007]0-Decrease, 1-Increase1 BitDPT.1CW
17Control Fan Speed +/- [DPT 1.008]0-Up, 1-Down1 BitDPT.1CW
18Control Vanes U-D/5 pos [DPT 5.001]0%-29% Pos1, 30%-49% Pos2, 50%-69% Pos3, 70%-89% Pos4, 90%-100% Pos51 ByteDPT.5CW
18Control Vanes U-D/5 pos [DPT 5.010]1 Pos1, 2 Pos2, 3 Pos3, 4 Pos4, 5 Pos51 ByteDPT.5CW
19Control Vanes U-D Standby [DPT 1.002]0-Off, 1-Standby1 BitDPT.1CW
20Control Vanes U-D Pos1 [DPT 1.002]1-Set position 11 BitDPT.1CW
21Control Vanes U-D Pos2 [DPT 1.002]1-Set position 21 BitDPT.1CW
22Control Vanes U-D Pos3 [DPT 1.002]1-Set position 31 BitDPT.1CW
23Control Vanes U-D Pos4 [DPT 1.002]1-Set position 41 BitDPT.1CW
24Control Vanes U-D Pos5 [DPT 1.002]1-Set position 51 BitDPT.1CW
25Control Vanes U-D swing [DPT 1.002]0-Off, 1-Swing1 BitDPT.1CW
26Control Vanes U-D +/- [DPT 1.007]0-Decrease, 1-Increase1 BitDPT.1CW
26Control Vanes U-D +/- [DPT 1.008]0-Up, 1-Down1 BitDPT.1CW
27Control Setpoint Temperature [DPT 9.001]ºC2 BytesDPT.9CW
28Control Setpoint Temp +/- [DPT 1.007]0-Decrease, 1-Increase1 BitDPT.1CW
28Control Setpoint Temp +/- [DPT 1.008]0-Up, 1-Down1 BitDPT.1CW
29Control Ambient Temperature [DPT 9.001]ºC2 BytesDPT.9CW
30Control Setpoint limitation [DPT 1.001]0-Disable, 1-Enable1 BitDPT.1CW
31Control Reset Filter [DPT 1.015]1-Reset filter1 BitDPT.1CW
32Control Window Contact Status [DPT 1.009]0-Open, 1-Closed1 BitDPT.1CW
33Control Switch Off timeout [DPT 1.010]0-Stop,1-Start1 BitDPT.1CW
34Control Occupancy [DPT 1.018]0-Not ocuppied, 1-Ocuppied1 BitDPT.1CW
35Control Sleep Timeout [DPT 1.010]0-Stop, 1-Start1 BitDPT.1CW
36Control Lock Control Objects [DPT 1.002]0-Unlocked, 1-Locked1 BitDPT.1CW
37Control Save/ Scene [DPT 18.001]0 to 4 - Exec Scene 1 to 5, 128 to 132 Save Scene 1 to 51 ByteDPT.18CW
38Control Save Scene 1 [DPT 1.002]1-Store Scene 11 BitDPT.1CW
39Control Save Scene 2 [DPT 1.002]1-Store Scene 21 BitDPT.1CW
40Control Save Scene 3 [DPT 1.002]1-Store Scene 31 BitDPT.1CW
41Control Save Scene 4 [DPT 1.002]1-Store Scene 41 BitDPT.1CW
42Control Save Scene 5 [DPT 1.002]1-Store Scene 51 BitDPT.1CW
43Control Execute Scene 1 [DPT 1.002]1-Execute Scene 11 BitDPT.1CW
44Control Execute Scene 2 [DPT 1.002]1-Execute Scene 21 BitDPT.1CW
45Control Execute Scene 3 [DPT 1.002]1-Execute Scene 31 BitDPT.1CW
46Control Execute Scene 4 [DPT 1.002]1-Execute Scene 41 BitDPT.1CW
47Control Execute Scene 5 [DPT 1.002]1-Execute Scene 51 BitDPT.1CW
48Control Disable Input 1 [DPT 1.002]0-False, 1-True1 BitDPT.1CW
48Control Disable Input 1 [DPT 1.003]0-Disable, 1-Enable1 BitDPT.1CW
49Control Disable Input 2 [DPT 1.002]0-False, 1-True1 BitDPT.1CW
49Control Disable Input 2 [DPT 1.003]0-Disable, 1-Enable1 BitDPT.1CW
50Control Disable Input 3 [DPT 1.002]0-False, 1-True1 BitDPT.1CW
50Control Disable Input 3 [DPT 1.003]0-Disable, 1-Enable1 BitDPT.1CW
51Status On/Off [DPT_1.001]0-Off, 1-On1 BitDPT.1CRT
