DG/S1.16.1 DALI-Gateway,16G,1f,MDRC 6197/44
ABB AG - BUSCH-JAEGER · Order number 6197/44 · Beleuchtung › DALI
Switch Dim Groups 1f DALI/1.3
Download .knxprod Switch Dim Groups 1f DALI/1.3 1.3 · 541 KB
Product
| Manufacturer | ABB AG - BUSCH-JAEGER |
|---|---|
| Product name | DG/S1.16.1 DALI-Gateway,16G,1f,MDRC |
| Order number | 6197/44 |
| Hardware | DG/S1.16.1 DALI-Gateway,16G, 1f,REG |
| Medium | Twisted Pair |
| Bus current (mA) | 10 |
| Rail mounted | Yes |
| Width (mm) | 107 |
| Registration | Registered |
| Languages | de-DE, en-US |
| Catalog entry | M-0007_H-2CDG.20110.20103.20R0011-1-O0002_HP-A057-13-5094-O0002_CI-6197.2F44-1 |
| Fingerprint | 5094 |
| SHA-256 | 6751e09c200b6efd5cb8cf4c6450845e27a21234da1f2f1c5d3ef32e98f037b0 |
| First seen | 2026-11-25 |
| Markets | Australia |
Application program: Switch Dim Groups 1f DALI/1.3 1.3
| Application number | $A057 |
|---|---|
| Version | 1.3 |
| Mask version | MV-0701 (7.1) |
| KNX Data Secure | No |
| Parameters | 2619 |
| Group objects | 316 |
Group objects (316)
| No | Name | Function | Size | DPT | Flags |
|---|---|---|---|---|---|
| 0 | Group 1 | Switch/Status | 1 Bit | CRWT | |
| 0 | Group 1 | Switch | 1 Bit | CW | |
| 1 | Group 1 | Activate Staircase lighting | 1 Bit | CW | |
| 1 | Group 1 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 1 | Group 1 | Activate function Slave | 1 Bit | CW | |
| 1 | Group 1 | Activate Slave/Status | 1 Bit | CRWT | |
| 1 | Group 1 | Activate function Sequence | 1 Bit | CW | |
| 1 | Group 1 | Activate Sequence/Status | 1 Bit | CRWT | |
| 1 | Group 1 | Status switch | 1 Bit | CRT | |
| 2 | Group 1 | Relative dimming | 4 Bit | CW | |
| 3 | Group 1 | Brightness value | 1 Byte | CW | |
| 3 | Group 1 | Brightness value/Status | 1 Byte | CRWT | |
| 4 | Group 1 | Status Brightness value | 1 Byte | CRT | |
| 4 | Group 1 | Brightness value of Slave | 1 Byte | CW | |
| 5 | Group 1 | Fault ballast | 1 Bit | CWT | |
| 5 | Group 1 | Fault lamp | 1 Bit | CRT | |
| 5 | Group 1 | Fault lamp or ballast | 1 Bit | CRT | |
| 6 | Group 2 | Switch/Status | 1 Bit | CRWT | |
| 6 | Group 2 | Switch | 1 Bit | CW | |
| 7 | Group 2 | Activate Staircase lighting | 1 Bit | CW | |
| 7 | Group 2 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 7 | Group 2 | Activate function Slave | 1 Bit | CW | |
| 7 | Group 2 | Activate Slave/Status | 1 Bit | CRWT | |
| 7 | Group 2 | Activate function Sequence | 1 Bit | CW | |
| 7 | Group 2 | Activate Sequence/Status | 1 Bit | CRWT | |
| 7 | Group 2 | Status switch | 1 Bit | CRT | |
| 8 | Group 2 | Relative dimming | 4 Bit | CW | |
| 9 | Group 2 | Brightness value | 1 Byte | CW | |
| 9 | Group 2 | Brightness value/Status | 1 Byte | CRWT | |
| 9 | group 2 | Brightness value | 1 Byte | CW | |
| 10 | Group 2 | Status Brightness value | 1 Byte | CRT | |
| 10 | Group 2 | Brightness value of Slave | 1 Byte | CW | |
| 11 | Group 2 | Fault ballast | 1 Bit | CRT | |
| 11 | Group 2 | Fault lamp | 1 Bit | CRT | |
| 11 | Group 2 | Fault lamp or ballast | 1 Bit | CRT | |
| 12 | Group 3 | Switch/Status | 1 Bit | CRWT | |
| 12 | Group 3 | Switch | 1 Bit | CW | |
| 13 | Group 3 | Activate Staircase lighting | 1 Bit | CW | |
| 13 | Group 3 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 13 | Group 3 | Activate function Slave | 1 Bit | CW | |
| 13 | Group 3 | Activate Slave/Status | 1 Bit | CRWT | |
| 13 | Group 3 | Activate function Sequence | 1 Bit | CW | |
| 13 | Group 3 | Activate Sequence/Status | 1 Bit | CRWT | |
| 13 | Group 3 | Status switch | 1 Bit | CRT | |
| 14 | Group 3 | Relative dimming | 4 Bit | CW | |
| 15 | Group 3 | Brightness value | 1 Byte | CW | |
| 15 | Group 3 | Brightness value/Status | 1 Byte | CRWT | |
