KNX Database
ABB AG - STOTZ-KONTAKT 2CDG 110 083 R0011 ZS/S1.1 Meter Interface Module,MDRC

ZS/S1.1 Meter Interface Module,MDRC 2CDG 110 083 R0011

ABB AG - STOTZ-KONTAKT · Order number 2CDG 110 083 R0011 · Energy Management › Meter Interfaces

Meter data logging/3.5

Download .knxprod Meter data logging/3.5a 3.5 · 444 KB

Product

ManufacturerABB AG - STOTZ-KONTAKT
Product nameZS/S1.1 Meter Interface Module,MDRC
Order number2CDG 110 083 R0011
Product textZS/S1.1 Meter Interface Module, MDRC
HardwareZS/S1.1 Zählerschnittstelle, REG
MediumTwisted Pair
Rail mountedYes
Width (mm)36
RegistrationCertified · 2012-08-17
Languagesen-US, de-DE, es-ES, fr-FR, it-IT, nl-NL, pl-PL, ru-RU
Catalog entryM-0002_H-2CDG.20110.20083.20R0011.20-1_HP-A04A-35-4D66_CI-2CDG.20110.20083.20R0011-1
Fingerprint4D66
SHA-256bfc86ceaba6fc3ec263dc4cd9dfd27c1321a62cb3c84c72a5e8c3080e5ee7407
First seen2026-11-25
Markets59 markets