52Status Mode [DPT_20.105]0-Auto, 1-Heat, 3-Cool, 9-Fan, 14-Dry1 ByteDPT.20CRT
53Status Mode Cool/Heat [DPT 1.100]0-Cool, 1-Heat1 BitDPT.1CRT
54Status Mode Auto [DPT 1.002]1-Auto1 BitDPT.1CRT
55Status Mode Heat [DPT 1.002]1-Heat1 BitDPT.1CRT
56Status Mode Cool [DPT 1.002]1-Cool1 BitDPT.1CRT
57Status Mode Fan [DPT 1.002]1-Fan1 BitDPT.1CRT
58Status Mode Dry [DPT 1.002]1-Dry1 BitDPT.1CRT
59Status Mode Text [DPT 16.001]ASCII String14 BytesDPT.16CRT
60Status Fan Speed / 3 Speeds [DPT 5.001]33%-Speed1, 67%-Speed2, 100%-Speed31 ByteDPT.5CRT
60Status Fan Speed / 3 Speeds [DPT 5.010]1-Speed1, 2-Speed2, 3-Speed31 ByteDPT.5CRT
61Status Fan Speed Manual/Auto [DPT 1.002]0-Manual, 1-Auto1 BitDPT.1CRT
62Status Fan Speed 1 [DPT 1.002]1-Fan is in speed 11 BitDPT.1CRT
63Status Fan Speed 2 [DPT 1.002]1-Fan is in speed 21 BitDPT.1CRT
64Status Fan Speed 3 [DPT 1.002]1-Fan is in speed 31 BitDPT.1CRT
65Status Fan Speed Text [DPT 16.001]ASCII String14 BytesDPT.16CRT
66Status Vanes U-D/5Pos [DPT 5.001]20%-Pos1, 40%-Pos2, 60%-Pos3, 80%-Pos4, 100%-Pos51 ByteDPT.5CRT
66Status Vanes U-D/5Pos [DPT 5.010]1-Pos1, 2-Pos2, 3-Pos3, 4-Pos4, 5-Pos51 ByteDPT.5CRT
67Status Vanes U-D Standby [DPT 1.002]0-Off, 1-Standby1 BitDPT.1CRT
68Status Vanes U-D Pos1 [DPT 1.002 1 - bit]1-Position 11 BitDPT.1CRT
69Status Vanes U-D Pos2 [DPT 1.002 1 - bit]1-Position 21 BitDPT.1CRT
70Status Vanes U-D Pos3 [DPT 1.002 1 - bit]1-Position 31 BitDPT.1CRT
71Status Vanes U-D Pos4 [DPT 1.002 1 - bit]1-Position 41 BitDPT.1CRT
72Status Vanes U-D Pos5 [DPT 1.002 1 - bit]1-Position 51 BitDPT.1CRT
73Status Vanes U-D Swing [DPT 1.002 1 - bit]0-Off, 1-Swing1 BitDPT.1CRT
74Status Vanes U-D Text [DPT 16.001]ASCII String14 BytesDPT.16CRT
75Status AC Setpoint Temp [DPT 9.001]ºC2 BytesDPT.9CRT
76Status AC Return Temp [DPT 9.001]ºC2 BytesDPT.9CRT
77Internal probe temperature [DPT 9.001]ºC2 BytesDPT.9CRT
78External probe temperature [DPT 9.001]ºC2 BytesDPT.9CRT
79Status Reset Filter [DPT 1.002]0-No Alarm, 1-Alarm1 BitDPT.1CRT
80Status setpoint Limitation [DPT 1.001]0-Disable, 1-Enable1 BitDPT.1CRT
81Status Error/Alarm [DPT 1.005]0-No Alarm, 1-Alarm1 BitDPT.1CRT
82Error text code [DPT 16.001]ASCII String14 BytesDPT.16CRT
83Status Operation Hour Counter [DPT 13.100]Number of operating hours4 BytesDPT.13CRT
84Status Lock Remote Control [DPT 1.002]0-Unlocked, 1-Locked1 BitDPT.1CRT
85Status Lock Control Objects [DPT 1.002]0-Unlocked, 1-Locked1 BitDPT.1CRT
86Status Current Scene [DPT 17.001]0 to 4 Scene 1 to 5, 63 No scene1 ByteDPT.17CRT
87Status In1 - Switching [DPT 1.001]0-Off, 1-On1 BitDPT.1CRT
87Status In1 - Dimming On/Off [DPT 1.001]0-Off, 1-On1 BitDPT.1CRT
87Status In1 - Blind Step [DPT 1.007]0-Step Up, 1-Step Down1 BitDPT.1CRT
88Status In1 - Dimming Step [DPT 3.007]Dimming Step4 BitDPT.3CRT
88Status In1 - Blind Move [DPT 1.008]0-Move up, 1-Move down1 BitDPT.1CRT