| 16 | Group 3 | Status Brightness value | 1 Byte | CRT | |
| 16 | Group 3 | Brightness value of Slave | 1 Byte | CW | |
| 17 | Group 3 | Fault ballast | 1 Bit | CRT | |
| 17 | Group 3 | Fault lamp | 1 Bit | CRT | |
| 17 | Group 3 | Fault lamp or ballast | 1 Bit | CRT | |
| 18 | Group 4 | Switch/Status | 1 Bit | CRWT | |
| 18 | Group 4 | Switch | 1 Bit | CW | |
| 19 | Group 4 | Activate Staircase lighting | 1 Bit | CW | |
| 19 | Group 4 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 19 | Group 4 | Activate function Slave | 1 Bit | CW | |
| 19 | Group 4 | Activate Slave/Status | 1 Bit | CRWT | |
| 19 | Group 4 | Activate function Sequence | 1 Bit | CW | |
| 19 | Group 4 | Activate Sequence/Status | 1 Bit | CRWT | |
| 19 | Group 4 | Status switch | 1 Bit | CRT | |
| 20 | Group 4 | Relative dimming | 4 Bit | CW | |
| 21 | Group 4 | Brightness value | 1 Byte | CW | |
| 21 | Group 4 | Brightness value/Status | 1 Byte | CRWT | |
| 22 | Group 4 | Status Brightness value | 1 Byte | CRT | |
| 22 | Group 4 | Brightness value of Slave | 1 Byte | CW | |
| 23 | Group 4 | Fault ballast | 1 Bit | CRT | |
| 23 | Group 4 | Fault lamp | 1 Bit | CRT | |
| 23 | Group 4 | Fault lamp or ballast | 1 Bit | CRT | |
| 24 | Group 5 | Switch/Status | 1 Bit | CRWT | |
| 24 | Group 5 | Switch | 1 Bit | CW | |
| 25 | Group 5 | Activate Staircase lighting | 1 Bit | CW | |
| 25 | Group 5 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 25 | Group 5 | Activate function Slave | 1 Bit | CW | |
| 25 | Group 5 | Activate Slave/Status | 1 Bit | CRWT | |
| 25 | Group 5 | Activate function Sequence | 1 Bit | CW | |
| 25 | Group 5 | Activate Sequence/Status | 1 Bit | CRWT | |
| 25 | Group 5 | Status switch | 1 Bit | CRT | |
| 26 | Group 5 | Relative dimming | 4 Bit | CW | |
| 27 | Group 5 | Brightness value | 1 Byte | CW | |
| 27 | Group 5 | Brightness value/Status | 1 Byte | CRWT | |
| 27 | Output A | Brightness value | 1 Byte | CW | |
| 28 | Group 5 | Status Brightness value | 1 Byte | CRT | |
| 28 | Group 5 | Brightness value of Slave | 1 Byte | CW | |
| 29 | Group 5 | Fault ballast | 1 Bit | CRT | |
| 29 | Group 5 | Fault lamp | 1 Bit | CRT | |
| 29 | Group 5 | Fault lamp or ballast | 1 Bit | CRT | |
| 30 | Group 6 | Switch | 1 Bit | CW | |
| 30 | Group 6 | Switch/Status | 1 Bit | CRWT | |
| 31 | Group 6 | Activate function Sequence | 1 Bit | CW | |
| 31 | Group 6 | Activate Sequence/Status | 1 Bit | CRWT | |
| 31 | Group 6 | Activate Staircase lighting | 1 Bit | CW | |
| 31 | Group 6 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 31 | Group 6 | Activate function Slave | 1 Bit | CW | |
| 31 | Group 6 | Activate Slave/Status | 1 Bit | CRWT | |
| 31 | Group 6 | Status switch | 1 Bit | CRT | |
| 32 | Group 6 | Relative dimming | 4 Bit | CW | |
| 33 | Group 6 | Brightness value | 1 Byte | CW | |
| 33 | Group 6 | Brightness value/Status | 1 Byte | CRWT | |
| 34 | Group 6 | Status Brightness value | 1 Byte | CRT | |
| 34 | Group 6 | Brightness value of Slave | 1 Byte | CW | |
| 35 | Group 6 | Fault ballast | 1 Bit | CRT | |
| 35 | Group 6 | Fault lamp | 1 Bit | CRT | |
| 35 | Group 6 | Fault lamp or ballast | 1 Bit | CRT | |
| 36 | Group 7 | Switch | 1 Bit | CW | |
| 36 | Group 7 | Switch/Status | 1 Bit | CRWT | |
| 37 | Group 7 | Activate function Slave | 1 Bit | CW | |
| 37 | Group 7 | Activate Slave/Status | 1 Bit | CRWT | |
| 37 | Group 7 | Activate Staircase lighting | 1 Bit | CW | |
| 37 | Group 7 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 37 | Group 7 | Activate function Sequence | 1 Bit | CW | |
| 37 | Group 7 | Activate Sequence/Status | 1 Bit | CRWT | |
| 37 | Group 7 | Status switch | 1 Bit | CRT | |
| 38 | Group 7 | Relative dimming | 4 Bit | CW | |
| 39 | Group 7 | Brightness value | 1 Byte | CW | |