Application program: Meter data logging/3.5a 3.5

Application number$A04A
Version3.5
Mask versionMV-0701 (7.1)
KNX Data SecureNo
Minimum ETS version3.0
Parameters213
Group objects121
Group objects (121)
NoNameFunctionSizeDPTFlags
0GeneralRequest status values1 BitCWT
1GeneralIn operation1 Bit1.1 switchCRT
2GeneralStatus byte1 ByteCRT
3GeneralError report1 BitCRT
4GeneralMeter type1 ByteCRT
5GeneralFalse meter type 1 BitCRT
6GeneralSend power fail counter1 Byte5.10 counter pulses (0..255)CRT
7GeneralReset power fail counter1 BitCWT
8GeneralSource of tariff switching1 Bit1.1 switchCW
9Dummy 091 BitCRWTU
10Meter readingRequest meter reading1 BitCWT
11Meter readingTotal active energy4 BytesCRT
11Meter readingActive energy4 BytesCRT
11Meter readingActive energy8 BytesCRT
11Meter readingTotal active energy8 BytesCRT
12Meter readingActive energy tariff 14 BytesCRT
12Meter readingActive energy tariff 18 BytesCRT
12Meter readingIntermediate meter4 BytesCRT
13Meter readingActive energy tariff 24 BytesCRT
13Meter readingActive energy tariff 28 BytesCRT
14Meter readingActive energy tariff 34 BytesCRT
14Meter readingActive energy tariff 38 BytesCRT
15Meter readingActive energy tariff 44 BytesCRT
15Meter readingActive energy tariff 48 BytesCRT
16Meter readingTotal reactive energy4 BytesCRT
16Meter readingReactive energy4 BytesCRT
16Meter readingReactive energy8 BytesCRT
16Meter readingTotal reactive energy8 BytesCRT
17Meter readingReactive energy tariff 14 BytesCRT
17Meter readingReactive energy tariff 18 BytesCRT
18Meter readingReactive energy tariff 24 BytesCRT
18Meter readingReactive energy tariff 28 BytesCRT
19Meter readingReactive energy tariff 34 BytesCRT
19Meter readingReactive energy tariff 38 BytesCRT
20Meter readingReactive energy tariff 44 BytesCRT
20Meter readingReactive energy tariff 48 BytesCRT
21Meter readingTotal active energy4 BytesCRT
21Meter readingTotal active energy8 BytesCRT
21Meter readingActive energy4 BytesCRT
21Meter readingActive energy8 BytesCRT
22Meter readingActive energy exported, Trf. 14 BytesCRT
22Meter readingActive energy exported, Trf. 18 BytesCRT
23Meter readingActive energy exported, Trf. 24 BytesCRT
23Meter readingActive energy exported, Trf. 28 BytesCRT
24Meter readingActive energy exported, Trf. 34 BytesCRT
24Meter readingActive energy exported, Trf. 38 BytesCRT
25Meter readingActive energy exported, Trf. 44 BytesCRT
25Meter readingActive energy exported, Trf. 48 BytesCRT
26Meter readingTotal reactive energy4 BytesCRT
26Meter readingTotal reactive energy8 BytesCRT
26Meter readingReactive energy4 BytesCRT
26Meter readingReactive energy8 BytesCRT
27Meter readingReactive energy tariff 14 BytesCRT
27Meter readingReactive energy tariff 18 BytesCRT
28Meter readingReactive energy tariff 24 BytesCRT
28Meter readingReactive energy tariff 28 BytesCRT
29Meter readingReactive energy tariff 34 BytesCRT
29Meter readingReactive energy tariff 38 BytesCRT
30Meter readingReactive energy tariff 44 BytesCRT
30Meter readingReactive energy tariff 48 BytesCRT
31TariffSend1 ByteCRT
32TariffTariff switching1 ByteCWT
33Power valuesRequest power values 1 BitCWT
34Power valueActive power total4 Bytes14.56 power (W)CRT
34Power valueActive power4 Bytes14.56 power (W)CRT
35Power valueActive power L14 Bytes14.56 power (W)CRT
36Power valueActive power L24 Bytes14.56 power (W)CRT
37Power valueActive power L34 Bytes14.56 power (W)CRT
38Power valueReactive power total4 Bytes14.56 power (W)CRT
38Power valueReactive power4 Bytes14.56 power (W)CRT
39Power valueReactive power L14 Bytes14.56 power (W)CRT
40Power valueReactive power L24 Bytes14.56 power (W)CRT
41Power valueReactive power L34 Bytes14.56 power (W)CRT
42Power valueApparent power total4 Bytes14.56 power (W)CRT
42Power valueApparent power4 Bytes14.56 power (W)CRT
43Power valueApparent power L14 Bytes14.56 power (W)CRT
44Power valueApparent power L24 Bytes14.56 power (W)CRT
45Power valueApparent power L34 Bytes14.56 power (W)CRT
46Power valuePhase angle power total4 Bytes14.55 phase angle (°)CRT
46Power valuePhase angle power4 Bytes14.55 phase angle (°)CRT
47Power valuePhase angle power L14 Bytes14.55 phase angle (°)CRT
48Power valuePhase angle power L24 Bytes14.55 phase angle (°)CRT
49Power valuePhase angle power L34 Bytes14.55 phase angle (°)CRT
50Power valuePower factor total4 Bytes14.57 power factor (cos Φ)CRT
50Power valuePower factor4 Bytes14.57 power factor (cos Φ)CRT
51Power valuePower factor L14 Bytes14.57 power factor (cos Φ)CRT
52Power valuePower factor L24 Bytes14.57 power factor (cos Φ)CRT
53Power valuePower factor L34 Bytes14.57 power factor (cos Φ)CRT
54Instrument valuesRequest instrument values1 BitCWT