88Status In1 - Value [DPT 5.010]1 byte unsigned value1 ByteDPT.5CRT
88Status In1 - Value [DPT 7.001]2 byte unsigned value2 BytesDPT.7CRT
88Status In1 - Value [DPT 8.001]2 byte signed value2 BytesDPT.8CRT
88Status In1 - Value [DPT 9.001]Temperature (ºC)2 BytesDPT.9CRT
88Status In1 - Value [DPT 12.001]4 byte unsigned value4 BytesDPT.12CRT
89Status In2 - Switching [DPT 1.001]0-Off, 1-On1 BitDPT.1CRT
89Status In2 - Dimming On/Off [DPT 1.001]0-Off, 1-On1 BitDPT.1CRT
89Status In2 - Blind Step [DPT 1.007]0-Step Up, 1-Step Down1 BitDPT.1CRT
90Status In2 - Dimming Step [DPT 3.007]Dimming Step4 BitDPT.3CRT
90Status In2 - Blind Move [DPT 1.008]0-Move up, 1-Move down1 BitDPT.1CRT
90Status In2 - Value [DPT 5.010]1 byte unsigned value1 ByteDPT.5CRT
90Status In2 - Value [DPT 7.001]2 byte unsigned value2 BytesDPT.7CRT
90Status In2 - Value [DPT 8.001]2 byte signed value2 BytesDPT.8CRT
90Status In2 - Value [DPT 9.001]Temperature (ºC)2 BytesDPT.9CRT
90Status In2 - Value [DPT 12.001]4 byte unsigned value4 BytesDPT.12CRT
91Status In3 - Switching [DPT 1.001]0-Off, 1-On1 BitDPT.1CRT
91Status In3 - Dimming On/Off [DPT 1.001]0-Off, 1-On1 BitDPT.1CRT
91Status In3 - Blind Step [DPT 1.007]0-Step Up, 1-Step Down1 BitDPT.1CRT
92Status In3 - Dimming Step [DPT 3.007]Dimming Step4 BitDPT.3CRT
92Status In3 - Blind Move [DPT 1.008]0-Move up, 1-Move down1 BitDPT.1CRT
92Status In3 - Value [DPT 5.010]1 byte unsigned value1 ByteDPT.5CRT
92Status In3 - Value [DPT 7.001]2 byte unsigned value2 BytesDPT.7CRT
92Status In3 - Value [DPT 8.001]2 byte signed value2 BytesDPT.8CRT
92Status In3 - Value [DPT 9.001]Temperature (ºC)2 BytesDPT.9CRT
92Status In3 - Value [DPT 12.001]4 byte unsigned value4 BytesDPT.12CRT
Parameters (84)
ParameterTypeDefault
Enable use of objects for FilterlistNo
Enable comm obj "Status_ Remote Lock"listNo
Enable comm obj "Ctrl_ /Status_ Control Lock"listNo
Enable "Mode Cool/Heat" objectslistNo
Enable PID-Compat Scaling Mode objectslistNo
Enable use of bit-type Mode objectslistNo
Enable use of +/- object for ModelistNo
> DPT type for +/- Mode objectlistStep [DPT 1.007]
Enable use of text object for ModelistNo
DPT object type for Fan SpeedlistScaling [DPT 5.001]
Enable use of bit-type Fan Speed objectslistNo
Enable use of +/- object for Fan SpeedlistNo
> DPT type for +/- Fan speed objectlistStep [DPT 1.007]
Enable use of Text object for Fan speedlistNo
DPT object type for Vanes Up-DownlistScaling [DPT 5.001]
Enable use of bit-type Vanes Up-Down objectslistNo
Enable use of +/- object for Vanes Up-DownlistNo
> DPT type for +/- Vanes Up-Down objectlistStep [DPT 1.007]
Enable use of text object for Vanes Up-DownlistNo
Periodic sending of "Status_ AC Setpoint" (in seconds. 0 = No periodic sending)"unsignedInt 0…14400
Enable use of +/- object for SetpointlistNo
> DPT type for +/- Setpoint objectlistStep [DPT 1.007]