| 39 | Group 7 | Brightness value/Status | 1 Byte | CRWT | |
| 40 | Group 7 | Brightness value of Slave | 1 Byte | CW | |
| 40 | Group 7 | Status Brightness value | 1 Byte | CRT | |
| 41 | Group 7 | Fault ballast | 1 Bit | CRT | |
| 41 | Group 7 | Fault lamp | 1 Bit | CRT | |
| 41 | Group 7 | Fault lamp or ballast | 1 Bit | CRT | |
| 42 | Group 8 | Switch/Status | 1 Bit | CRWT | |
| 42 | Group 8 | Switch | 1 Bit | CW | |
| 43 | Group 8 | Activate Staircase lighting | 1 Bit | CW | |
| 43 | Group 8 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 43 | Group 8 | Activate function Slave | 1 Bit | CW | |
| 43 | Group 8 | Activate Slave/Status | 1 Bit | CRWT | |
| 43 | Group 8 | Activate function Sequence | 1 Bit | CW | |
| 43 | Group 8 | Activate Sequence/Status | 1 Bit | CRWT | |
| 43 | Group 8 | Status switch | 1 Bit | CRT | |
| 44 | Group 8 | Relative dimming | 4 Bit | CW | |
| 45 | Group 8 | Brightness value | 1 Byte | CW | |
| 45 | Group 8 | Brightness value/Status | 1 Byte | CRWT | |
| 46 | Group 8 | Status Brightness value | 1 Byte | CRT | |
| 46 | Group 8 | Brightness value of Slave | 1 Byte | CW | |
| 47 | Group 8 | Fault ballast | 1 Bit | CRT | |
| 47 | Group 8 | Fault lamp | 1 Bit | CRT | |
| 47 | Group 8 | Fault lamp or ballast | 1 Bit | CRT | |
| 48 | Group 9 | Switch/Status | 1 Bit | CRWT | |
| 48 | Group 9 | Switch | 1 Bit | CW | |
| 49 | Group 9 | Activate Staircase lighting | 1 Bit | CW | |
| 49 | Group 9 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 49 | Group 9 | Activate function Slave | 1 Bit | CW | |
| 49 | Group 9 | Activate Slave/Status | 1 Bit | CRWT | |
| 49 | Group 9 | Activate function Sequence | 1 Bit | CW | |
| 49 | Group 9 | Activate Sequence/Status | 1 Bit | CRWT | |
| 49 | Group 9 | Status switch | 1 Bit | CRT | |
| 50 | Group 9 | Relative dimming | 4 Bit | CW | |
| 51 | Group 9 | Brightness value | 1 Byte | CW | |
| 51 | Group 9 | Brightness value/Status | 1 Byte | CRWT | |
| 52 | Group 9 | Status Brightness value | 1 Byte | CRT | |
| 52 | Group 9 | Brightness value of Slave | 1 Byte | CW | |
| 53 | Group 9 | Fault ballast | 1 Bit | CRT | |
| 53 | Group 9 | Fault lamp | 1 Bit | CRT | |
| 53 | Group 9 | Fault lamp or ballast | 1 Bit | CRT | |
| 54 | Group 10 | Switch | 1 Bit | CW | |
| 54 | Group 10 | Switch/Status | 1 Bit | CRWT | |
| 54 | Group 10 | Switch | 1 Bit | CRWT | |
| 55 | Group 10 | Activate function Sequence | 1 Bit | CW | |
| 55 | Group 10 | Activate Sequence/Status | 1 Bit | CRWT | |
| 55 | Group 10 | Activate Staircase lighting | 1 Bit | CW | |
| 55 | Group 10 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 55 | Group 10 | Activate function Slave | 1 Bit | CW | |
| 55 | Group 10 | Activate Slave/Status | 1 Bit | CRWT | |
| 55 | Group 10 | Status switch | 1 Bit | CRT | |
| 56 | Group 10 | Relative dimming | 4 Bit | CW | |
| 57 | Group 10 | Brightness value | 1 Byte | CW | |
| 57 | Group 10 | Brightness value/Status | 1 Byte | CRWT | |
| 58 | Group 10 | Status Brightness value | 1 Byte | CRT | |
| 58 | Group 10 | Brightness value of Slave | 1 Byte | CW | |
| 59 | Group 10 | Fault ballast | 1 Bit | CRT | |
| 59 | Group 10 | Fault lamp | 1 Bit | CRT | |
| 59 | Group 10 | Fault lamp or ballast | 1 Bit | CRT | |
| 60 | Group 11 | Switch | 1 Bit | CW | |
| 60 | Group 11 | Switch/Status | 1 Bit | CRWT | |
| 61 | Group 11 | Activate function Slave | 1 Bit | CW | |
| 61 | Group 11 | Activate Slave/Status | 1 Bit | CRWT | |
| 61 | Group 11 | Activate Staircase lighting | 1 Bit | CW | |
| 61 | Group 11 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 61 | Group 11 | Activate function Sequence | 1 Bit | CW | |
| 61 | Group 11 | Activate Sequence/Status | 1 Bit | CRWT | |