55Instrument valueCurrent L14 Bytes14.19 electric current (A)CRT
55Instrument valueCurrent4 Bytes14.19 electric current (A)CRT
56Instrument valueCurrent L24 Bytes14.19 electric current (A)CRT
57Instrument valueCurrent L34 Bytes14.19 electric current (A)CRT
58Instrument valueCurrent N4 Bytes14.19 electric current (A)CRT
59Instrument valueVoltage L1-N4 Bytes14.27 electric potential (V)CRT
59Instrument valueVoltage4 Bytes14.27 electric potential (V)CRT
60Instrument valueVoltage L2-N4 Bytes14.27 electric potential (V)CRT
61Instrument valueVoltage L3-N4 Bytes14.27 electric potential (V)CRT
62Instrument valueVoltage L1-L24 Bytes14.27 electric potential (V)CRT
63Instrument valueVoltage L2-L34 Bytes14.27 electric potential (V)CRT
64Instrument valueVoltage L1-L34 Bytes14.27 electric potential (V)CRT
65Instrument valueFrequency4 Bytes14.33 frequency (Hz)CRT
66Instrument valuePhase angle current L14 Bytes14.55 phase angle (°)CRT
66Instrument valuePhase angle current4 Bytes14.55 phase angle (°)CRT
67Instrument valuePhase angle current L24 Bytes14.55 phase angle (°)CRT
68Instrument valuePhase angle current L34 Bytes14.55 phase angle (°)CRT
69Instrument valuePhase angle voltage L14 Bytes14.55 phase angle (°)CRT
69Instrument valuePhase angle voltage4 Bytes14.55 phase angle (°)CRT
70Instrument valuePhase angle voltage L24 Bytes14.55 phase angle (°)CRT
71Instrument valuePhase angle voltage L34 Bytes14.55 phase angle (°)CRT
72Instrument valueQuadrant (total)1 ByteCRT
72Instrument valueInstrument value1 ByteCRT
73Instrument valueQuadrant L11 ByteCRT
74Instrument valueQuadrant L21 ByteCRT
75Instrument valueQuadrant L31 ByteCRT
76Current transformersTransformer ratio voltage2 Bytes7.1 pulsesCRT
76Current transformersTransformer ratio voltage4 Bytes12.1 counter pulses (unsigned)CRT
77Current transformersTransformer ratio current2 Bytes7.1 pulsesCRT
78Current transformersTotal transformer ratio4 Bytes12.1 counter pulses (unsigned)CRT
79Intermediate meterReset intermediate meter1 BitCWT
80Intermediate meterNumber of resets4 Bytes12.1 counter pulses (unsigned)CRT
Parameters (45)
ParameterTypeDefault
GenerallistDummy
Meter typelistDELTAplus
VersionlistActive energy meter (direct connected)
Power and instrument valueslistSend as secondary values
Send power- and intsrument values aslistSend as secondary values
Meter reading valueslistSend as secondary values (4-Byte object type)
Voltage networklist4-wire (L1, L2, L3, N)
TariffslistNo tariffs
Register for exported energylistNo
Intermediate meterlistNo
Sending delay [device number * base delay time]listNo
Device number [1...255]unsignedInt 1…2551
Base delay time in s [1...65,535]unsignedInt 1…655351
Send object "In operation"listNo
Sending cycle time in s [1...65,535]unsignedInt 1…6553560
Limit number of telegramslistNo
Max. Number of transmitted telegrams within periodunsignedInt 0…2552
Depending on the meter type used some objects do not function (cf. manual)list<--- Note
PeriodsignedInt -32768…327671
Meter readinglistDummy
Send Meter Reading values aslistSend as secondary values
Send meter reading cyclicallylistNo
Cycle time in s [20...172,800]unsignedInt 20…172800900
Send meter reading on requestlistNo
Power valueslistDummy
Send power values cyclicallylistNo
Cycle time in s [1...172,800]unsignedInt 1…172800900
Send power values on requestlistNo
Send power values on changelistNo
Send active power in W at +/- [0...65,535]unsignedInt 0…655350
Send reactive power in var at +/- [0…65,535]unsignedInt 0…655350
Send apparent power in VA at +/- [0...65,535]unsignedInt 0…655350
Send phase angle power in degrees at +/- [0...90]unsignedInt 0…900
Send power factor at +/- 0.01 * Value [0...100]unsignedInt 0…1000
Instrument valueslistDummy
Send instrument values cyclicallylistNo
Send instrument values on requestlistNo
Send instrument values on changelistNo
Send current in mA at +/- 100 mA * Value [0...65,535]unsignedInt 0…655350
Send voltage in mV at +/- 10 mV * Value [0...65,535]unsignedInt 0…655350
Send frequency in Hz at +/- 0.1 Hz * Value [0...100]unsignedInt 0…1000
Send Frequency in Hz at +/- 0,1 Hz * Value [0...100]unsignedInt 0…1000
Send phase angle current in degrees at +/- [0...90]unsignedInt 0…900
Send phase angle voltage in degrees at +/- [0...90]unsignedInt 0…900
Send quadrant on changelistNo

Version history

ApplicationApp noFingerprintFirst seenSizeFile
Meter data logging/3.5a 3.5 latest$A04A4D662026-11-25444 KBDownload

About this file

This is the official ETS product database for the ABB AG - STOTZ-KONTAKT ZS/S1.1 Meter Interface Module,MDRC (2CDG 110 083 R0011), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.

More from ABB AG - STOTZ-KONTAKT

All ABB AG - STOTZ-KONTAKT products