Enable limits on Control_ Setpoint objlistNo
> Lower limit (ºC)unsignedInt 16…3016
> Upper limit (ºC)unsignedInt 16…3030
Ambient temperature is provided from KNXlistNo
Enable use of Open WindowlistNo
> AC window timeout (min)unsignedInt 0…25510
> Disallow On/Off operation when timeout is elapsedlistNo
Enable use of Switch off timeout functionlistNo
> AC switch-off timeout (min)unsignedInt 0…25510
Enable use of Occupancy WindowlistNo
> Timeout to apply actions (min)unsignedInt 0…25530
> Action after timeout elapsedlistSwitch off
> Timeout for unoccupied modeunsignedInt 0…25530
> Disallow On/Off operation when not occupiedlistNo
Enable use of Sleep functionlistNo
> Sleep function switch-off timeout (min)unsignedInt 0…25560
Enable use of sceneslistNo
Enable use of bit objects for storing sceneslistNo
Enable use of bit objects for scene executionlistNo
Scene 1 idunsignedInt 0…630
Scene 1 PresetlistNo
> Value for On-OfflistUnchanged
> Value for ModelistUnchanged
> Value for Fan SpeedlistUnchanged
> Value Vanes U-DlistUnchanged
> Value for SetpointlistUnchanged
Scene 2 idunsignedInt 0…631
Scene 2 PresetlistNo
Scene 3 idunsignedInt 0…632
Scene 3 PresetlistNo
Scene 4 idunsignedInt 0…633
Scene 4 PresetlistNo
Scene 5 idunsignedInt 0…634
Scene 5 PresetlistNo
Enable use of Input 1listNo
Contact typelistNO: Normally Open
Debounce timelist50 ms
Disabling functionlistNo
> DPT type for +/- Disabling input objectlistBool [DPT 1.002]
FunctionlistSwitching
> Send telegram after bus recoverylistNo action
> Sending delay after bus recovery (s)unsignedInt 0…25510
> Value on raising edge (contact activated)listNo action
> Value on falling edge (contact deactivated)listNo action
> Cyclical sendinglistNever
> Period for cyclical sending (s)unsignedInt 0…25510
> Mode for short (long) operationlistToggle: On/Off (increase/decrease)
> Increasing steplist25%
> Decreasing steplist-25%
> Short/long operation limit (ms)unsignedInt 0…655351000
> Cyclical sending period in long operation (0-No cyclical sending) (ms)unsignedInt 0…655350
> OperationlistDown
> MethodlistStep-Move-Step
> Vanes adjustment time (ms)unsignedInt 0…655351000
> DPT to be sentlistDPT 5.010
> Value on raising edge (when contact activated)unsignedInt 0…2550
> Value on raising edge (when contact activated)unsignedInt 0…655350
> Value on raising edge (when contact activated)signedInt -32767…327670
> Value on raising edge (when contact activated)unsignedInt 0…42949672950
> Scene when contact is activatedlistScene 1
Enable use of Input 2listNo
Enable use of Input 3listNo

Version history

ApplicationApp noFingerprintFirst seenSizeFile
kmachine 1.2 latest$00049AB92026-11-2583 KBDownload

About this file

This is the official ETS product database for the AIRZONE – ALTRA KNX-HVAC AIRZONE GATEWAY (AIDOO-AZAI6KNXxxx), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.