| 61 | Group 11 | Status switch | 1 Bit | CRT | |
| 62 | Group 11 | Relative dimming | 4 Bit | CW | |
| 63 | Group 11 | Brightness value | 1 Byte | CW | |
| 63 | Group 11 | Brightness value/Status | 1 Byte | CRWT | |
| 64 | Group 11 | Brightness value of Slave | 1 Byte | CW | |
| 64 | Group 11 | Status Brightness value | 1 Byte | CRT | |
| 65 | Group 11 | Fault ballast | 1 Bit | CRT | |
| 65 | Group 11 | Fault lamp | 1 Bit | CRT | |
| 65 | Group 11 | Fault lamp or ballast | 1 Bit | CRT | |
| 66 | Group 12 | Switch/Status | 1 Bit | CRWT | |
| 66 | Group 12 | Switch | 1 Bit | CW | |
| 67 | Group 12 | Activate Staircase lighting | 1 Bit | CW | |
| 67 | Group 12 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 67 | Group 12 | Activate function Slave | 1 Bit | CW | |
| 67 | Group 12 | Activate Slave/Status | 1 Bit | CRWT | |
| 67 | Group 12 | Activate function Sequence | 1 Bit | CW | |
| 67 | Group 12 | Activate Sequence/Status | 1 Bit | CRWT | |
| 67 | Group 12 | Status switch | 1 Bit | CRT | |
| 68 | Group 12 | Relative dimming | 4 Bit | CW | |
| 69 | Group 12 | Brightness value | 1 Byte | CW | |
| 69 | Group 12 | Brightness value/Status | 1 Byte | CRWT | |
| 70 | Group 12 | Status Brightness value | 1 Byte | CRT | |
| 70 | Group 12 | Brightness value of Slave | 1 Byte | CW | |
| 71 | Group 12 | Fault ballast | 1 Bit | CRT | |
| 71 | Group 12 | Fault lamp | 1 Bit | CRT | |
| 71 | Group 12 | Fault lamp or ballast | 1 Bit | CRT | |
| 72 | Group 13 | Switch/Status | 1 Bit | CRWT | |
| 72 | Group 13 | Switch | 1 Bit | CW | |
| 73 | Group 13 | Activate Staircase lighting | 1 Bit | CW | |
| 73 | Group 13 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 73 | Group 13 | Activate function Slave | 1 Bit | CW | |
| 73 | Group 13 | Activate Slave/Status | 1 Bit | CRWT | |
| 73 | Group 13 | Activate function Sequence | 1 Bit | CW | |
| 73 | Group 13 | Activate Sequence/Status | 1 Bit | CRWT | |
| 73 | Group 13 | Status switch | 1 Bit | CRT | |
| 74 | Group 13 | Relative dimming | 4 Bit | CW | |
| 75 | Group 13 | Brightness value | 1 Byte | CW | |
| 75 | Group 13 | Brightness value/Status | 1 Byte | CRWT | |
| 76 | Group 13 | Status Brightness value | 1 Byte | CRT | |
| 76 | Group 13 | Brightness value of Slave | 1 Byte | CW | |
| 77 | Group 13 | Fault ballast | 1 Bit | CRT | |
| 77 | Group 13 | Fault lamp | 1 Bit | CRT | |
| 77 | Group 13 | Fault lamp or ballast | 1 Bit | CRT | |
| 78 | Group 14 | Switch | 1 Bit | CW | |
| 78 | Group 14 | Switch/Status | 1 Bit | CRWT | |
| 79 | Group 14 | Activate function Sequence | 1 Bit | CW | |
| 79 | Group 14 | Activate Sequence/Status | 1 Bit | CRWT | |
| 79 | Group 14 | Activate Staircase lighting | 1 Bit | CW | |
| 79 | Group 14 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 79 | Group 14 | Activate function Slave | 1 Bit | CW | |
| 79 | Group 14 | Activate Slave/Status | 1 Bit | CRWT | |
| 79 | Group 14 | Status switch | 1 Bit | CRT | |
| 80 | Group 14 | Relative dimming | 4 Bit | CW | |
| 81 | Group 14 | Brightness value | 1 Byte | CW | |
| 81 | Group 14 | Brightness value/Status | 1 Byte | CRWT | |
| 82 | Group 14 | Status Brightness value | 1 Byte | CRT | |
| 82 | Group 14 | Brightness value of Slave | 1 Byte | CW | |
| 83 | Group 14 | Fault ballast | 1 Bit | CRT | |
| 83 | Group 14 | Fault lamp | 1 Bit | CRT | |
| 83 | Group 14 | Fault lamp or ballast | 1 Bit | CRT | |
| 84 | Group 15 | Switch | 1 Bit | CW | |
| 84 | Group 15 | Switch/Status | 1 Bit | CRWT | |
| 85 | Group 15 | Activate function Slave | 1 Bit | CW | |
| 85 | Group 15 | Activate Slave/Status | 1 Bit | CRWT | |
| 85 | Group 15 | Activate Staircase lighting | 1 Bit | CW | |
| 85 | Group 15 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 85 | Group 15 | Activate function Sequence | 1 Bit | CW | |
| 85 | Group 15 | Activate Sequence/Status | 1 Bit | CRWT | |
| 85 | Group 15 | Status switch | 1 Bit | CRT | |
| 86 | Group 15 | Relative dimming | 4 Bit | CW | |
| 87 | Group 15 | Brightness value | 1 Byte | CW | |
| 87 | Group 15 | Brightness value/Status | 1 Byte | CRWT | |
| 88 | Group 15 | Brightness value of Slave | 1 Byte | CW | |
| 88 | Group 15 | Status Brightness value | 1 Byte | CRT | |
| 89 | Group 15 | Fault ballast | 1 Bit | CRT | |
| 89 | Group 15 | Fault lamp | 1 Bit | CRT | |
| 89 | Group 15 | Fault lamp or ballast | 1 Bit | CRT | |
| 90 | Group 16 | Switch/Status | 1 Bit | CRWT | |
| 90 | Group 16 | Switch | 1 Bit | CW | |
| 91 | Group 16 | Activate Staircase lighting | 1 Bit | CW | |
| 91 | Group 16 | Act. Staircase lighting/Status | 1 Bit | CRWT | |
| 91 | Group 16 | Activate function Slave | 1 Bit | CW | |
| 91 | Group 16 | Activate Slave/Status | 1 Bit | CRWT | |
| 91 | Group 16 | Activate function Sequence | 1 Bit | CW | |
| 91 | Group 16 | Activate Sequence/Status | 1 Bit | CRWT | |
| 91 | Group 16 | Status switch | 1 Bit | CRT | |
| 92 | Group 16 | Relative dimming | 4 Bit | CW | |
| 93 | Group 16 | Brightness value | 1 Byte | CW | |
| 93 | Group 16 | Brightness value/Status | 1 Byte | CRWT | |
| 94 | Group 16 | Status Brightness value | 1 Byte | CRT | |
| 94 | Group 16 | Brightness value of Slave | 1 Byte | CW | |
| 95 | Group 16 | Fault ballast | 1 Bit | CRT | |
| 95 | Group 16 | Fault lamp | 1 Bit | CRT | |
| 95 | Group 16 | Fault lamp or ballast | 1 Bit | CRT | |
| 96 | Output A | Switch | 1 Bit | CW | |
| 96 | Output A | Switch/Status | 1 Bit | CRWT | |
| 97 | Output A | Status switch | 1 Bit | CRT | |
| 98 | Output A | Relative dimming | 4 Bit | CW | |
| 99 | Output A | Brightness value | 1 Byte | CW | |
| 99 | Output A | Brightness value/Status | 1 Byte | CRWT | |
| 100 | Output A | Status Brightness value | 1 Byte | CRT | |
| 101 | Output A | Fault lamp | 1 Bit | CRT | |
| 102 | Output A | Fault ballast | 1 Bit | CRT | |
| 103 | Output A | Fault DALI | 1 Bit | CRT | |
| 104 | Output A | Fault group/device code | 1 Byte | CRT | |
| 105 | Output A | Number of faults | 1 Byte | CRT | |
| 106 | Output A | No. Group/device fault | 1 Byte | CRT | |
| 107 | Output A | Switch up next fault alarm | 1 Bit | CW | |
| 108 | Output A | Disable sending of fault alarm | 1 Bit | CW | |
| 109 | Output A | Time for dimming changeable | 1 Byte | CW | |
| 110 | Output A | Detect ballasts | 1 Bit | CW | |
| 111 | Output A | Burn-in lamps/Status | 1 Bit | CRWT | |
| 111 | Output A | Burn-in lamps | 1 Bit | CW | |
| 112 | Scenes 1..14 | 8 bit Scene | 1 Byte | CW | |
| 113 | Scene 1/2 | Recall Scene | 1 Bit | CW | |
| 114 | Scene 3/4 | Recall Scene | 1 Bit | CW | |
| 115 | Scene 5/6 | Recall Scene | 1 Bit | CW | |
| 116 | Scene 7/8 | Recall Scene | 1 Bit | CW | |
| 117 | Scene 9/10 | Recall Scene | 1 Bit | CW | |
| 118 | Scene 11/12 | Recall Scene | 1 Bit | CW | |
| 119 | Scene 13/14 | Recall Scene | 1 Bit | CW | |
| 120 | Scene 1/2 | Store Scene | 1 Bit | CW | |
| 121 | Scene 3/4 | Store Scene | 1 Bit | CW | |
| 122 | Scene 5/6 | Store Scene | 1 Bit | CW | |
| 123 | Scene 7/8 | Store Scene | 1 Bit | CW | |
| 124 | Scene 9/10 | Store Scene | 1 Bit | CW | |
| 125 | Scene 11/12 | Store Scene | 1 Bit | CW | |
| 126 | Scene 13/14 | Store Scene | 1 Bit | CW | |
| 127 | General | Block manual Operation/Status | 1 Bit | CRWT | |
| 128 | General | Request status values | 1 Bit | CW | |
| 129 | General | Acknowledge faults | 1 Bit | CW | |
| 130 | General | Fault Gateway supply | 1 Bit | CRT | |
| 131 | General | Diagnostics | 2 Bytes | CRT | |
| 132 | General | Request Diagnostics | 1 Byte | CW | |
| 133 | General | In Operation | 1 Bit | CT |
Parameters (163)
| Parameter | Type | Default |
|---|---|---|
| Converted from version 0.3 | unsignedInt 0…255 | 3 |
| Enable manual operation Object "Block Manual operation/Status" | list | yes |
| Enable automatic DALI addressing | list | yes |
| Send object "In Operation" | list | no |
| Telegram will repeated all in s [1...65,535] | unsignedInt 1…65535 | 60 |
| Limit number of sent telegrams | list | no |
| Time between two response telegrams in s [1...255] | unsignedInt 1…255 | 20 |
| in period | list | 1 s |
| "Acknowledge faults" | list | no - acknowledge is not necessary |
| "Fault Gateway supply voltage" | list | no |
| Send | list | after a change |
| "Request Status values" | list | no |
| Request with object value | list | 1 |
| Enable function Scene | list | no |
| Enable Sequence time curve (one curve per gateway) | list | no |
| Enable Staircase lighting time curve (one curve per gateway) | list | no |
| IMPORTANT: Scene 13 and 14 are used for function Staircase lighting! | list | <--- IMPORTANT |
| Devices Channel A | list | enabled |
| Brightness value when turned ON | list | 100 % (255) |
| Permit channel to be turned on via dim telegram | list | yes |
| Permit channel to be turned OFF via dim telegram | list | yes |
| Allow switching OFF via Brightness value | list | yes |
| Dim period to reach turn on or off Brightness value (Obj. "Switch") | list | 2 s |
| Dimming speed, time for 0...100 % (Object Relative dimming) | list | 5.5 s |
| Dim period to reach set Brightness value (Object "Brightness value") | list | 2 s |
| Enable function lamp Burn-in object "Burn-in lamps" | list | no |
| Lamp Burn-in period in hours [1..254] | unsignedInt 1…254 | 100 |
| Status of Burn-in | list | no |
| send | list | after a change |
| Status response for different status in the output: | list | ON |
| OFF, in case of different states a 0 will be sent | list | <--- NOTE |
| ON, in case of different states a 1 will be sent | list | <--- NOTE |
| Status response of Switching state of the DALI output | list | no |
| Switch value for different values in the output | list | ON |
| Status response of Brightness value of the DALI output | list | no |
| Brightness value for different values in the output | list | average brightness of all lamps in the output |
| "Fault DALI" | list | no |
| "Fault lamp" | list | no |
| "Fault ballast" | list | no |
| "Fault group/device Code" enable encoded fault message | list | no |
| Send no. of the failed group or failed or failed device | list | group orientated |
| Enable Lighting group 1...4 | list | yes |
| Enable Lighting group 5...8 | list | no |
| Enable Lighting group 9...12 | list | no |
| Enable Lighting group 13...16 | list | no |
| DALI device will set automatically in gr. 16, if it is no member of an other | list | no |
| Minimal Brightness value | list | lowest brightness of all lamps in the group |
| Maximum Brightness value | list | highest brightness of all lamps in the group |
| Brightness value on ballast Power on (ballast supply voltage) | list | average brightness of all lamps in the group |
| Name | text | G1 |
| Select additional function | list | none |
| Brightness value when turned ON (only if add. fct. is not activated) | list | 100 % (255) |
| Minimal Brightness value | list | 1 % (3) |
| Maximum Brightness value | list | 100 % (255) |
| Enable with function Burn-in (Object "Burn-in lamps/Status") | list | no |
| Dimming speed, time for 0...100 % is the same as set for A: Central | list | <--- NOTE |
| Char. adjustment of DALI lighting curve | list | no, logarithm DALI lighting curve |
| Status response of Switching state of the lighting group | list | no |
| Switch value for different values in the group | list | ON |
| Status response of Brightness value of the lighting group | list | no |
| Brightness value for different values in the group | list | average brightness of all lamps in the group |
| Status response of lamp/ballast fault | list | no |
| Content of communication object | list | Fault lamp or ballast |
| Reaction on KNX bus voltage failure | list | no change |
| Reaction on download or KNX bus voltage recovery | list | no change |
| Reaction on DALI bus voltage failure or failure gateway supply voltage | list | no change |
| Reaction on DALI bus voltage recovery or recovery gateway supply voltage | list | no change |
| Saving Brightness value every 2 sec. NOTE: possibility storage no. ballast | list | <--- NOTE |
| Brightness value when ballast Power on (Ballast supply voltage recovery) | list | 100 % (255) |
| One Staircase time curve per gateway. Enable fct. on para. site "General" | list | <--- NOTE |
| Dim period to reach set Brightness value (Object "Slave Brightness value") | list | 2 s |
| One Sequence time curve per gateway. Enable fct. on para. site "General" | list | <--- NOTE |
| Brightness value after switching on | list | 100 % (255) |
| Dimming to Basis brightness | list | 30 % (77) |
| switch | list | no reaction |
| Switch on | list | no reaction |
| Brightness value | list | no reaction |
| Relative dimming | list | no reaction |
| Recall Scene | list | no reaction |
| Function Staircase lighting after gateway supply voltage recovery | list | active |
| Function Slave after gateway supply voltage recovery | list | active |
| Function Sequence after gateway supply voltage recovery | list | active |
| Function Staircase lighting after download or KNX bus voltage recover | list | active |
| Function Slave after download or KNX bus voltage recovery | list | active |
| Function Sequence after download or KNX bus voltage recovery | list | active |
| Status response of function Staircase lighting of the lighting group | list | no |
| Status response of function Slave of the lighting group | list | no |
| Status response of function Sequence of the lighting group | list | no |
| Status resposne for diff. Staircase lighting fct in overlapping groups: | list | Function active |
| Status response for different Slave fct. in overlapping groups: | list | Function active |
| Status response for different Sequence fct in overlapping groups: | list | Function active |
| Name | text | G2 |
| Name | text | G3 |
| Name | text | G4 |
| Status response of Switching state | list | no |
| Status response of Brightness value | list | no |
| Name | text | G5 |
| Reaction on DALI bus voltage failure or failure Gateway supply voltage | list | no change |
| Name | text | G6 |
| Switch value for different values in the group | list | average brightness of all lamps in the group |
| Name | text | G7 |
| Name | text | G8 |
| Name | text | G9 |
| Name | text | G10 |
| Send Switch status response (Object "Switch/Status") | list | after a change |
| Value for different switch Status in a group | list | ON |
| Send no. of the failed group or failed or failed device | list | ON |
| Name | text | G11 |
| Name | text | G12 |
| Name | text | G13 |
| Name | text | G14 |
| Status response for different status in overlapping groups: | list | Function active |
| Name | text | G15 |
| Name | text | G16 |
| Scenes | list | enabled |
| Enable Scene 1/2 | list | no |
| Enable Scene 3/4 | list | no |
| Enable Scene 5/6 | list | no |
| Enable Scene 7/8 | list | no |
| Enable Scene 9/10 | list | no |
| Enable Scene 11/12 | list | no |
| Enable Scene 13/14 | list | no |
| Transition time for Scene | list | 2 s |
| Overwrite Scene on download or KNX bus voltage recovery | list | yes |
| Group 1 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 2 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 3 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 4 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 5 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 6 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 7 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 8 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 9 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 10 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 11 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 12 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 13 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 14 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 15 Brightness value of Scene | list | no change (no member in this Scene) |
| Group 16 Brightness value of Scene | list | no change (no member in this Scene) |
| Number of cycles (0...255, 0 = not limited)) | unsignedInt 0…255 | 1 |
| Step 1 | list | Scene 1 |
| Transition time, replaces transition time in the Scene | list | 2 s |
| Runtime | list | 5 min |
| Enable next Sequence step assignments | list | no |
| Brightness value and the group member will defined in the Scene | list | <--- NOTE |
| Step 2 | list | Scene 2 |
| Step 3 | list | Scene 3 |
| Step 4 | list | Scene 4 |
| Step 5 | list | Scene 5 |
| Step 6 | list | Scene 6 |
| Step 7 | list | Scene 7 |
| Step 8 | list | Scene 8 |
| Step 9 | list | Scene 9 |
| Step 10 | list | Scene 10 |
| IMPORTANT: Scene 13 and 14 are used for function Staircase lighting! | list | <--- NOTE |
| Time for dimming up (soft start) | list | 2 s |
| Staircase lighting time | list | 2 min |
| Time for dimming down after enlightment (Warning before light turned off) | list | 5.5 s |
| Basis brightness hold time | list | 10 s |
| The parameterized min./max. dimming values apply to all functions, e.g. | list | <--- NOTE |
| If characteristics f. overlapping groups are not parameterised, the lighting | list | <--- NOTE |
| In group 3 function Staircase light- ing is set, in group 7 function Slave. | list | <--- EXAMPLE |
Version history
| Application | App no | Fingerprint | First seen | Size | File |
|---|---|---|---|---|---|
| Switch Dim Groups 1f DALI/1.3 1.3 latest | $A057 | 5094 | 2026-11-25 | 541 KB | Download |
About this file
This is the official ETS product database for the ABB AG - BUSCH-JAEGER DG/S1.16.1 DALI-Gateway,16G,1f,MDRC (6197/44), published by the manufacturer in the KNX online catalog. To use it, open ETS, go to Catalogs → Import and choose the downloaded .knxprod file. The device then appears in your catalog and can be added to a project. Older versions are kept so existing projects can be matched to the application program they were commissioned with.
More from ABB AG - BUSCH-JAEGER
- UD/S4.210.2.11 LED Dimmer 4x210W 2CKA006197A0046
- UD/S6.210.2.11 LED Dimmer 6x210W 2CKA006197A0048
- 6197/xx Universal Dimming Actuator 6fold, MDRC 6197/14-101
- 6197/xx-101 Universal Dimming Actuator 4fold, MDRC 6197/1x-101
- 6197/41 DALI-Gateway,1fach,REG 6197/41
- 6197/45 DALI Gateway, Basic, 1f, MDRC 6197/45
- 6197/46 DALI-Gateway,Basic,2f,MDRC 6197/46
- IPS/S3.5.11 IP Interface Secure,MDRC 2CDG 110 204 R0021
- FCC/S1.1.2.11 Fan Coil Controller,PWM,3-speed,manual operation,MDRC 2CDG 110 211 R0021
- FCC/S1.2.2.11 Fan Coil Controller,0-10V,3-speed,manual operation,MDRC 2CDG 110 213 R0021
- FCC/S1.3.2.11 Fan Coil Controller,0-10V,0-10V,manual operation,MDRC 2CDG 110 215 R0021
- VC/S4.1.11 Valve Drive Controller,4-fold,MDRC 2CDG 110 216 R0021